How DLR works
Device Level Ring (DLR) is an EtherNet/IP protocol defined by ODVA to detect and recover from a single point of failure on a ring network (
- Ring supervisor — manages the ring. In normal operation the supervisor blocks one of its two ports so the ring does not form a loop, but still sends beacons out of both ports. When beacons stop travelling all the way round, the supervisor unblocks the port and traffic flows in both directions to either side of the break (p. 7–8, p. 12).
- Ring participant — a device in the ring: forwards data and reports fault locations to the supervisor.
- Redundant gateway (optional) — a switch connecting the ring to the rest of the plant network.
The supervisor function is disabled by default on supervisor-capable devices, and every ring must have at least one supervisor (p. 7). A ring without a supervisor is an uncontrolled loop that can cause a broadcast storm and bring down the whole network (p. 8).
Numbers to remember
| Parameter | Value | Source |
|---|---|---|
| Recommended nodes per ring | up to 50; switch-only ring: up to 24 switches and 230 end devices | |
| Default beacon interval / beacon timeout | 400 µs / 1960 µs | p. 97 |
| Worst-case recovery time (default, 100 Mbps full duplex) | 2890 µs with copper (100 m segments); 3140 µs with fibre (2 km segments) | p. 97 |
| Switchover between two redundant gateways | 14 ms to 6.1 s, depending on the redundancy protocol on the uplink | p. 22 |
Rings above 50 nodes must be tested before going into production: the more nodes, the higher the chance of multiple simultaneous faults and the longer the detection and recovery times (p. 9).
Rules for building a ring
- Only one active supervisor. The device with the highest precedence wins (on a tie, the higher MAC address wins); other supervisors become back-ups. Rockwell recommends configuring at least one back-up supervisor (p. 8–9).
- Only DLR-capable devices connect directly to the ring. Single-port or non-DLR devices connect through a DLR-capable Stratix switch or a
1783-ETAP EtherNet/IP tap (p. 9). - One speed per ring — either 100 Mbps or 1 Gbps. Mixing
1756-EN2TR (100 Mbps) and1756-EN4TR (1 Gbps) is possible, but port speeds must be set as instructed: leave auto-negotiate, except that the link between two adjacent 1 Gbps nodes in a 100 Mbps ring must be fixed at 100 Mbps (p. 10–11). - DLR ports are not configured with STP, REP, EtherChannel, Flex Links, PRP, NAT, 802.1x or MAC-based port security; DLR ports must be full duplex (p. 10).
- Order for closing the ring: wire it as a line, leaving one segment unconnected; configure the supervisor and DLR on every switch; connect the last segment last (p. 14–15).
Connecting the ring to the plant network
There are three common layouts: a device ring (a tap acting as supervisor), a device ring with Stratix switches (the switch acts as supervisor, collects diagnostics and provides the uplink), and a switch-only ring (p. 17–19). With two redundant gateways, this function is only available on Stratix switches, and every device in the ring must be compatible with redundant gateways, otherwise connections may drop when the two gateways swap roles (p. 22, p. 24). Stratix 5400 and 5800 support up to three rings per switch (p. 29).
A broken ring with the machine still running — it must be monitored
This is the point most easily forgotten: after one break, the I/O keeps running normally, so nobody knows the ring has lost its redundancy until a second break occurs. The application should monitor ring status (p. 12). The supervisor reports the status (0 normal, 1 ring fault, 2 unexpected loop, 3 partial fault, 4 rapid fault/restore cycle) and the IP/MAC addresses of the two nodes on either side of the break (p. 95). This information can be read from Logix Designer, the module's web page, Stratix Device Manager, or a ready-made DLR faceplate for the HMI (p. 89–93).
PRP: two parallel networks, no recovery time
The Parallel Redundancy Protocol (IEC
Mandatory rules: never connect LAN A directly to LAN B; the two networks share no switch; a DAN uses the same subnet on both networks; infrastructure switches must allow an MTU of at least 1506 bytes (p. 16, p. 21). On ControlLogix,
Quick comparison
| Aspect | DLR | PRP |
|---|---|---|
| Standard | ODVA | IEC |
| Fault tolerance | one point | several points depending on topology; worst case one |
| Infrastructure | not duplicated | duplicated — twice the number of switches |
| Topology | ring | any |
| Switchover | fast recovery (milliseconds) | no recovery time |
Table source:
How to choose
DLR suits distributed I/O, drives and HMIs within one area — less cabling, no extra switches, recovery within a few milliseconds. PRP is for processes that cannot accept any interruption at all and can justify the cost of two networks. Both must be tested by pulling real cables during FAT, not just on paper. DLR-capable catalog numbers include:
Frequently asked questions
What is the difference between DLR and PRP?
DLR (ODVA) is a ring that tolerates a single point of failure, needs no duplicated infrastructure and recovers within a few milliseconds. PRP (IEC
What is the recovery time of a DLR ring?
With the default beacon interval of 400 µs and beacon timeout of 1960 µs, at 100 Mbps full duplex, the worst-case recovery time is 2890 µs with copper (100 m segments) and 3140 µs with fibre (2 km segments) (
How many nodes can a DLR ring have?
Rockwell recommends up to 50 nodes per ring; a switch-only ring can have up to 24 switches and 230 end devices (
Why does the machine keep running when a DLR ring is broken?
After one break the supervisor unblocks its port and the I/O keeps running normally, so the ring has lost its redundancy without anyone noticing until a second break occurs. The application should monitor the ring status reported by the supervisor, together with the IP/MAC addresses of the two nodes on either side of the break (p. 12, p. 95).
Can 1756-EN2TR and 1756-EN4TR be mixed in the same DLR ring?
Yes, but a ring runs at one speed and port speeds must be set as instructed: leave auto-negotiate, except that the link between two adjacent 1 Gbps nodes in a 100 Mbps ring must be fixed at 100 Mbps (p. 10–11).
Sources
- Rockwell Automation,
ENET-AT007E-EN-P , EtherNet/IP Device Level Ring, 06/2023 — p. 7–12, 14–15, 17–19, 22, 24, 29, 89–93, 95, 97 - Rockwell Automation,
ENET-AT006D-EN-P , EtherNet/IP Parallel Redundancy Protocol, 08/2021 — p. 7, 10–16, 21, 41 - Rockwell Automation,
1756-TD003R-EN-E , 1756 ControlLogix Communication Modules Specifications Technical Data, 01/2025 — p. 4 - Rockwell Automation,
1783-TD002G-EN-P , Stratix Ethernet Device Specifications Technical Data, 04/2025 — p. 29, 44 - Rockwell Automation,
ENET-TD015G-EN-P , Deploying Device Level Ring within a Converged Plantwide Ethernet Architecture (CPwE design guide, further reading), 01/2022 - Rockwell Automation,
ENET-TD021B-EN-P , Deploying Parallel Redundancy Protocol within a Converged Plantwide Ethernet Architecture (CPwE design guide, further reading), 08/2022 - Rockwell Automation, Stratix 5700 and Stratix 5400 product pages on rockwellautomation.com (discontinuation dates)
This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.