Not every FLEX I/O 1794 catalog number is about to be discontinued. Per Rockwell's product pages (read 13 November 2026), the
This article summarises Rockwell's migration guide, FLEX I/O to FLEX 5000 I/O Migration Guide (
Lifecycle of each 1794 code on Rockwell's pages
| Catalog number | Status on Rockwell's page | Discontinued date | Replacement named on the page |
|---|---|---|---|
| End of Life | 30/09/2028 | ||
| Active Mature | — | Only "Replacement Available" | |
| Discontinued | 22/10/2026 | Engineering Replacement, no catalog number | |
| Discontinued | 22/10/2026 | Engineering Replacement, no catalog number | |
| Discontinued | 22/10/2026 | ||
| End of Life | 31/03/2026 | ||
| Discontinued | 01/10/2026 | ||
| End of Life | 28/02/2027 | ||
| Active Mature | — | Only "Replacement Available" | |
| Active Mature | — | None given |
Per the pages read 13 November 2026,
When to migrate
- ControlNet or DeviceNet adapters past their discontinued date. FLEX 5000 has no ControlNet or DeviceNet adapter; to use FLEX 5000 the network must first move to EtherNet/IP, and the controller needs an EtherNet/IP module such as
1756-EN2TR (5094-RM001B pp. 14, 26). For ControlNet, Rockwell points to theCNET-RM001 guide. - Analog modules that already have a date.
1794-IE8H has a replacement inside the 1794 family (1794-IF8IH ), so the rack can stay;1794-OE8H and1794-OE4 are pointed straight to FLEX 5000 on Rockwell's pages. - EtherNet/IP racks running
1794-AENTR and "Active Mature" modules. There is no deadline yet; the sensible time is the next controller upgrade, because FLEX 5000 does not run with ControlLogix 5570 or CompactLogix 5370 (5094-RM001B p. 27). - When new features are needed. FLEX 5000 offers 1 Gbps EtherNet/IP, DLR on every adapter, PRP from firmware 4.011, runtime reconfiguration and up to 16 modules per adapter (
5094-RM001B pp. 12, 15).
Equivalent adapters
| FLEX I/O | Network | FLEX 5000 |
|---|---|---|
| EtherNet/IP | ||
| ControlNet | Move the network to EtherNet/IP, then |
|
| DeviceNet | As above | |
| Remote I/O, PROFIBUS | As above |
Table 2 of
Equivalent I/O modules
A condensed table from
| FLEX I/O | FLEX 5000 | Note |
|---|---|---|
| IB8 moves to a module with more channels | ||
| — | ||
| — | ||
| Not a direct replacement for protected outputs | ||
| — | ||
| — | ||
| 8 channels instead of 4 | ||
| — | ||
| — | ||
| — | ||
| — |
Common catches:
- No replacement:
1794-IV16 ,1794-IV32 (FLEX 5000 has no sourcing inputs),1794-OV16 ,1794-OV32 ,1794-IG16 ,1794-IC16 ,1794-IH16 ,1794-OC16 ,1794-IP4 ,1794-IF4ICFXT (pp. 16–20). - Combo modules such as
1794-IE4XOE2 ,1794-IE8XOE4 and1794-IB10XOB6 must be split into two FLEX 5000 modules, using extra slots (pp. 16, 18). - Diagnostic modules
1794-IB16D ,1794-OB16D and1794-OB4D have no FLEX 5000 equivalent with diagnostics (p. 16). - Isolation: among FLEX 5000 analog modules, only
5094-IF8IH and5094-OF8IH are isolated; there are also the isolated relay modules5094-OW8I and5094-OW4IS (p. 15), and5094-IJ2I is listed as an isolated-frequency input module (p. 20).1794-IT8 and1794-IR8 are isolated to 850 V,5094-IY8 to 250 V;5094-IY8 does not accept3-wire current/voltage devices (pp. 62–63). - Analog output load:
1794-OE4 drives a 15…750 Ω current load (1794-SG002I p. 43),5094-OF8 a maximum of 500 Ω in current mode (5094-TD001M p. 39). High-burden 4–20 mA loops need rechecking.
Terminal bases and reusing the wiring
1794 terminal bases do not take 5094 modules. A FLEX 5000 terminal base is two parts ordered separately: the
| FLEX 5000 module | RTB |
|---|---|
About the existing wiring:
- Wires have to be moved by hand from the old base to the new RTB; if existing wires are too short to reach the new positions, the job gets much harder (
5094-RM001B p. 47). Chapter 3 has side-by-side diagrams for 12 module pairs (pp. 47–60). For example, a3-wire RTD on5094-IY8 no longer ties RTD- to the L terminal as on1794-IR8 (p. 58). - Maximum wire size stays 2.5 mm² on both systems (p. 13).
- Shields: the 1794 base has dedicated shield terminals; FLEX 5000 needs a
5094-STB shield bar, typically for every analog module and5094-HSC . The bar adds about 33 mm to the base height (p. 26). - Field power: both systems jumper terminals 33→16 (common) and 51→34 (DC+); FLEX 5000 offers the
4-prong 5094-SAJMPR jumper, for screw-type RTBs only (p. 25). - Size: the footprint is about the same, but FLEX 5000 modules are 10–30 mm taller (p. 13). The
5094-CE05 /CE10 bank cables replace1794-CE1 /CE3; the connector is about 12.7 mm wider and the cable orientation differs (p. 24). The last base needs a5094-ECR end cap; empty slots take a5094-N2 cover (pp. 25, 29). - Power: FLEX 5000 needs no separate power supply module, but it may draw more SA current than the FLEX I/O backplane did; recheck the load on the existing 24 V supply (pp. 23, 26).
Controllers and Studio 5000 versions
- Studio 5000 Logix Designer 31.00.00 or later and RSLinx Classic 4.10.00 for the FLEX 5000 Add-on Profiles (
5094-RM001B p. 5). - Controllers: ControlLogix 5580, CompactLogix 5380 and 5480 (and their GuardLogix safety versions: GuardLogix 5580, Compact GuardLogix 5380) (pp. 5, 27). SIL levels and safety values must be determined by a competent engineer per IEC 61511 for each project. Systems on ControlLogix 5570 or CompactLogix 5370 must replace the controller first, per
1756-RM100 (p. 27). - Minimum versions from Table 4 (pp. 27–28): standard modules v31 with 5580/5380, v32 with CompactLogix 5480; HART modules
5094-IF8IH /OF8IH v32.02 with ControlLogix 5580 and CompactLogix 5380; ControlLogix redundancy v33;5094-IJ2I v34. - A redundant controller cannot use Listen Only or Input Only connections to FLEX 5000, so this I/O cannot be shared with other controllers (p. 28).
- The program must change: Rockwell treats this migration as an engineered solution, and every reference to FLEX I/O must be replaced with FLEX 5000 (p. 29). Analog data changes from INT (0…22,000, 0…65,535, ±32,767) to REAL, scaled 0…100 % by default; the RPI range changes from 2…750 ms to 0.2…750 ms (p. 29). Slot numbering changes from 0–7 to 1–8 or 1–16 (p. 16).
- Integrated Architecture Builder (IAB) has a migration wizard that builds the BOM and flags modules without a replacement (p. 31).
XT and environmental conditions
| FLEX I/O | FLEX 5000 | |
|---|---|---|
| Operating temperature, standard | 0…55 °C, some codes -20…+55 °C | -40…+70 °C |
| Operating temperature, XT | -20…+70 °C | -40…+70 °C |
| Corrosion protection | XT conformal coated to G1, G2, G3 per ANSI/ |
Standard G2, XT G3 per ISA S71.04 |
Sources:
Diagnostics
5094-IF8 has open-wire detection, notch and digital filters, which1794-IE8 lacks;5094-IF8IH adds short-circuit detection and internal loop power (5094-RM001B p. 62). Open-wire detection must be enabled in the module configuration (5094-UM002E p. 41).- Analog modules report data quality through I.Chxx.Fault (do not use for control: open wire, under/over range, field power loss…) and I.Chxx.Uncertain tags (
5094-UM002E pp. 28–29). Digital modules have I.Ptxx.Fault and I.Ptxx.Uncertain (5094-UM001I p. 36), plus field power loss detection down to the point (p. 40). - Logix Designer reads each module's serial number, firmware, faults and diagnostic data; check firmware in the PCDC before commissioning (
5094-UM001I pp. 36–37).
Reading module connection fault codes in Logix Designer is covered in the article ControlLogix I/O module fault 16#0204, 16#0203.
A TDL maintenance case
In the making areas of FMCG plants that TDL maintains, FLEX I/O 1794 and FLEX 5000 (
Checklist before migrating
- List every 1794 code per rack (adapter, modules, bases, power supply, bank cables) and look up each code's lifecycle status.
- Identify the network: ControlNet, DeviceNet, Remote I/O or PROFIBUS racks need an EtherNet/IP plan first.
- Check the controller and Logix Designer version against Table 4 of
5094-RM001B ; if it is a 5570 or 5370, add the controller replacement to the scope. - Map modules using pp. 16–20; flag codes with no replacement, combo modules, channel-isolated modules and diagnostic modules.
- Choose the
5094-MB and the right RTB for each module; add5094-STB ,5094-SAJMPR ,5094-ECR ,5094-N2 and5094-CE cables. - Measure wire lengths and cabinet height; label every wire before removal.
- Recalculate SA current and the 24 V supply load; check current-loop load on analog outputs.
- Update the program: new tags, new slot numbers, REAL scaling, RPI, and any logic that reads the old diagnostic bits.
- Check switches and cables if running 1 Gbps, DLR or PRP.
Need an engineer to survey the running system: send a request
Frequently asked questions
Is all FLEX I/O 1794 being discontinued?
No. Per Rockwell's pages read on 13 November 2026,
What replaces the 1794-AENT ?
Rockwell's page names
How do 1794-ACN15 or 1794-ACNR15 racks move to FLEX 5000?
FLEX 5000 has EtherNet/IP adapters only, so the ControlNet network must first move to EtherNet/IP, then
Can the old terminal bases and wiring be reused?
The 1794 bases cannot be reused; FLEX 5000 needs a
Which Studio 5000 version does FLEX 5000 need?
At least 31.00.00 with ControlLogix 5580 and CompactLogix 5380; v32 with CompactLogix 5480; v32.02 for HART modules with ControlLogix 5580 and CompactLogix 5380; v33 with ControlLogix redundancy (
Sources
- Rockwell Automation,
5094-RM001B-EN-P , FLEX I/O to FLEX 5000 I/O Migration Guide Reference Manual, 09/2026 — pp. 5, 9, 11–16, 18–20, 22–29, 31, 47, 58, 62–63 - Rockwell Automation,
5094-TD001M-EN-P , FLEX 5000 Module Specifications Technical Data, 11/2025 — pp. 25–26, 39, 109, 111 - Rockwell Automation,
5094-UM001I-EN-P , FLEX 5000 Standard and Safety I/O Modules User Manual, 06/2026 — pp. 36–37, 40 - Rockwell Automation,
5094-UM002E-EN-P , FLEX 5000 Analog I/O Modules User Manual, 03/2025 — pp. 28–29, 41 - Rockwell Automation,
1794-SG002I-EN-P , FLEX I/O and FLEX I/O-XT Selection Guide, 04/2024 — pp. 4–5, 8, 43 - Rockwell Automation, rockwellautomation.com product page for each of
1794-AENT ,1794-AENTR ,1794-ACN15 ,1794-ACNR15 ,1794-ADN ,1794-IE8H ,1794-OE8H ,1794-OE4 ,1794-IB16 ,1794-IB32 ,1794-OB16 ,1794-OW8 ,1794-IE8 ,1794-IF8IH ,1794-OF8IH ,1794-IT8 ,1794-IRT8 ,1794-TB3 ,5094-AENTR ,5094-IF8IH (lifecycle status, discontinued date, replacement)