Rockwell Automation Vulnerabilities 2024–2026: Lookup by Product

TDL Industrial Automation · Last updated:

A lookup table of Rockwell Automation security advisories from January 2024 to November 2026 by product family: Logix controllers and 1756 modules, ThinManager, FactoryTalk View SE/ME, PanelView Plus 7, FactoryTalk Linx and other lines. With version checks, update planning and compensating measures.

The tables below collect the Rockwell Automation security advisories released from 1 January 2024 to date for the product lines most plants run: ControlLogix, CompactLogix, GuardLogix, 1756 modules, ThinManager, FactoryTalk View SE/ME, PanelView Plus 7, FactoryTalk Linx, Micro800, PowerFlex, Stratix and a few other FactoryTalk products. Each row gives the advisory ID, release date, affected products and versions, CVE, CVSS score, impact and what to do. The tables were read on 8 November 2026. Rockwell and CISA keep updating advisories: open the original advisory before you decide to update or touch a running system.

How to read the tables

  • Advisory ID: ICSA-yy-ddd-nn is an advisory published by CISA; SDxxxx is an advisory on Rockwell's Trust Center. A row with only an SD number is one whose CISA page could not be opened on 8 November 2026, so the data comes from the Rockwell page.
  • Date: the initial release date as the page states it; "updated" is the revision date in CISA's update history.
  • CVSS: written with the version the page prints. CISA usually prints both v3 (or v3.1) and v4; Rockwell prints "CVSS 3.1" and "CVSS 4.0". The two versions give different numbers and are not directly comparable.
  • MNRF (major nonrecoverable fault): the controller faults and stops running; depending on the advisory it restarts by itself (SD1661) or needs a restart, a power cycle, a program download or a reset to recover.
  • Versions: many issues are fixed on several firmware branches (for example V34.014, V35.013, V36.011). Pick the fix on the branch you already run if the project is not ready for a new branch.

On exploitation: on the CISA pages in these tables, CISA states that no known public exploitation specifically targeting the vulnerability had been reported to it (at the time of publication); ICSA-24-284-19 (PowerFlex 6000T) carries no such statement, and none of these CISA pages reports active exploitation. Two Rockwell pages show a KEV status that differs between the page header and the detail table (SD1749, SD1792); in that case check CISA's KEV catalog. On 20 March 2026 Rockwell released SD1771, stating it had become aware of potential threat actor activity targeting Rockwell controllers and repeating its advice to disconnect devices from the internet.

For the three vulnerabilities analysed in depth (ICSA-21-056-03, ICSA-23-193-01, ICSA-24-214-09), see Rockwell PLC OT security hardening. Here ICSA-24-214-09 gets a single row.

Logix controllers and 1756 communication modules

Advisory Date Affected products, versions CVE · CVSS Impact What to do
SD1661 30 Jan 2024 ControlLogix, GuardLogix 5570 from 20.011; 5570 Redundancy from 20.054_kit1 CVE-2024-21916 · v3.1 8.6 MNRF; the controller restarts itself to recover v33.016, 34.013, 35.012, 36.011+; Redundancy: v33.053_kit1, 34.052_kit1, 35.052_kit1, 36.051_kit1+
ICSA-24-107-03 16 Apr 2024, updated 9 May 2024 ControlLogix, GuardLogix 5580, CompactLogix 5380/5480, Compact GuardLogix 5380, Process versions: V35.011; 1756-EN4TR V5.001 CVE-2024-3493 · v3.1 8.6 · v4 9.2 MNRF, manual restart needed V35.013 or V36.011; EN4TR V6.001
SD1673 12 Jun 2024 5580, GuardLogix 5580, CompactLogix 5380/5480, Compact GuardLogix 5380 from V34.011; 1756-EN4 from V4.001 CVE-2024-5659 · v3.1 7.4 · v4.0 8.3 MNRF via the mDNS port, from the same network V34.014, V35.013, V36.011+; EN4 V6.001; if APD is not used, block port 5353; enable CIP Security
ICSA-24-214-09 1 Aug 2024 ControlLogix, GuardLogix 5580; 1756-EN4TR; 1756-EN2T/EN2F/EN2TR/EN3TR/EN2TP CVE-2024-6242 · v3.1 8.4 · v4 7.3 Trusted Slot feature bypass 5580: V32.016, V33.015, V34.014, V35.011+; EN4TR V5.001; newer EN2x modules V12.001; older series have no fix, move to Series D; meanwhile keyswitch in RUN
ICSA-24-226-09 13 Aug 2024 CompactLogix 5380/5480, ControlLogix, GuardLogix 5580, Compact GuardLogix 5380 before v34.014, v35.013, v36.011 CVE-2024-7507 · v3.1 7.5 · v4 8.7 Denial of service v34.014, v35.013, v36.011; restrict access to CIP object 103 (0x67)
SD1686 13 Aug 2024 Same lines as above, from v28.011 (GuardLogix 5580, Compact GuardLogix 5380 SIL 2 from v31.011; Compact GuardLogix 5380 SIL 3 from V32.013; CompactLogix 5480 from V32.011) CVE-2024-7515 · v3.1 8.6 · v4.0 8.7 MNRF via PTP packets v34.014, v35.013, v36.011+; if PTP is not used, block UDP 319, 320
SD1690 13 Aug 2024 ControlLogix, GuardLogix 5580 from v34.011 CVE-2024-40619 · v3.1 7.5 · v4.0 8.7 MNRF v34.014, v35.011+
ICSA-24-256-18 12 Sep 2024 5380, 5480, 5580, GuardLogix, Process versions: v32.011 or v33.011 by line; 1756-EN4 v2.001 CVE-2024-6077 · v3.1 7.5 · v4 8.7 Denial of service via the CIP Security object, factory reset needed v33.017, v34.014, v35.013, v36.011+; EN4 v6.001; if you cannot upgrade, disable CIP Security per SECURE-AT001 chapter 2
ICSA-24-284-18 10 Oct 2024 5380, 5480, 5580, GuardLogix: later than v33.011 up to v33.015; 1756-EN4TR v3.002 CVE-2024-8626 · v3.1 8.6 · v4 8.7 Denial of service (memory leak) CISA lists v33.015+ for branch 33, v34.011+; EN4TR 4.001; check against Rockwell's advisory
SD1707 10 Oct 2024 5580 (incl. Process), GuardLogix 5580, CompactLogix 5380/5480, Compact GuardLogix 5380, FactoryTalk Logix Echo CVE-2024-6207 · v3.1 7.5 · v4.0 8.7 MNRF, program download needed V33.017, V34.014, V35.013, V36.011+
ICSA-25-035-02 4 Feb 2025, updated 18 Feb 2025 GuardLogix 5580, Compact GuardLogix 5380 SIL 3 before V33.017, V34.014, V35.013, V36.011 CVE-2025-24478 · v3.1 6.5 · v4 7.1 MNRF, needs a low-privilege account The versions listed; restrict access to the task object with CIP Security and Hard Run
SD1732 14 Aug 2025 1756-EN2T/D, EN2F/C, EN2TR/C, EN3TR/B, EN2TP/A: 11.004 and earlier CVE-2025-7353 · v3.1 9.8 · v4.0 9.3 Remote code execution 12.001
ICSA-25-226-31 14 Aug 2025, updated 9 Sep 2025 1756-EN4TR, EN4TRXT (CISA also lists "1756-ENT2R"): 6.001 and earlier CVE-2025-8007, CVE-2025-8008 · v3 6.5 · v4 7.1 Denial of service 7.001+
ICSA-25-252-06 9 Sep 2025 CompactLogix 5480 versions 32–37.011 with Windows package 2.1.0 (Win10 v1607) CVE-2025-9160 · v3 6.8 · v4 7.0 Code execution, needs physical access No fix listed; apply security best practices
ICSA-25-252-07 9 Sep 2025 ControlLogix 5580 V35.013 CVE-2025-9166 · v3 7.5 · v4 8.2 MNRF 35.014+
SD1755 14 Oct 2025 Compact GuardLogix 5370 (1769-L3xS) 30.012 and earlier CVE-2025-9124 · v3.1 7.5 · v4.0 8.7 MNRF 30.14+ (as printed)
SD1769 20 Jan 2026 1756-RM2, RM2XT, all versions CVE-2025-14027 · v3.1 7.5 · v4.0 8.7 Redundancy module hangs or MNRF; the controller keeps running No firmware fix; move to 1756-RM3
SD1770 20 Jan 2026 CompactLogix 5370: 34.013, 35.012 and earlier, 36.011 CVE-2025-11743 · v3.1 6.5 · v4.0 7.1 MNRF, restart needed 34.016, 35.015, 36.012, 37.011+
SD1772 16 Jun 2026 CompactLogix, Compact GuardLogix 5370; ControlLogix, GuardLogix 5570: before 34.016, 35.015, 36.012 CVE-2026-11317 · v3.1 7.5 · v4.0 8.7 MNRF, program download needed 34.016, 35.015, 36.012, 37.011+
SD1776 16 Jun 2026 CompactLogix 5370 L1, L2, L3: V37.011 and earlier CVE-2025-11694 · v3.1 7.5 · v4.0 8.7; CVE-2026-9307 · v3.1 5.3 · v4.0 6.3 Denial of service V38.011
SD1780 14 Jul 2026 1756-EN2, EN3: V12.001 and earlier; 1756-ENBT V6.006 CVE-2026-9653 · v3.1 7.5 · v4.0 8.7 Repeated connection disruption EN2, EN3: V12.002; no fix for ENBT
SD1781 14 Jul 2026 5370, 5570: V35.015 and earlier; 5380, 5480, 5580: V34.012, V35.011 and earlier; recovery boot firmware below 1.072 CVE-2025-12011, CVE-2025-12012, CVE-2025-11698 · v3.1 8.6 · v4.0 9.2 MNRF 5370/5570: V36.011; 5380/5480/5580: V34.014, V35.013, V36.011; boot 1.072 (included in V36.013, V37.011); if you cannot upgrade, consider disabling the memory card
SD1788 14 Jul 2026 5580, 5380, GuardLogix: V36–V37; 1756-EN4TR V6.001, V7.001 CVE-2026-9636 · v3.1 5.9 · v4.0 8.2 CIP Security bypass, only with CRL enabled and intermediate certificates in use V38.011; EN4TR V8.001
SD1792 1 Sep 2026 5580, 5380, GuardLogix 5580, Compact GuardLogix 5380: V33 and earlier, V34.011–V34.014, V35.011–V35.013, V36.011–V36.012 CVE-2026-9637 · v3.1 7.5 · v4.0 8.7 MNRF, power cycle needed V34.015, V35.014, V36.013, V37.011
SD1795 1 Sep 2026 5580, GuardLogix 5580, 5380, Compact GuardLogix 5380, 5480: before 34.015, 35.014, 36.013 CVE-2021-42260 (third-party library) · v3.1 7.5 · v4.0 8.7 MNRF 34.015, 35.014, 36.013, 37.011+
SD1798 1 Sep 2026 1756-ENBT, 1756-EWEB, all versions CVE-2026-84235 · v3.1 7.5 · v4.0 8.7 Module crashes, restart needed No fix; move to 1756-EN2T or 1756-EN4TR

ThinManager

Advisory Date Affected versions CVE · CVSS Impact What to do
SD1677 20 Jun 2024 ThinServer from 11.1.0, 11.2.0, 12.0.0, 12.1.0, 13.0.0, 13.1.0, 13.2.0 (CVE-2024-5990 is not listed for 13.2.0) CVE-2024-5988, CVE-2024-5989 · v3.1 9.8 · v4.0 9.3; CVE-2024-5990 · v3.1 7.5 · v4.0 8.7 Remote code execution; denial of service 11.1.8, 11.2.9, 12.0.7, 12.1.8, 13.0.5, 13.1.3, 13.2.2; limit TCP 2031 to known thin clients and servers
ICSA-24-242-01 (SD1692) 29 Aug 2024 ThinServer 11.1.0–11.1.7, 11.2.0–11.2.8, 12.0.0–12.0.6, 12.1.0–12.1.7, 13.0.0–13.0.4, 13.1.0–13.1.2, 13.2.0–13.2.1 CVE-2024-7986, CVE-2024-7987, CVE-2024-7988 · v3.1 5.5 / 7.8 / 9.8 · v4 6.8 / 8.5 / 9.3 Read arbitrary files, execute code with system privileges 11.1.8, 11.2.9, 12.0.7, 12.1.8, 13.0.5, 13.1.3, 13.2.2+
ICSA-24-256-25 12 Sep 2024 13.1.0–13.1.2, 13.2.0–13.2.1 CVE-2024-45826 · v3 6.8 · v4 8.5 Remote code execution 13.1.3, 13.2.2+
ICSA-24-305-01 31 Oct 2024 11.2.0–11.2.9, 12.0.0–12.0.7, 12.1.0–12.1.8, 13.0.0–13.0.5, 13.1.0–13.1.3, 13.2.0–13.2.2, 14.0.0 CVE-2024-10386 · v3.1 9.8 · v4 9.3; CVE-2024-10387 · v3.1 7.5 · v4 8.7 Database manipulation; denial of service Fix on the ThinManager download site; let only devices that need it reach TCP 2031
ICSA-25-119-01 (SD1727) 29 Apr 2025 14.0.0 and earlier CVE-2025-3618 · v3.1 7.5 · v4 8.7; CVE-2025-3617 · v3.1 7.8 · v4 8.5 Denial of service; privilege escalation 14.0.2; CVE-2025-3618 is also fixed in 11.2.11, 12.0.9, 13.1.5, 13.2.4
ICSA-25-252-01 9 Sep 2025 13.0 through 14.0 CVE-2025-9065 · v3.1 7.2 · v4 8.6 Exposure of the ThinServer service account NTLM hash 14.1+
SD1782 14 Jul 2026 13.0.0–13.0.7, 13.1.0–13.1.5, 13.2.0–13.2.4, 14.0.0–14.0.2 CVE-2026-11917 · v3.1 8.1 · v4.0 7.2 File writes to system directories, needs an authenticated account 13.0.8, 13.1.6, 13.2.5, 14.0.3

FactoryTalk View SE

Advisory Date Affected versions CVE · CVSS Impact What to do
SD1670 7 May 2024 Before 14 CVE-2024-4609 · v3.1 7.6 · v4.0 8.8 SQL injection in the Datalog function, HMI design time only Fixes for V11, 12, 13, 14+
SD1675 12 Jun 2024 From v12.0 CVE-2024-37367 · v3.1 9.8 · v4.0 page shows 9.2 and 8.2 HMI project viewable without proper authentication v14.0+; network segmentation, IPsec
SD1676 12 Jun 2024 From v11.0 CVE-2024-37368 · v3.1 9.8 · v4.0 9.2 As SD1675 v14.0; network segmentation, IPsec
ICSA-24-165-17 13 Jun 2024 v12.0 CVE-2024-37369 · v3.1 7.8 · v4 8.5 Low-privilege users can edit scripts V14.0+
ICSA-24-226-06 (SD1688) 13 Aug 2024, updated 29 Aug 2024 v13.0 CVE-2024-7513 · v3.1 8.8 · v4 8.5 Edit or replace files run by an elevated account; not remotely exploitable Remove the INTERACTIVE group from the HMI projects folder permissions, grant specific users or groups
ICSA-24-256-23 12 Sep 2024 V12.0, V13.0, V14.0 CVE-2024-45824 · v3.1 9.8 · v4 9.2 Unauthenticated remote code execution Apply the patches per Rockwell's advisory
ICSA-25-028-04 28 Jan 2025 Before 15.0 CVE-2025-24481, CVE-2025-24482 · v3.1 7.3 · v4 7.0 Unauthenticated access to the system configuration; DLLs run with elevated privileges; not remotely exploitable V15.0 or patch; restrict port 8091; FactoryTalk View SE install path first in PATH

FactoryTalk View ME and PanelView Plus 7

Advisory Date Affected versions CVE · CVSS Impact What to do
ICSA-24-086-04 26 Mar 2024 FactoryTalk View ME before v14 CVE-2024-21914 · v3.1 5.3 · v4 6.9 Loss of view or control of the PanelView Plus 7 Update to the latest version
ICSA-24-317-03 12 Nov 2024 v14.0 and earlier, default folder privileges CVE-2024-37365 · v3.1 7.3 · v4 7.0 Local privilege escalation V15.0; remove the INTERACTIVE group from the HMI project folder
SD1719 28 Jan 2025 Below V15 CVE-2025-24479 · v3.1 8.4 · v4.0 8.6; CVE-2025-24480 · v3.1 9.8 · v4.0 9.3 Local privilege escalation; remote command execution with high privileges V15 or the V12–V14 patches per SD1719
SD1752 14 Oct 2025 PanelView Plus 7 Standard and Performance Series A v12–v14; Performance Series B; Terminal v14 and earlier CVE-2025-9066 · v3.1 7.5 · v4.0 8.7 Temporary denial of service Standard, Series A: patch per SD1752; Series B: V14.103
SD1753 14 Oct 2025 FactoryTalk View ME before V15.00; PanelView Plus 7 Performance Series B V14.100 CVE-2025-9064 · v3.1 7.5 · v4.0 8.7; CVE-2025-9063 · v3.1 7.3 · v4.0 7.0 File deletion on the panel; authentication bypass ME V15.00 or patch; Series B V14.103; if you cannot update, remove the Web Browser ActiveX control

FactoryTalk Linx

Advisory Date Affected versions CVE · CVSS Impact What to do
ICSA-25-226-24 14 Aug 2025 Before 6.50 CVE-2025-7972 · v3.1 9.0 · v4 8.4 Create, update and delete FTLinx drivers 6.50
SD1754 14 Oct 2025 6.40 and earlier CVE-2025-9067, CVE-2025-9068 · v3.1 7.8 · v4.0 8.5 Escalation to SYSTEM, needs valid Windows credentials 6.50+; install the Microsoft MSI fix

Other lines: summary by product family

To keep the tables short, the families below are summarised. See each advisory for the full CVE, CVSS and version data.

Product family Advisory (date) Fix, what to do
Micro800 SD1684 (12 Aug 2024), ICSA-25-226-25 (14 Aug 2025), SD1766 (9 Dec 2025) L50E/L70E to V23.012; the LC20, LC50, LC70 lines have no fix and Rockwell recommends moving to L20E, L50E, L70E. ICSA-25-226-25 scores v3 9.8, v4 9.3 (remote code execution)
PowerFlex SD1664 (21 Mar 2024), ICSA-24-284-19 (10 Oct 2024), ICSA-25-056-01 (25 Feb 2025) PowerFlex 527 ≤v2.001.x: no fix yet, segment the network, disable the web server if not needed; 6000T to 10.001; 755 to v20.3.407
Stratix SD1745 (9 Sep 2025), SD1749 (26 Sep 2025) SD1745: Stratix IOS to 15.2(8)E6 (SD1749 lists 5700/5400/5410 as affected up to 15.2(8)E7); SD1749 (Cisco CVE-2025-20352): fixed software from PCDC, for 5200/5800 the page says "Expected March 2026", check again; KEV status shown inconsistently (header "No", detail table "Yes" after revision 1.1 of 12 Jan 2026), check CISA's KEV catalog
FactoryTalk Activation Manager ICSA-24-004-01 (4 Jan 2024), SD1741 (9 Sep 2025), SD1799 (1 Sep 2026) Fixed in 5.01, 5.02 and 5.03 respectively; use the latest
FactoryTalk AssetCentre ICSA-25-030-05 (30 Jan 2025) Update to the fixed version (CISA writes V15.00.001 and v15.00.01 in two places); January 2025 patch rollup for older versions
FactoryTalk Optix ICSA-25-252-04 (9 Sep 2025) 1.5.0–1.5.7 to 1.6.0+
Studio 5000 Logix Designer ICSA-25-226-29 (14 Aug 2025), SD1783 (14 Jul 2026) 37.00.02+ for ICSA-25-226-29; SD1783 is fixed per branch V32–V37, see the table in the SD

Applying this in a running plant

1. Know what the plant runs

  1. List the equipment: catalog number, series and firmware of every controller and communication module.
  2. For Logix controllers, read the firmware revision in "Controller Properties" in Studio 5000 Logix Designer while online, and record it.
  3. Record the software versions on each PC: FactoryTalk View, FactoryTalk Linx, ThinManager, Activation Manager, AssetCentre.
  4. Check each row against the "affected" list in the original advisory, not against this summary.
  5. Watch for new advisories: Rockwell's Trust Center filters by product, CVSS severity and KEV status, with alert sign-up and RSS; CISA republishes Rockwell advisories under ICS Advisories.

2. Set priorities

Start with devices exposed to the internet or connected to the office network, then vulnerabilities that need no authentication and those that stop the controller. CISA reminds owners to perform impact analysis and risk assessment before deploying defensive measures.

3. Plan the update with the plant

  1. Upload the program from every controller and keep an offline copy, as SD1771 recommends.
  2. Check compatibility between firmware, Logix Designer and FactoryTalk software on compatibility.rockwellautomation.com (PCDC).
  3. Test the new version on a spare controller or a test bench first.
  4. Agree an outage window with production: a controller firmware update stops the machine. Some issues also need a program download or reset to recover.
  5. After the update: check I/O connections, HMI and historian, then record the new versions.

When several steps come together (firmware, Logix Designer, FactoryTalk software), see the controller firmware upgrade and compatibility service.

4. Compensating measures when you cannot update yet

CISA's general recommendations in the advisories:

  • Minimize network exposure for all control system devices, and make sure they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls, isolated from business networks.
  • When remote access is required, use more secure methods such as VPNs, and keep the VPN updated to the latest version.

In SD1771 Rockwell adds, for ControlLogix and CompactLogix: put the controller mode switch in Run; deploy a CIP Security policy with FactoryTalk Policy Manager to require authenticated connections; close unauthenticated open ports on edge routers. For Micro850 and Micro870: also put the mode switch in Run.

Some advisories have their own workarounds, listed in the tables: block port 5353 when APD is not used, block UDP 319, 320 when PTP is not used, limit TCP 2031 for ThinManager, remove the INTERACTIVE group from the HMI project folder. For writing firewall rules see FactoryTalk and Logix firewall ports; for an overall network review see Industrial networks and OT security.

Frequently asked questions

Which Rockwell vulnerabilities are being exploited in the wild?

On the CISA pages in these tables, CISA states that no known public exploitation specifically targeting the vulnerability had been reported to it at the time of publication (ICSA-24-284-19 has no such statement); none of them reports active exploitation. SD1749 and SD1792 show an inconsistent KEV status, so check CISA's KEV catalog. In March 2026 Rockwell stated in SD1771 that it had become aware of potential threat actor activity targeting Rockwell controllers.

Does patching a Logix controller vulnerability require stopping the machine?

Yes. A controller firmware update needs a planned outage, with a backup and a test run first. In the meantime apply the compensating measures: segmentation, firewalls, the mode switch in Run and the specific workarounds the advisory gives.

Should I look at the CVSS v3.1 or the v4 score?

CISA usually prints both, and Rockwell prints CVSS 3.1 and 4.0. The two versions are calculated differently, so they give different numbers and are not directly comparable. The score is only one input; priority also depends on which networks can reach the device and the impact on production.

How do I find out about new advisories for the plant's equipment?

Rockwell's Trust Center filters advisories by product, CVSS severity and KEV status, with alert sign-up and RSS. CISA republishes Rockwell advisories under ICS Advisories. Check each new advisory against the plant's equipment and version list.

Which port should be restricted for ThinManager?

SD1677 and ICSA-24-305-01 recommend limiting TCP 2031 so that only the thin clients and ThinManager servers that need it can connect. This does not replace updating to a fixed version.

Sources

Read 8 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.