Firmware on a ControlLogix or CompactLogix controller is changed with ControlFLASH Plus, with AutoFlash from inside Studio 5000 Logix Designer, or, for devices that do not support CIP, with the older ControlFLASH. The revision comes from Rockwell Automation's Product Compatibility and Download Center (PCDC) and must share its major revision with the Logix Designer version that opens the project. This article follows the ControlFLASH Plus 6.02 help and Rockwell's controller and redundancy manuals. Which software version goes with which controller: RSLogix 5000 and Studio 5000 Logix Designer versions.
1. ControlFLASH Plus, ControlFLASH and AutoFlash
The ControlFLASH Plus help calls the tool the next generation of ControlFLASH. It updates controllers, I/O, drives, servo drives and overloads, several in one operation, and downloads firmware from the PCDC. It updates only devices that support the Common Industrial Protocol (CIP); for other devices the help points to the legacy ControlFLASH. FactoryTalk Linx 6.60.00 and FactoryTalk Services Platform 6.60.00 must be installed first, with the communication drivers configured and tested in FactoryTalk Linx. From ControlFLASH Plus 2.00.00 an optional package installs both.
Both tools can run on one computer and share one policy, ControlFlash, in FactoryTalk Administration Console; its Firmware: Update action sets who may update devices. Uninstalling ControlFLASH cuts ControlFLASH Plus off from the older MSI-based firmware kits.
AutoFlash is the route from Logix Designer: Who Active, select the controller, Update Firmware, choose the revision. For ControlLogix 5570 and 5560,
2. Choosing the revision: PCDC, kits and the major revision
Controller firmware and Logix Designer must have the same major revision;
Firmware comes as a Device Management Kit (DMK): one file with everything needed to update one or more catalogue numbers, the digital signature files and, where included, the release notes. ControlFLASH Plus looks for kits in the monitored folders set under Settings, Firmware Locations; the help advises against the legacy ControlFLASH installation folder, where files can in rare cases be deleted. A kit whose publisher is not yet trusted brings up a prompt, and the update goes on only if the publisher is trusted.
The help says to specify the exact revision; otherwise the result is unpredictable. Connected to the PCDC, the Manage Firmware tab shows each device's lifecycle status and each revision's release notes. A firmware series that does not match the device series is flagged in the Status column.
3. Before flashing: mode, faults, SD card, security
The ControlLogix manuals require the controller to be in Remote Program or Program mode with all major recoverable faults cleared (
The help adds: update only when the process can stop and the devices can be taken out of service, check connections and bandwidth, and keep the computer powered and out of sleep mode, because sleep can interrupt the update.
Two more things can undo or disturb an update:
- SD card. On a 5570 with a locked card set to load On Power Up, the firmware is not updated and the stored firmware and project load instead (
1756-UM001Q p. 50). On a 5580 the update switches the card's load option to User Initiated where it can; on a locked card it cannot, and the card's firmware can overwrite the new firmware (1756-UM543 ). PDF edition:1756-UM543 . - CIP Security. On a CIP-secured device, ControlFLASH Plus warns that communications may be lost after the update, because flashing can disturb security information; it gives the same warning while a CIP Security configuration is in progress. See CIP Security on ControlLogix 5580 and CompactLogix 5380.
4. The update and the order of devices
On the Flash Devices tab: set the browse path, tick the devices, pick a revision in the Flash To column, read the warnings, and open the Compatibility dialog box for any device marked Not compatible or Maybe compatible. After Next, revisions not yet on the computer are downloaded from the PCDC once the licence agreement is accepted; firmware that is not in a DMK is installed by hand, followed by Refresh Firmware. Flash starts the update; Retry repeats the devices that failed or were cancelled. A flash report is saved as a CSV file.
The Status column moves through Pending, Transmitting update, Polling for power-up and Flash finished, or ends in Failed, Flash interrupted or Canceled. Cancel stops only pending updates; running ones finish.
ControlFLASH Plus sets the order itself, from the topology and parent-child relationships. Up to version 2.00.00 it flashes up to 20 devices at once, but parents before children, peers on a linear bus (Ethernet linear or DLR, SERCOS) one after another, and a device with several active ports, such as a
For GuardLogix 5580, selecting the safety controller, for example a
5. When an update is interrupted
ControlFLASH Plus shows the number of interrupted flashes at the top of the Flash Devices tab: click View, then Resolve in the device's Status column, and follow the Flash interrupted dialog box.
6. Redundant pairs: one bundle, secondary chassis first
For a redundant ControlLogix pair,
The manual's chapter on online firmware updates (pp. 187–195) runs in this order: verify the version of the Redundancy Module Configuration Tool (RMCT), prepare the project, update the redundancy module in the secondary chassis and then in the primary, update the other modules in the secondary, download the project to the secondary controller, lock the system and initiate a locked switchover, update the new secondary, and synchronise. The Logix Designer 37.00 help adds that the secondary is disqualified first, the project is uploaded from the primary, converted and downloaded to the secondary, and redundancy is off during the update, so the secondary cannot take over if the primary fails. Firmware cannot go to a locked primary or through a synchronised or locked secondary.
The RMCT 10.01 help sets Auto-Synchronization to Never and allows Lock For Update and Initiate Locked Switchover only from the RMCT opened on the primary redundancy module. If a locked switchover fails, both redundancy modules show DISQ and control is lost.
What we check first
This is TDL's practice, not a Rockwell Automation requirement.
- We back up the program and record the current revision of every module in the chassis first.
- We run PCDC Compare for each catalogue number against the Logix Designer version the plant uses, and read every release note between the old and the new revision.
- We keep the old DMK on the laptop, so the way back is ready.
- We check the SD card: load option, lock, and which firmware is stored on it.
- We ask whether CIP Security is deployed and who holds the policy.
- We flash on mains power with sleep off, inside a shutdown window agreed with the plant; on a redundant pair, the locked switchover is agreed with operations.
- We file the flash report with the backup.
Firmware work at TDL
TDL Industrial Automation is a System Integrator in the Rockwell Automation PartnerNetwork. At Samsung's SEHC complex our scope includes ControlLogix firmware migration and redundancy reconfiguration, and the preventive maintenance of the PLC stations includes firmware and redundancy checks. The same work is a service package, controller firmware upgrade and Studio 5000 compatibility check, ending with the final revision table at handover. Related: Rockwell PLC security, FactoryTalk Linx cannot see the controller, Rockwell system upgrades.
Frequently asked questions
Which software updates ControlLogix and CompactLogix firmware?
ControlFLASH Plus, or AutoFlash from Logix Designer. ControlFLASH Plus updates only CIP devices; the legacy ControlFLASH handles the rest. ControlFLASH Plus needs FactoryTalk Linx 6.60.00 and FactoryTalk Services Platform 6.60.00.
Why does ControlFLASH Plus say the device is not in the correct mode?
The controller is in Remote Run or Hard Run. The manuals require Remote Program or Program mode with all major recoverable faults cleared; change the mode in Logix Designer or on the controller, then refresh.
What happens if a ControlLogix firmware update is interrupted?
ControlFLASH Plus marks it Flash interrupted and offers Resolve in the Status column. For ControlLogix 5570 and 5560,
Can firmware be updated on a running redundant ControlLogix system?
Yes, the secondary chassis first: update it, download the converted project, lock the system and initiate a locked switchover, then update the new secondary and synchronise. Redundancy is off during the update, and a failed locked switchover leaves both redundancy modules in DISQ with control lost.
Where do I download ControlLogix firmware?
From the Product Compatibility and Download Center, as Device Management Kits that ControlFLASH Plus can download directly. Logix Designer also installs firmware, but that is the initial release of its version.
Sources
- Rockwell Automation, ControlFLASH Plus Help 6.02 (last update December 2025): ControlFLASH Plus overview, Getting started, Device Management Kit, Update devices, Messages in the status column, Flash operation statuses, Fix interrupted flash operations, Canceling flash operations, Compatibility dialog box, Safety controller and partners, View a flash report, Flash scheduling, Manage Firmware tab, Configure ControlFLASH Plus policy and The co-existence of ControlFLASH and ControlFLASH Plus
- Rockwell Automation, ControlLogix 5580 and GuardLogix 5580 Controllers User Manual
1756-UM543 , online edition (last update December 2025, supersedes1756-UM543S-EN-P ): Controller Firmware and Logix Designer Application Compatibility, Obtain Controller Firmware, Use ControlFLASH Plus Software to Update Firmware, Use AutoFlash to Update Firmware, Firmware Upgrade Guidelines for Safety Controllers and Use the Memory Card PDF edition:1756-UM543 . - Rockwell Automation,
1756-UM001Q-EN-P , ControlLogix 5570 and 5560 Controllers User Manual, 12/2024 — p. 48–58 - Rockwell Automation,
1756-UM015O-EN-P , Redundancy Systems User Manual, 07/2026 — p. 39–40, 187–195 - Rockwell Automation,
5069-UM001N-EN-P , CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual, 01/2026 — p. 19 - Rockwell Automation, Redundancy System Update, Studio 5000 Logix Designer 37.00 help
- Rockwell Automation, System Update Tab Overview, FactoryTalk Linx Redundancy Module Configuration Tool 10.01 help (
1756-RM2 ) - Rockwell Automation, Product Compatibility and Download Center
Read 15 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.