Wiring and grounding PWM drives: shielded motor cable, 360° shield termination, cable spacing, long leads

TDL Industrial Automation · Last updated:

From Rockwell's DRIVES-IN001Q: why a drive cable is not an ordinary power cable, choosing unshielded, shielded or armored motor cable, PE grounding and the common mode noise return path, 360° shield termination instead of pigtails, spacing between power and signal cables, reflected wave and charging current on long motor leads.

A PWM drive does not send a sine wave down the motor cable. It sends fast voltage pulses, and the cable, the shield and the grounding decide whether the noise from those pulses stays in the drive circuit or reaches the PLC, the analog inputs and the network next to it. For Allen-Bradley drives the reference is Rockwell Automation's Wiring and Grounding for Pulse Width Modulated (PWM) AC Drives (DRIVES-IN001Q-EN-P, June 2019). This article sets out what it says about the motor cable, grounding, shield termination, cable separation and long motor leads. It does not replace the user manual of your drive or the local electrical code.

1. Why a drive cable is not an ordinary power cable

A PWM drive creates motor current by sending DC voltage pulses to the motor. The pulses stress the wire insulation and are a source of electrical noise (DRIVES-IN001Q, p. 23). The fast dV/dt of IGBT drives raises common mode noise, noise induced on signals with respect to ground, at 250 kHz to 6 MHz; the circulating ground currents can couple into signal and logic circuits and cause improper operation (p. 85).

The manual grounds a drive for two reasons, safety and noise containment. They can share a path, but they are different circuits with different requirements (p. 57).

2. Choosing the motor cable

  • Unshielded cable is acceptable where the drive's noise does not disturb other devices, such as communication cards, photoelectric switches or weigh scales, and where no EMC standard (CE, RCM, FCC) requires shielded cable (p. 18).
  • Shielded cable adds a copper braid that contains much of the noise. The manual recommends it near sensitive equipment, with many drives in one place, under EMC regulations or with a lot of networking. The braid needs at least 75% coverage; an extra foil shield helps (p. 19).
  • Armored cable with continuous aluminum armor adds mechanical strength. Continuous welded armor is preferred, interlocked armor is acceptable for shorter runs, and an overall PVC jacket is recommended because armor touching building steel affects noise containment (pp. 20–21).

Use one ground conductor for drives up to 200 Hp (150 kW) and three, spaced symmetrically, above that, all rated for full drive ampacity (pp. 16, 21). Wire insulation must be at least 15 mil (0.4 mm) thick (p. 17). In wet areas Rockwell strongly suggests XLPE: damp or wet THHN (PVC) wire was found to have less than half the corona inception voltage of the same wire when dry (pp. 81, 84). Cables that twist four THHN conductors and wrap them tightly in foil raise cable charging current; unless a length table lists them as tested with the drive, they are not recommended and their performance against the length limits is not known (pp. 20, 93).

Input power cable has no special requirements in general; installations that must meet EMC standards for CE, RCM or FCC use the same shielded cable between drive and transformer as for the motor (p. 22).

3. Grounding: the safety ground and the noise path

The drive PE is connected to building steel, a ground rod, a bus bar or the building ground grid, as the local code requires. The motor frame goes directly to the drive PE with a separate ground conductor, and Rockwell recommends grounding each motor frame to building steel at the motor as well (p. 58).

Rockwell recommends grounded neutral supplies: they give common mode current a controlled path and a consistent line-to-ground reference (p. 29). An ungrounded supply gives the noise current no direct path, so it looks for uncontrolled ones (p. 60). On ungrounded, high-resistance grounded or B-phase grounded systems, disconnect the drive's phase-to-ground MOV circuit and common mode capacitors from ground; in some drives one jumper does both (p. 51).

The manual rates three layouts (pp. 61–62). Wires in conduit are acceptable, but conduit is not the lowest-impedance path for high-frequency noise, and where it touches building steel the noise enters the ground grid. Shielded or armored cable with a PVC jacket on the motor side is effective. PVC-jacketed shielded cable on both input and output is optimal: it returns the noise to the transformer and keeps the ground grid as clean as possible.

With shielded or armored cable, the shield or armor is the main return path: to the drive PE terminal, the cabinet PE bus and the grounded neutral of the supply transformer. Bond the shield or armor to the drive PE with a low-impedance cable or strap, not the smaller ground wire inside the motor cable, or the high-frequency current looks for another path (p. 86).

4. Terminating the shield: 360°, not a pigtail

Shields of motor and input cables are bonded at both ends. Control and signal cable shields are connected at one end only, at the cabinet that contains the signal source, and never to the common of a logic circuit (p. 63).

The cable connector must give 360° contact and low transfer impedance from the shield or armor to the conduit entry plate, at the motor and at the drive cabinet; for CE installations this is mandatory (p. 68). On a painted entry plate, use a connector that cuts through the paint or remove the paint around the hole (p. 68). Inside the panel, a circular clamp with 360° bonding is the preferred method (p. 77).

A pigtail is the least effective method of noise containment. It is not recommended for cables longer than 1 m (3.2 ft) or leaving the panel, in noisy areas, for noise-sensitive signals such as encoder cables, or where strain relief is needed (pp. 69, 78). Run the motor cable in one piece; if a disconnect switch at the motor breaks it, use fully shielded bulkhead connectors (p. 63).

PWM drive wiring: where shields and grounds connectHorizontal diagram, left to right: supply transformer with the X0 neutral grounded; shielded cable with PVC jacket into the drive cabinet; inside the cabinet the AC drive, its PE terminal connected down to the cabinet PE bus; shielded or armored cable with PVC jacket out to the motor, motor frame grounded. 360° shield connectors where the cable enters the cabinet and the motor. Signal and encoder cable on its own route above. A red dashed line is the common mode current return: along the motor cable shield to the drive PE, the cabinet PE bus and back to the transformer neutral. Notes: 1 grounded neutral gives common mode current a controlled path (p. 29); 2 input and motor cable shields bonded at both ends, 360° to the entry plate at the cabinet and at the motor (pp. 63, 68); 3 drive chassis bonded to a zinc-plated panel, PE to the cabinet PE bus, the bus to building steel (pp. 58, 63, 65); 4 motor frame to the drive PE with a separate ground conductor and to building steel at the motor (p. 58); 5 signal and encoder cables on their own route, at least 0.3 m (1 ft) from power wires, crossing at right angles (p. 24); 6 common mode current returns on the shield or armor to the drive PE, the cabinet PE bus and the transformer neutral (p. 86). Based on Rockwell Automation DRIVES-IN001Q-EN-P (June 2019).PWM drive wiring: where shields and grounds connect5signal / encoder cable: own routeTransformersupply, X0neutralgroundedMotorframe andterminal boxDrive cabinetAC drivePE terminalcabinet PE busshielded cable,PVC jacketshielded orarmored,PVC jacket6common mode current return122341Grounded neutral: common mode current gets a controlled path (p. 29).2Input and motor cable shields bonded at both ends, 360° to the entry plate at the cabinet and at themotor (pp. 63, 68).3Drive chassis bonded to a zinc-plated panel; PE to the cabinet PE bus, the bus tobuilding steel (pp. 58, 63, 65).4Motor frame to the drive PE with a separate ground conductor, and to building steel at themotor (p. 58).5Signal and encoder cables on their own route, at least 0.3 m (1 ft) from power wires, crossing atright angles (p. 24).6Common mode current returns on the shield or armor to the drive PE, the cabinet PE bus, then thetransformer neutral (p. 86).Based on Rockwell Automation DRIVES-IN001Q-EN-P (June 2019), pp. 24–86, simplified.Read 23 November 2026. Figure: drawn by TDL.
Figure 1: PWM drive wiring: where shields and grounds connect. On a phone, swipe sideways to see the whole figure.

The cabinet is part of the path too. A zinc-plated steel mounting panel works as the ground plane, the drive chassis is bonded to it, and paint is removed at every mounting and grounding point (pp. 65–66). Use star washers and ring lugs, never one lug stacked on another (pp. 69–70). Do not rely on door hinges: doors 2 m (78 in.) high get two or three braided straps (p. 66).

5. Separating power and signal

Route power and motor leads apart from I/O and signal leads, in separate conduit or with tray dividers (p. 71). Keep control and analog signal wires at least 0.3 m (1 ft) from power wires, run encoder cables in their own conduit, and cross power cables at right angles (p. 24). The spacing table's example: 480 V AC power and 24 V DC logic need 76 mm (3 in.) between steel conduits, or 152 mm (6 in.) in a cable tray (p. 72). For large drives, signal trays stay 1 m (3.2 ft) or more from power and motor wiring (p. 76).

In a shared enclosure, group the drive input and output cables on one side and the PLC and other susceptible equipment on the opposite side, so common mode current returns away from the PLC backplane (p. 73). Do not run power or motor cables in the same conduit as control or communication cables, and route no more than three drives' motor leads in one conduit (p. 74).

6. Long motor cables: reflected wave and charging current

Pulses are reflected back along the motor cable; one IGBT drive output can see transient stress of up to twice the DC bus voltage (p. 83). To protect the motor, cable length is limited. The drive user manual and Appendix A list the limits by drive, rating, carrier frequency and motor insulation (columns for 1000, 1200, 1488 and 1600 V, plus extra columns for some PowerFlex 753/755 and 755T tables), with or without a reactor, damping resistor or 1321-RWR (pp. 84, 98–99).

Long cables also draw charging current. Shielded cable has more capacitance than wires in conduit, a higher carrier frequency raises the current, and drives under 2 Hp are more susceptible to overcurrent trips; the remedies listed are a 2 kHz carrier, shorter cables and an output inductor (pp. 97–98). Install common mode chokes when the drive is more than 22.8 m (75 ft) from the motor or transformer and sensitive circuits with leads over 22.8 m run near it (p. 87).

What we check first

This is TDL's practice, not a Rockwell Automation requirement.

  • The supply: grounded wye, high-resistance ground or ungrounded, and whether the drive's MOV and common mode capacitor jumper must come out according to the drive user manual.
  • The motor cable: type, braid coverage, insulation, and the run length checked against the table for that drive, carrier frequency and motor insulation rating.
  • The glands: a 360° shield connector at the cabinet and at the motor, paint-free entry plates, no pigtails on long or noisy runs.
  • The panel layout: drive power on one side, PLC, analog and network wiring on the other.
  • After installation: every ground connection tight and correct, which the manual asks to check periodically (p. 57).

How TDL approaches it

TDL designs and builds control panels, drive cabinets included, at its Ho Chi Minh City workshop and tests them before shipment through our control panel engineering service, with cable, gland and grounding details from DRIVES-IN001 and the drive user manual. For Crown Da Nang, TDL designed and built the control cabinet with two 90 kW variable-frequency drives for two compressor motors, with PLC and HMI monitoring integrated into the plant control system, and carried out FAT and site commissioning. TDL is a System Integrator in the Rockwell Automation PartnerNetwork. Related: PowerFlex 4/40 to PowerFlex 525, PowerFlex 755 to 755TS, hazardous-area control panels.

Frequently asked questions

Is the motor cable shield grounded at one end or both ends?

Both ends. The manual bonds the shields of motor and input cables at both ends to give common mode current a continuous path. Control and signal cable shields are connected at one end only, at the cabinet with the signal source, never to a logic common.

Is a pigtail acceptable for the motor cable shield?

It is accepted practice in most installations, but the manual calls it the least effective method of noise containment. It is not recommended for cables longer than 1 m (3.2 ft) or leaving the panel, in noisy areas, for encoder or other noise-sensitive cables, or where strain relief is needed. A 360° connector is mandatory for CE installations.

How far apart should signal and power cables run?

At least 0.3 m (1 ft) for control and analog signal wires, crossing at right angles. The spacing table gives 76 mm (3 in.) between steel conduits or 152 mm (6 in.) in a tray for 480 V AC power and 24 V DC logic, and 1 m (3.2 ft) or more for the signal trays of large drives.

How long can the motor cable be?

It depends on the drive, its rating, the carrier frequency and the motor insulation. The drive user manual and Appendix A give the limits; the manual's worked example, a 15 kW PowerFlex 753/755 wall mount drive at 400 V and 2 kHz with a 1488 V motor, allows 365.8 m (1200 ft). Reactors, damping resistors or 1321-RWR extend the limits.

Is unshielded cable in steel conduit good enough?

The manual rates it acceptable for a single drive, with continuous magnetic steel conduit. Conduit is not the lowest-impedance path for high-frequency noise, and where it touches building steel the noise can enter the ground grid. PVC-jacketed shielded or armored cable contains the noise better.

Sources

  • Rockwell Automation, DRIVES-IN001Q-EN-P, Wiring and Grounding for Pulse Width Modulated (PWM) AC Drives, Installation Instructions, June 2019 (supersedes DRIVES-IN001P, September 2017) — pp. 16–24, 29, 51, 57–58, 60–63, 65–78, 81, 83–87, 93, 97–99

Read 23 November 2026. This article paraphrases the source and quotes it only briefly; read the original document and the user manual of your drive before you design or install. The link opens the latest edition in Rockwell's literature library; page numbers refer to the edition cited.