The POINT I/O
1. Which adapters and which documents
| Adapter | Document used here | Lifecycle on Rockwell's page (read 15 November 2026) |
|---|---|---|
| Active | ||
| Active | ||
| Active Mature; "Replacement Available" with no product named | ||
| End of Life, discontinued date 30 September 2028; functional replacement |
Both have two 10/100 Mbps Ethernet ports; on the
2. 1734-AENTR indicators
From
| Indicator | State | Meaning and action |
|---|---|---|
| Module status | Off | No power applied |
| Flashing green | Needs commissioning: configuration missing, incomplete or incorrect | |
| Solid green | Operating normally | |
| Flashing red | Recoverable fault: complete the firmware update, verify the address switches | |
| Solid red | Unrecoverable fault; the adapter may need replacing | |
| Flashing red/green | Self-test | |
| Network status | Off | Not online: duplicate MAC ID test not finished, or no power; check Module status |
| Flashing green | Online, no CIP connections | |
| Solid green | Online, CIP connections established | |
| Flashing red | One or more CIP connections timed out (POINT Guard I/O timeouts excluded): check for an I/O module failure and controller operation | |
| Solid red | Duplicate IP address: verify and correct the IP setting | |
| Flashing red/green | Self-test | |
| POINTBus status | Off | Not online: check Module status and power |
| Flashing green | Online, no connections; also during a firmware (NVS) update | |
| Solid green | Online, connections established | |
| Flashing red | Recoverable fault: module count mismatch at power cycle, missing module, or I/O connection timeout | |
| Solid red | Unrecoverable fault, adapter bus off | |
| Flashing red/green | Power-up test | |
| System power | Off / green | Off: adapter power off or DC-DC converter problem; green: 5 V DC-DC output active |
| Field power | Off / green | Off: adapter power off; green: 24 V input present |
| Network activity, Link 1, Link 2 | Off | No link |
| Green | Link at 100 Mbps; flashing: traffic at 100 Mbps | |
| Yellow | Link at 10 Mbps; Link 1 or 2 flashing yellow: traffic at 10 Mbps |
The single-port
3. 1794-AENTR indicators
From
| Indicator | State | Meaning and action |
|---|---|---|
| Link 1, Link 2 | Off | No link: check the network cabling |
| Green / flashing green | Link at 100 Mbps / traffic at 100 Mbps | |
| Yellow / flashing yellow | Link at 10 Mbps / traffic at 10 Mbps | |
| Module Status | Off | No 24 V DC: confirm power reaches the adapter |
| Flashing green | Standby, not configured: configure the adapter | |
| Green | Operating correctly | |
| Flashing red | Minor, recoverable fault, often an incorrect or inconsistent configuration: check and reconfigure | |
| Red | Major, unrecoverable fault: cycle power; if it stays, replace the adapter | |
| Flashing red/green | Power-up self-test | |
| Network Status | Off | Not powered or no IP address: check power, wiring and configuration |
| Flashing green | IP address, no connections | |
| Green | IP address and at least one CIP connection | |
| Flashing red | A connection with the adapter as target timed out | |
| Red | Duplicate IP address: assign a unique address | |
| Flashing red/green | Power-up self-test |
The
4. Reading them together
- Network status flashing red. A connection timed out. Rockwell's first check on POINT I/O is an I/O module failure and the controller. The codes the controller shows for a lost connection, such as 16#0203 or 16#0204, are explained in ControlLogix I/O fault 16#0204, 16#0203.
- Network status solid red. Another device holds the same IP address.
- POINTBus status flashing red. One cause the table names is a module count mismatch. On a new or replaced
1734-AENTR , check the chassis size: the adapter allows no I/O connection until the module count matches its stored chassis size (1734-UM017F pp. 13–15). - Link yellow. The port linked at 10 Mbps; for Stratix switch ports see Stratix 5700 and 5400 troubleshooting.
5. IP address: switches, DHCP and 888
| Switch setting | ||
|---|---|---|
| 001–254 | Sets the network address; gateway 0.0.0.0 at 001, 192.168.1.1 at 002–254 | 192.168.1.xxx, mask 255.255.255.0; gateway 0.0.0.0 on firmware 1.013 and earlier; with firmware 1.014, 192.168.1.1 at 002–254 |
| 999 | As shipped, DHCP enabled | As shipped, DHCP enabled |
| 888 | Restores factory defaults | After a power cycle: DHCP on, auto-negotiation on, both ports disabled, configuration password blank; return the switches and cycle power to re-enable the ports |
| 801–864 | Chassis size (firmware 5.015 or later); Ethernet ports disabled while set | Not used |
| Other (000, above 254) | DHCP if enabled, else the address stored in memory | Same |
Sources:
On the
6. Built-in web pages
7. Implicit protected mode
Both adapters block changes while I/O connections run through or to them; the mode ends when all those connections stop and cannot be configured. On the
8. Replacing an adapter
Do not remove or replace an adapter under power; on POINT I/O, interrupting the backplane can cause unintended machine motion (
1734-AENTR . After fitting it, set the network address, IP address and chassis size (1734-UM017F p. 27). The controller does not send the chassis size in its connection request (p. 15), so a new adapter starts at the default of 1 (p. 13). The1734-AENTR accepts1734-AENT keying (1734-IN040C p. 7).1794-AENTR . The Flexbus connector is unplugged and plugged back as part of the swap (1794-UM066E pp. 14–15). With BOOTP, enter the new adapter's hardware address (p. 19). On firmware 2.013 or later the web server and SNMP are off until switched on again (pp. 24, 49).- Firmware.
1794-UM066E points to the Product Compatibility and Download Center (PCDC) for firmware, AOP and EDS files (p. 7); its compatibility table starts at Studio 5000 Logix Designer 20 and RSLinx 2.59 (p. 10).1734-UM017F points to the PCDC to verify module compatibility (p. 12). The update itself: ControlLogix and CompactLogix firmware updates.
What we check first
This is TDL's practice, not a Rockwell requirement.
- We photograph the indicators and switch positions before anyone touches the rail.
- On a solid red Network status we look for the second device on that address, including any DHCP server on the segment.
- On a yellow Link we check the switch port before the cable.
- We record catalog number, series, firmware, chassis size, IP method and web server state of every adapter with the program backup.
- Because protected mode blocks IP and firmware changes, we agree a machine stop before that work.
Remote I/O work at TDL
TDL Industrial Automation is a System Integrator in the Rockwell Automation PartnerNetwork. At Crown Da Nang we replaced DeviceNet with EtherNet/IP on a body maker, with POINT I/O adapters for the body maker and trimmer. The Intel Vietnam SWTP control system we delivered runs on Flex remote I/O. See also breakdown support, Rockwell Automation upgrades and FLEX I/O to FLEX 5000.
Frequently asked questions
What does a flashing red Network status mean on a 1734-AENTR ?
One or more CIP connections timed out.
Why is the POINTBus status flashing red after replacing a 1734-AENTR ?
A module count that does not match the stored chassis size is one documented cause. The controller does not send the chassis size, a new adapter starts at 1, and no I/O connection is allowed until the module count matches. It is set with the thumbwheel at 801 to 864 on firmware 5.015 or later.
What does solid red Network Status mean on a 1794-AENTR ?
A duplicate IP address. Another device uses the same address; assign a unique one.
Why can't I change the IP address or firmware of a running adapter?
Implicit protected mode. While I/O connections run through or to the adapter, both the
Does the 1794-AENTR have a web page?
Yes, with diagnostic pages for CIP connections, Ethernet statistics and I/O connections. From firmware 2.013 the web server is off by default and is switched on in Module Properties with the adapter inhibited.
Sources
- Rockwell Automation,
1734-IN040C-EN-P , POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions (1734-AENTR ), 12/2018 — pp. 7, 9–12, 15–18 - Rockwell Automation,
1734-UM017F-EN-E , POINT I/O and ArmorPOINT I/O Dual-port EtherNet/IP Adapters User Manual, 05/2023 — pp. 12–15, 26–27, 34–35, 41–44, 101–118 - Rockwell Automation,
1734-IN042J-EN-P , POINT I/O EtherNet/IP Adapter Installation Instructions (1734-AENT ,1734-AENTK Series C), 06/2026 — pp. 8–9 - Rockwell Automation,
1794-UM066E-EN-E , FLEX I/O Dual-port EtherNet/IP Adapters User Manual, 12/2025 — pp. 7, 10, 14–17, 19, 21–25, 45–46, 49–54 - Rockwell Automation,
1794-IN131E-EN-P , FLEX I/O Dual-port EtherNet/IP Adapter Installation Instructions (1794-AENTR ,1794-AENTRXT ), 06/2024 — pp. 4, 8–9 - Rockwell Automation,
1794-IN082G-EN-P , FLEX I/O EtherNet/IP Adapters Installation Instructions (1794-AENT ,1794-AENTK Series B), 06/2024 — pp. 9–10 - Rockwell Automation, product pages
1734-AENTR ,1734-AENT ,1794-AENTR and1794-AENT (lifecycle status, discontinued date, replacement)
Read 15 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.