TDL Industrial Automation · Last updated:

From Rockwell's 1834-UM001C user manual, 1834-TD001B technical data and product page: the 1834-AENTR gateway, the seven-conductor 1486-CBL flat cable, interface modules for 100-E contactors and 800F push buttons, the 25 m and 40-node limits, how the system fits a Logix project, the coil power budget, and when it is worth using in a new panel.

In a conventional control panel, every motor starter and push button is wired point to point to an I/O card. Rockwell Automation's EtherNet/IP In-cabinet Solution replaces much of that control wiring with one flat cable that carries power, single pair Ethernet and device position to the starters and push buttons in the panel, behind a gateway on the plant's EtherNet/IP network. Rockwell announced it in a press release dated 20 May 2025. This article, based on Rockwell's documents, explains what the system consists of, how it fits a Logix project, the limits its manuals set, and when it is worth considering.

1. The problem it addresses

Rockwell's brochure describes traditional panels as burdened with point-to-point wiring, configuration time and hard troubleshooting (1834-SP001A, p. 4). The user manual states the aim: the system gives access to identity, state, runtime and maintenance information from devices in the panel, eliminates control wiring, reduces panel space and reduces commissioning effort (1834-UM001C, p. 9).

Power wiring stays: the motor circuit still runs through breaker, contactor and overload relay. What moves onto the cable is the control side: coil power, commands, status and diagnostics.

2. What the system consists of

The user manual lists the supported devices (1834-UM001C, pp. 11–14; product page):

Catalog number Role
1834-AENTR Gateway between a standard EtherNet/IP network and the In-cabinet bus; primary power source of the bus
1834-SUP-PWR Supplemental power tap that injects extra switched power into the bus
1486-CBL-10M / -25M / -100M Flat media cable, 10 m, 25 m or 100 m lengths
1486-CON-P1, -P2L, -P2R, -S1, -T1, -D1 Connectors: device plug, left and right end plugs, splicer, terminator, dust cover
100-E-INT-D / 104-E-INT-D Interface module on a non-reversing / reversing 100-E starter, with a discrete input for interlocking
100-E-INT-X / 104-E-INT-X As the -D version, plus a data port to a 140ME breaker or an E100 overload relay
800F-INT Interface module for a non-illuminated 22 mm 800F push button
800F-INT-L Interface module for an illuminated 800F push button or pilot light

The manual's examples combine a 140MT or 140ME motor protection circuit breaker with a 100-E contactor and its interface module, with an E100 overload relay in three-component starters (1834-UM001C, pp. 9–11). The technical data covers 100-E contactors from 100-E09 to 100-E96 (1834-TD001B, p. 17).

3. One flat cable: power, data and position

The 1486-CBL is a seven-conductor flat cable for a multi-drop bus. Two conductors carry switched power for coil control (SP+ and SP-), two carry network power for the communication interfaces (NP+ and NP-), two are the single pair Ethernet (SPE+ and SPE-), and the seventh, the Select Line, gives each device its position on the cable (1834-UM001C, p. 23; 1834-TD001B, p. 8).

EtherNet/IP In-cabinet: from controller to motor startersFive layers from top to bottom. A Logix 5000 controller on a standard EtherNet/IP network: Studio 5000 Logix Designer project; each device on the bus appears in the Controller Organizer and generates I/O tags automatically. An Ethernet cable goes to the gateway's two RJ45 ports; in a Device Level Ring the gateway is a ring participant only. The 1834-AENTR gateway at position 0: 24 V DC input, Network Power and Switched Power out to the bus; local address 192.168.1.1, devices behind it get the next addresses; the gateway terminates its end of the bus. The 1486-CBL seven-conductor flat cable: SP+ and SP- for coil control, NP+ and NP- for communication interface power, SPE+ and SPE- for single pair Ethernet, Select Line for device position; at most 25 m from gateway to terminator; 1486-CON connectors at least 50 mm apart, 100 mm recommended. End nodes, up to 39 besides the gateway: 100-E or 104-E contactors with 100-E-INT-D, -X or 104-E-INT-D, -X modules, combined with a 140MT or 140ME motor protection circuit breaker; the data port of the -X version connects an E100 or a 140ME; 800F push buttons with 800F-INT, pilot lights with 800F-INT-L; optional 1834-SUP-PWR adds Switched Power. The bus ends at a 1486-CON-T1. Based on Rockwell Automation 1834-UM001C and 1834-TD001B.EtherNet/IP In-cabinet: from controller to motor startersLogix 5000 controllerstandard EtherNet/IP networkStudio 5000 Logix Designer projecteach device on the bus appears in the Controller Organizerwith automatic I/O tagsEthernet cable, two RJ45 ports (DLR: ring participant only)1834-AENTR gatewayposition 0 on the bus24 V DC input; Network Power (NP) and Switched Power(SP) outlocal address 192.168.1.1; devices behind it get thenext addressesterminates its end of the bus1486-CON connector1486-CBL flat cableseven conductors,25 m maximumSP+ and SP-: contactor coil controlNP+ and NP-: communication interface powerSPE+ and SPE-: single pair EthernetSelect Line: device position on the cable1486-CON connectors at least 50 mm apart,100 mm recommended1486-CON-P1 to each moduleEnd nodesup to 39 besides the gateway100-E / 104-E contactor with an -INT-D or -INT-X module,with a 140MT or 140ME breakerdata port of the -X version: E100 overload relay or 140ME800F push button with 800F-INT, pilot light with 800F-INT-Loptional: 1834-SUP-PWR adds Switched Powerend of cable1486-CON-T1 terminatorterminates the far endthe gateway already terminates the other endBased on Rockwell Automation, 1834-UM001C (09/2026) pp. 9–13, 18, 22–26, 46–47 and 1834-TD001B(04/2026) pp. 3, 8 (read 23 November 2026). Figure: drawn by TDL, simplified.
Figure 1: EtherNet/IP In-cabinet: from controller to motor starters. On a phone, swipe sideways to see the whole figure.

The limits the manuals give for one bus:

  • One gateway and as many as 39 more devices; the gateway counts as one of the 40 node connections (1834-UM001C, pp. 12, 22).
  • At most 25 m (82 ft) from the gateway connection to the 1486-CON-T1 terminator. Both ends must be terminated; the gateway terminates its own end (p. 22).
  • Connectors at least 50 mm apart, with 100 mm or more recommended to leave cable slack (pp. 22, 35).
  • Cable and connectors are IP20 and for in-cabinet use only, in UL 508A industrial control panels, UL 845 motor control centers and similar ordinary locations (1834-TD001B, pp. 6, 9).
  • No bending along the cable's length; route it away from strong electric or magnetic fields (1834-TD001B, p. 9), with extra insulation where it crosses a door hinge (1834-UM001C, p. 32).

Two rules matter for maintenance. 1486-CON connectors cannot be added to or removed from an active system, and only one device can be removed at a time (1834-UM001C, p. 24). Modules are disconnected from power before removal or replacement, because interrupting the flat cable can cause unintended operation or machine motion (p. 32).

4. How it sits on EtherNet/IP and in Logix

The 1834-AENTR connects to a standard EtherNet/IP network through two RJ45 ports, which can join a Device Level Ring as a ring participant only, never as supervisor (1834-UM001C, pp. 12, 18). The gateway has two IP addresses: its address on the plant network, set by rotary switches or DHCP, and the local In-cabinet address, which starts at 192.168.1.1 (p. 46). On first power-up the gateway assigns the devices behind it local addresses in ascending order; once a reference topology is saved, it uses that topology (p. 47).

In the Studio 5000 Logix Designer project, the gateway is configured first, then the devices (p. 47). Each device on the bus appears in the Controller Organizer and generates its I/O tags automatically (p. 11). Other functions the manual describes:

  • Reference topology. The project stores which device should sit at which position; the gateway can warn on a device missing, inserted, changed or mismatched at a position (pp. 51–52).
  • Automatic Device Configuration. Always enabled: the controller downloads the configuration to the gateway and end nodes each time it connects, which shortens device replacement (p. 19).
  • Peer commands. Up to seven per device: devices act on each other's data without the controller, for example a push button starting a starter. The manual does not recommend combining CIP Security with peer-to-peer communication (pp. 14, 16).
  • Diagnostics. Predictive maintenance views show remaining or elapsed life for the gateway and the devices (pp. 62–63, 94), and Logix Automatic Diagnostics, enabled by default from controller firmware revision 33, passes device diagnostics to HMIs (p. 180).

The manual's planning example shows a 5580 or 5380 controller, a Stratix 5700 switch and Studio 5000 Logix Designer v37 or later (p. 22). Firmware, Add-on Profiles and EDS files are downloaded from Rockwell's Product Compatibility and Download Center (p. 8). Its security chapter, written for IEC 62443-4-2 SL 1 requirements, asks for gateway firmware revision 1.001 or later and compensating countermeasures elsewhere in the system (pp. 159, 163); see also CIP Security on ControlLogix 5580 and CompactLogix 5380.

5. Power budget

The gateway feeds two channels from one 24 V DC supply: network power for every interface module, and switched power for the 100-E and 104-E coils. Each has 4 A continuous. The technical data rates both outputs at 8 A for no longer than 5 s, and the user manual describes this boost on switched power, with a properly sized 10 A supply, to cover coil in-rush (1834-TD001B, p. 4; 1834-UM001C, pp. 25–26). The manual's planning figures (1834-UM001C, pp. 26–28):

  • Each interface module draws about 30 to 50 mA of network power; a full bus of 40 nodes needs 1.2 to 2 A.
  • The gateway provides up to 96 W of hold-in and 196 W of peak power for contactor coils.
  • Switched power depends on the number of contactors, their coil types (EJ and QJ are low consumption) and how many start together.

In the manual's example, 15 contactors 100-E38 with QJ coils starting together need 25.5 W hold-in and 90 W in-rush. When switched power runs short, a 1834-SUP-PWR adds another 4 A continuous with the same 8 A boost; it counts as one node on cables up to 12 m and two on cables of 13 to 25 m, and its zone control can disable coil control in a safety or maintenance lockout (pp. 13, 29).

Temperature matters too: for a non-ventilated enclosure the technical data gives 22 °C ambient without derating and 40 °C with derating (42 °C and 60 °C open), and NP and SP current is derated above 40 °C (1834-TD001B, pp. 3–5).

6. When it is worth considering

The system fits a new panel with many small starters and operator devices of the supported families, such as a motor control panel or a small MCC on a Logix system, where control wiring is a large share of the work. Each gateway covers 25 m and 40 nodes, so a larger panel needs more gateways.

In TDL's view it is seldom worth it on an existing panel: other starters and push buttons would have to be replaced and the panel rebuilt around the flat cable, so it is better considered when a panel is replaced anyway. It is also an in-cabinet bus, not a way to reach field devices; for those, see choosing a remote I/O adapter on EtherNet/IP.

What we check first

This is TDL's practice, not a Rockwell Automation requirement.

  • The device list: every starter and operator must be one the bus supports, and anything else stays hard-wired.
  • Controller, firmware and Studio 5000 versions against the Product Compatibility and Download Center, and the Add-on Profiles on the engineering workstations.
  • A power budget per bus: nodes, contactor coil types, starts at the same time, and whether a 1834-SUP-PWR is needed.
  • Cable length and position plan within 25 m and 40 nodes, connector spacing, the door hinge crossing, and the panel temperature.
  • The DLR design if the gateway joins a ring, and the IP plan on the plant side.
  • Safety circuits are designed on their own. The documents we read do not present the In-cabinet bus as a safety function.
  • Spares, and maintenance staff who know devices are changed with the bus powered down.

How TDL approaches it

TDL designs and builds control panels with factory acceptance testing through our control panel engineering service, and designs EtherNet/IP networks on Stratix managed switches with DLR rings through our industrial networks and OT security service. For a new Logix panel, TDL can evaluate the EtherNet/IP In-cabinet Solution against a hard-wired design on the points above. Older networks are covered in DeviceNet and ControlNet to EtherNet/IP migration and DeviceNet to EtherNet/IP; ring options in DLR vs PRP.

Frequently asked questions

What is single pair Ethernet in the EtherNet/IP In-cabinet Solution?

It is the Ethernet link carried on one pair, conductors SPE+ and SPE-, of the seven-conductor 1486-CBL flat cable. The same cable carries network power, switched power for contactor coils and a select line for device position.

How many devices and how much cable can one gateway handle?

One 1834-AENTR gateway supports 40 node connections including itself, so up to 39 devices, and at most 25 m of flat cable from the gateway to the 1486-CON-T1 terminator.

Which devices can connect to the bus?

Bulletin 100-E and 104-E contactors with 100-E-INT or 104-E-INT interface modules, 800F push buttons and pilot lights with 800F-INT modules, and the 1834-SUP-PWR power tap. The -X interface modules add a data port to an E100 overload relay or a 140ME breaker.

Can a device be replaced while the bus is running?

No. The manual says connectors cannot be added to or removed from an active system, and modules are disconnected from power before removal, because interrupting the cable can cause unintended operation. Automatic Device Configuration then downloads the configuration to the new device.

Can the gateway sit in a DLR ring?

Yes, through its two RJ45 ports, but only as a ring participant. Another device on the ring must be the ring supervisor.

Sources

  • Rockwell Automation, 1834-UM001C-EN-P, EtherNet/IP In-cabinet System User Manual, 09/2026 — pp. 8–9, 11–14, 16, 18–19, 22–29, 32, 35, 46–47, 51–52, 62–63, 94, 159, 163, 180
  • Rockwell Automation, 1834-TD001B-EN-P, EtherNet/IP In-cabinet System Specifications (Technical Data), 04/2026 — pp. 3–6, 8–9, 17
  • Rockwell Automation, 1834-SP001A-EN-P, EtherNet/IP In-cabinet Solution brochure, 05/2025 — p. 4
  • Rockwell Automation, EtherNet/IP In-cabinet Solution, product page with catalog list
  • Rockwell Automation, press release, 20 May 2025, launch of the EtherNet/IP In-cabinet Solution

Read 23 November 2026. This article paraphrases the sources and quotes them only briefly; read the current manual and technical data before designing a panel. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.