Securing Rockwell Automation (Allen-Bradley) PLCs in a plant starts with a few basics: keep PLCs off the internet, block EtherNet/IP at the edge of the control zone, leave the mode keyswitch in RUN during normal operation, update firmware according to the vendor's security advisories, and keep backups with change detection. This article summarises what Rockwell Automation and CISA publish, and how to apply it in a running plant.
Where the risk is
In May 2024 Rockwell issued notice SD1672: customers should immediately check for devices facing the public internet and remove that connectivity where devices are not designed for it, citing heightened geopolitical tensions and cyber activity. The notice lists related CVEs in Logix controllers, Logix Designer, 1756 communication modules and FactoryTalk.
The clearest example is
Without overstating it: in several advisories (for example
Layers of protection from the vendor documents
| Layer | What to do | Basis |
|---|---|---|
| No internet exposure | Remove every path from PLCs, HMIs and engineering stations to the public internet | SD1672; CISA fact sheet 05/2025 |
| Block ports at the edge | Block or restrict TCP and UDP 44818 and 2222 from outside the control zone | PN1042; |
| Segmentation | Separate control and office networks through an IDMZ | |
| Remote access | Up-to-date VPN, two-factor authentication, role-based access, local on/off control | |
| Mode switch | RUN with the key removed in normal operation | |
| CIP Security | Device authentication, integrity and encryption on EtherNet/IP | |
| Firmware | Update per advisories, download from the official portal | |
| Backup and change detection | Versioned backups, comparison, log monitoring |
Keep PLCs off the internet
Start with an inventory of every IP device and every path out: the machine builder's 4G modem, a router with port forwarding, a dual-homed engineering laptop, preinstalled remote-control software. The May 2025 fact sheet from CISA, FBI, EPA and DOE puts removing OT connections to the public internet first, followed by changing default passwords. Where disconnection is not yet feasible, SD1672 asks customers to apply Rockwell's security best practices in the meantime.
Do not expose EtherNet/IP outside the control zone
Advisory PN1042 recommends blocking traffic to CIP-based devices from outside the operational zone by blocking or restricting TCP and UDP ports 2222 and 44818 on a firewall or similar security appliance;
If MES or reporting on the office network needs PLC data, do not open 44818 through the firewall.
Segmentation: zones and conduits
In practice: one VLAN/subnet per line; per-flow firewall rules between zones; the IDMZ as the only path to the office; AD, DNS and NTP replicated inside the Industrial Zone; and the ability to cut access at the firewall. IEC 62443 security levels need a risk assessment per system.
Controlled remote access
CISA and Rockwell allow remote access under conditions: an up-to-date VPN, multi-factor authentication, role-based access, dormant accounts disabled. For Stratix 4300 with FactoryTalk Remote Access,
Mode keyswitch: RUN, REM, PROG
According to the ControlLogix 5580 user manual (
- RUN: online edits, program downloads and firmware updates are not allowed.
- REM: allows mode changes (Remote Run, Remote Program, Remote Test) and online edits from Logix Designer.
- PROG: Program mode for local work; the controller does not execute the program.
Rockwell recommends RUN with the key removed during normal operation, and REM or PROG only for commissioning, maintenance or program changes.
Two notes. With the switch in REM, anyone who can reach the network with Logix Designer may be able to change the program;
CIP Security
CIP Security, based on the ODVA standard, lets EtherNet/IP devices authenticate each other and provides data integrity and encryption. Policies are set in FactoryTalk Policy Manager, workstations connect through FactoryTalk Linx; RSLinx Classic cannot be used. The FactoryTalk Linx help lists minimum firmware, for example ControlLogix 5580 from 32.011 and CompactLogix 5380 from 34.011; the
For ControlLogix 5570 at firmware v31 and later, that advisory gives the option of adding a
Firmware per security advisories
Rockwell's Trust Center filters advisories by product, severity and CISA KEV status, with email alerts. Two examples:
ICSA-23-193-01 / PN1633:1756-EN2T , EN2TR, EN3TR and EN4TR modules need specific firmware (11.004 for the newer series such as EN2T Series D, EN2TR Series C and EN3TR Series B; 5.002 for EN4TR; signed 5.029 for older series). Once on signed firmware, you cannot revert to unsigned versions.ICSA-24-214-09 : a bypass of the ControlLogix 5580 Trusted Slot feature; fixed in V32.016, V33.015, V34.014, V35.011 or later; some olderEN2T-family modules have no fix and must move to Series D.
Backup and change detection
Where a vulnerability cannot be patched, Rockwell recommends monitoring changes with the Controller Log (v17+), Change Detection in Logix Designer (v20+) or FactoryTalk AssetCentre (
Order of work in a running plant
Start with the low-cost layers: inventory and removing internet paths, the firewall, the key in RUN, scheduled backups. Firmware updates go into planned shutdowns; CIP Security and detailed segmentation belong in the upgrade plan.
Network and OT security design: industrial networks and OT security. Need an engineer on site: request support.
Frequently asked questions
Will HMI or SCADA lose data with the keyswitch in RUN?
According to
Do PLCs on an internal-only network still need attention?
Yes, at a different level. The advisories assume the attacker can reach the network; if the control network is flat and shared with the office, an infected office PC can still reach the PLC. That is why segmentation matters.
What if older controllers do not support CIP Security?
Rely on the other layers: segmentation, firewalls, the RUN position, limited External Access and change monitoring. When planning an upgrade, consider the
Which ports should be blocked to protect Rockwell PLCs at the control zone boundary?
Advisory PN1042 recommends blocking or restricting TCP and UDP ports 2222 and 44818 from outside the operational zone on a firewall or equivalent security device;
Can CVE-2021-22681 on Logix controllers be patched?
No. Rockwell states that the vulnerability in
Sources
- Rockwell Automation,
SECURE-RM001J-EN-P , System Security Design Guidelines Reference Manual, 11/2025 — chapter 3 "Secure Networks and Communication" (Logical Zones, IDMZ, CIP Security, Remote Access), chapter 4 "Harden the Control System", chapter 5 "Manage User Access" (Control Data Access), chapter 6 "Monitor and Recover" - Rockwell Automation,
1756-UM543 , ControlLogix 5580 and GuardLogix 5580 Controllers User Manual — "Change the Operation Mode" (keyswitch), "Controller Operation Modes", "Secure Controller Systems"; online edition on Rockwell Automation Documentation - Rockwell Automation, SD1672: IMPORTANT NOTICE: Rockwell Automation Reiterates Customer Guidance to Disconnect Devices from the Internet to Protect from Cyber Threats, 21/05/2024, rev 1.1 updated 07/08/2025
- CISA, Rockwell Automation Encourages Customers to Assess and Secure Public-Internet-Exposed Assets, 21/05/2024
- CISA,
ICSA-21-056-03 : Rockwell Automation Logix Controllers (Update A),CVE-2021-22681 - CISA,
ICSA-23-193-01 : Rockwell Automation Select Communication Modules,CVE-2023-3595 /3596 - Rockwell Automation, PN1633: Remote Code Execution and Denial-of-Service Vulnerabilities in Select Communication Modules, 12/07/2023
- CISA,
ICSA-24-214-09 : Rockwell Automation Logix Controllers,CVE-2024-6242 , 01/08/2024 - Rockwell Automation, PN1042: MicroLogix 1400 Controllers, 1756 ControlLogix EtherNet/IP Communication Modules Denial of Service, 06/11/2018
- CISA, FBI, EPA, DOE, Primary Mitigations to Reduce Cyber Threats to Operational Technology (fact sheet), 05/2025
- Rockwell Automation, FactoryTalk Services Platform 6.60 help, FactoryTalk Linx Help: "Software and hardware" (CIP Security), on Rockwell Automation Documentation
- Rockwell Automation, Trust Center: Security Advisories
Read 25 October 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.