Rockwell Burner Management Suite library for GuardLogix: six AOIs, faceplates, limits and testing

TDL Industrial Automation · Last updated:

From Rockwell's BMS-RM001A manual (05/2025): the Burner Management Suite library's six AOIs (Interface, Master, Purge, Pilot, Fuel, 2-State Device) and FactoryTalk View SE faceplates, the burner configurations it covers, its safety task architecture, import files, v36 requirements, SC 3 to IEC 61508 and System Test mode.

A burner management system (BMS) handles flame safety on a boiler, furnace or oven: it proves the purge, lights the pilot and main flame, proves each flame and trips the fuel when an interlock is lost. Rockwell Automation's Burner Management Suite (BMS) Library is a set of Add-On Instructions (AOIs) and HMI faceplates for building one on a GuardLogix safety controller. This article follows Rockwell's reference manual BMS-RM001A-EN-P (May 2025, library release v1.00). It does not assign a SIL to any burner; the level a safety function needs comes from the plant's risk assessment. The safety task and signature are covered in GuardLogix safety program.

1. What the library is

Rockwell describes it as a tested, documented and life cycle managed library: a configured AOI set with optional HMI faceplates for Compact GuardLogix 5380 and GuardLogix 5580 controllers. Its aim is to make a single burner, single fuel system easy to implement with minimal code, while staying flexible enough for multi-fuel and multi-burner applications. The same page states that it is the user's responsibility to determine if the AOI set is suitable for the intended application (BMS-RM001A, p. 13).

The BMS does not run the air/fuel ratio; that stays with the burner's combustion control system (CCS). The Purge AOI does not control air flow: the CCS positions the air actuators and the BMS confirms the air flow through interlock switches (pp. 93, 97). The pre-ignition and post-firing purges remove unburned fuel vapors from the combustion chamber (p. 96). The Interface AOI collects CCS status confirming that the selected fuels are in the air/fuel ratio calculation (p. 51), and the Master releases the burner for modulation only once the requested fuels are lit and stable (p. 74). Why protection stays separate from process control: What is SIL.

2. The six Add-On Instructions

The system is made of five Safety-class AOIs and one Standard-class AOI (p. 13). Names start with "raS" for Rockwell Automation Safety (p. 19).

AOI Class Instances What it does
raS_Opr_BMS_Interface Standard 1 (p. 51) Takes start, stop and reset commands from program logic or the HMI and returns system status (p. 14)
raS_Opr_BMS_Master Safety 1 (p. 67) Primary burner controller: validates requests, coordinates the other AOIs, monitors system interlocks with safety trip and first-out capture (p. 14)
raS_Opr_BMS_Purge Safety 1 (p. 93) Monitors air flow and fans; times the pre-ignition and post-firing purge (p. 14)
raS_Opr_BMS_Pilot Safety 1–4 (p. 113) Pilot ignition and flame proving, optional valve proving; up to 3 spark igniters and 3 flame sensors (p. 14)
raS_Opr_BMS_Fuel Safety 0–4 main fuel + 1 fuel header (p. 139) Main fuel ignition through the requested pilots, flame proving, optional valve proving; up to 2 flame sensors (p. 14)
raS_Dvc_BMS_D2S Safety 3 to 56 per burner system (p. 167) One on-off device that energizes to act and de-energizes to its safe state, with position feedback and a heartbeat to its host AOI (pp. 14–15)

Each Pilot or Fuel AOI drives at least one blocking valve and up to five valves: two blocking valves, an auxiliary vent or recirculation valve, an atomizing media valve and a fuel scavenging valve (p. 14). Every AOI validates its configuration, provides required, selectable and user-definable interlocks that trip when lost, captures the first-out with a manual reset, and checks a heartbeat at both ends of its link to the Master (pp. 24–25).

3. Which burners it covers

The manual lists these limits (p. 13):

  • One purge zone for all equipment under the AOI set.
  • Up to four main fuel trains, feeding one burner with different fuels, several burners, or both.
  • Up to four pilot fuel trains with spark igniter control; Pilot AOIs can instead serve spark-ignited main fuels, but not both in one system (p. 113).
  • An optional fuel header, built with the Fuel AOI.
  • All Safety AOIs in the same task, scanned at the same rate and in the same order. The Interface AOI sits outside the safety logic but must be scanned fast enough to avoid communication watchdog failures.

The library covers single burner and some multi-burner applications; for multi-burner use, the Master's Cfg_AnyFlameOK setting must be false (pp. 33, 182).

4. How the parts connect

BMS library: how the six AOIs connectTop row, three boxes: the combustion control system CCS handles the air/fuel ratio and modulation; the Interface AOI runs in a standard task, one per system; the HMI is the FactoryTalk View SE faceplates. The Interface is linked both ways to the CCS and to the HMI. From the Interface down to the Master AOI: commands go in a safety-mapped SINT array, and Master status comes back up through program parameters. A dashed red frame is the safety task, holding every Safety AOI in one task. The Master AOI, one per system, monitors system interlocks, trips and first-out, and has a D2S device for the master fuel trip relay MFTR. The Master links to four boxes below through one UDT with a heartbeat at both ends: the Purge AOI, one required, monitors air flow and fans and times the pre-ignition and post-firing purge, with no devices of its own; the Pilot AOI, 1 to 4, for pilots or spark-ignited main fuels, with D2S devices igniters A, B and C, blocking valves A and B, vent or recirculation valve, atomizing valve and scavenging valve; the Fuel AOI, 0 to 4, one per fuel train, lit through pilots, with D2S devices blocking valves A and B, vent or recirculation valve, atomizing valve and scavenging valve; the Fuel AOI used as fuel header, 0 or 1, with D2S devices blocking valves A and B and vent or recirculation valve. Starred devices are optional. Simplified from Rockwell BMS-RM001A-EN-P pp. 23–24.BMS library: how the six AOIs connectCCScombustion control: air/fuelratio, modulationInterface AOIstandard task · 1per systemHMIFactoryTalk View SEfaceplatescommands: safety-mapped SINT arraystatus: Master program parametersMaster AOI · 1 per systemsystem interlocks, trip and first-out; D2S · MFTRone UDT, heartbeat at both endsPurge AOI1 requiredPilot AOI1–4Fuel AOI0–4, one per fuel trainFuel AOIas fuel header, 0–1air flow and fans;pre-ignition andpost-firing purgepilot, or spark-ignitedmain fuelmain fuel, lit througha pilotno flame, atomizing orscavenging inputsD2S devicesno devices of its ownD2S devicesigniters A, B*, C*blocking valves A, B*vent or recirc valve*atomizing valve*scavenging valve*D2S devicesblocking valves A, B*vent or recirc valve*atomizing valve*scavenging valve*D2S devicesblocking valves A, B*vent or recirc valve** optional device. Each device is a 2-State Device (D2S) AOI: energize to act, de-energize to the safe state.Safety task: every Safety AOI in one taskSimplified from Rockwell Automation BMS-RM001A-EN-P (05/2025), architecture diagram pp. 23–24; AOI rolespp. 13–15. Read 23 November 2026. Figure: drawn by TDL.
Figure 1: BMS library: how the six AOIs connect. On a phone, swipe sideways to see the whole figure.

In the manual's architecture diagram (pp. 23–24), the Interface AOI sits between the CCS and the HMI, outside the safety task, and every Safety AOI sits inside the safety task; the Interface program runs in a standard task (p. 30). The Interface sends commands to the Master in a safety-mapped SINT array and receives status through program parameters (p. 51). The Master exchanges data with the Purge, Pilot and Fuel AOIs through one UDT; each D2S device is tied to its host AOI by an InOut reference (pp. 67, 167). The master fuel trip relay (MFTR) is a D2S device under the Master (pp. 24, 182).

A typical implementation has two programs: one in the safety task for the Safety AOIs, one in a standard task for the user interface and alarms (p. 30). The PlantPAx Process Object Library v5.x runs only on process-class controllers and the BMS library only on safety-class controllers, so they need separate controllers, though they can share one FactoryTalk View SE application (p. 49). See PlantPAx 5 process library.

5. Files, import and faceplates

The library .zip holds an example project, View SE displays, global objects and images, and L5X files for AOI, rung and routine import (p. 20). Rockwell recommends importing the ROUTINE or RUNG files; importing only the AOI files and building your own rungs makes configuration errors more likely and can miss logic needed outside the AOI. AOI files are for upgrading an existing application (p. 29). BMS safety tags can be aliased only to safety I/O channels (p. 32).

The HMI platform is FactoryTalk View SE (p. 21). Faceplates have Home, Configuration, Interlocks, Permissives, Diagnostics and Help tabs (p. 22). Safety trip alarms come from UDTs with Logix alarm definitions, which the manual says are enough with FactoryTalk View SE, PanelView 5000 or FactoryTalk Optix (p. 41).

Before a project, note that this release does not support Studio 5000 Application Code Manager (p. 9), AOI updates are made offline with a download (p. 44), and the objects have no simulated mode (p. 72).

6. Software, hardware and certification

Item As listed in BMS-RM001A (p. 15)
Programming software Studio 5000 Logix Designer v36
HMI software FactoryTalk View Studio v14 and later, for FactoryTalk View Site Edition
Controllers GuardLogix 5580 or Compact GuardLogix 5380 with v36 firmware
I/O FLEX 5000, 5069 Compact 5000, POINT Guard I/O, 1756 ControlLogix digital safety I/O

Rockwell states that, based on the assessment by the certification body, the Burner Management Suite is in compliance with IEC 61508 and meets Systematic Capability (SC) 3, and that the certification applies only to Logix Designer version 36 (p. 15). The AOI safety signatures for each release are in the library release notes on the Product Compatibility and Download Center (p. 16).

SC 3 is a property of the library, not of a burner. The manual leaves it to the user to confirm that each implementation meets all applicable regulatory codes (p. 181) and does not name a burner or furnace code.

7. System Test mode and testing

The AOIs have four modes: Normal; TEST ENABLE, a maintenance mode in which devices are selected for manual testing one at a time; Test Active, with one device under test; and Disabled (p. 25). In TEST ENABLE the burner cannot start, and the Master energizes the MFTR so devices can be tested (p. 72). If two components report a device test at once, the Master trips (p. 73). In normal operation no device can be operated on its own from external code or the HMI (p. 14).

For gaseous fuels, Pilot and Fuel AOIs can run a valve proving sequence using two pressure switches between the blocking valves. It does not supersede annual manual valve leak testing as required by code (pp. 119, 145).

The implementation checklist ends with: apply the safety task signature, test the burner, remove and reapply the signature for any change and retest, then record the BMS program's Safety ID and Safety Updated time stamp (pp. 182–183). Without a safety task signature the Master trips (p. 71). Testing over the plant's life: Cause and effect matrix and SIS testing, SIS useful life and proof testing.

What we check first

This is TDL's practice, not a Rockwell Automation requirement.

  • We ask for the safety requirements and risk assessment; the SIL target comes from the plant, not from TDL or the library.
  • We check the burner against the limits: one purge zone, four main fuel trains, four pilot trains.
  • We confirm Logix Designer v36, controller firmware v36, FactoryTalk View SE v14 or later, and the release notes.
  • We list every signal between the BMS and the combustion control before writing code.
  • We agree with the plant who may use System Test mode, and how valve proving fits the annual leak test.
  • At acceptance we record the Safety ID, the signature and every configuration setting.

How TDL approaches it

TDL Industrial Automation is a Bronze System Integrator in the Rockwell Automation PartnerNetwork. Through our ICSS and safety systems service we implement safety functions up to SIL 2 / PLd or SIL 3 / PLe on GuardLogix, depending on controller configuration. For a BMS on GuardLogix, the work is the functional design from the plant's requirements, the safety and standard programs, the FactoryTalk View SE faceplates and the FAT.

On Rockwell Logix projects, TDL runs the logic on FactoryTalk Logix Echo before the FAT, with the HMI connected where the project has one. I/O, scan time, redundancy and safety functions are still tested on the real hardware at the FAT. More: Rockwell Automation system integrator in Vietnam, coal-fired power plant automation, oil and gas automation.

Frequently asked questions

Does using the BMS library make a burner SIL 3?

No. Rockwell states that the library meets Systematic Capability 3 to IEC 61508, for Logix Designer v36 only. The level each safety function needs comes from the plant's risk assessment, and the manual makes the user responsible for deciding whether the library suits the application.

Which software and controllers does the library need?

Studio 5000 Logix Designer v36, FactoryTalk View Studio v14 or later for View SE, and a GuardLogix 5580 or Compact GuardLogix 5380 controller with v36 firmware. Listed I/O families are FLEX 5000, 5069 Compact 5000, POINT Guard I/O and 1756 digital safety I/O.

Can one BMS program handle several fuels or burners?

Within limits: one purge zone, up to four main fuel trains, up to four pilot trains and an optional fuel header. The manual says it covers single burner and some multi-burner applications; for multi-burner use, Cfg_AnyFlameOK on the Master must be false.

Can the BMS library and PlantPAx process objects run in the same controller?

No. Process Object Library v5.x runs only on process-class controllers and the BMS library only on safety-class controllers, so they go in separate controllers. Both can share one FactoryTalk View SE application.

Does valve proving replace the annual valve leak test?

No. The manual says the valve proving sequence does not supersede annual manual valve leak testing as required by code. When selected, it runs before light-off or after shutdown and confirms that the blocking valves close and seal without significant leakage.

Sources

  • Rockwell Automation, BMS-RM001A-EN-P, Burner Management Suite (BMS) Library Reference Manual, Release v1.00, 05/2025 — pp. 9, 13–16, 19–25, 29–33, 41, 44, 49, 51, 67, 71–74, 93, 96–97, 113, 119, 139, 145, 167, 181–183
  • Rockwell Automation, Burner Management (BMS) AOI Suite release notes, Product Compatibility and Download Center — named in BMS-RM001A p. 16 as the source of the AOI safety signatures; not opened for this article