A new Stratix 5200 (
1. The nine Stratix 5200 catalog numbers
Stratix 5200 switches are Layer 2 fixed switches in 6, 10 and
| Catalog number | Copper ports | Combo / SFP | Firmware | CIP Sync | DLR rings | PRP, NAT |
|---|---|---|---|---|---|---|
| 4 FE | 2 GE SFP | Base | – | – | – | |
| 4 GE | 2 GE SFP | Full | Yes | – | – | |
| 8 FE | 2 GE combo | Base | – | – | – | |
| 8 GE | 2 GE combo | Full | Yes | – | – | |
| 8 GE | 2 GE combo | Full | Yes | 1 | – | |
| 8 GE | 2 GE combo | Full | Yes | 2 | Yes | |
| 18 FE | 2 GE combo | Base | – | 1 | – | |
| 18 GE | 2 GE combo | Full | Yes | 1 | – | |
| 18 GE | 2 GE combo | Full | Yes | 2 | Yes |
FE: Fast Ethernet, GE: Gigabit Ethernet. The page also lists -C2 versions of the 10DP, 10DN and 20DB with the same features. All take 12–48 V DC, are open-style IP30 devices and use the
2. Four ways in: Express Setup, WebUI, Logix Designer, CLI
Per the manual's Table 1 (p. 15–16), VLANs, Smartports, PRP, PTP, port security, STP and NAT can be set in the WebUI or in Logix Designer; DLR, ACLs, QoS, REP, MRP and SNMP only in the WebUI. The Cisco command-line interface (CLI) reaches every feature, from the RJ45 or USB-micro console port or a WebUI page (p. 15, 21, 238).
3. Express Setup and the IP address
After power is applied, the power-on sequence can take up to 140 seconds on a Stratix 5200; it is finished when EIP Mod and Setup flash green (p. 30). The recessed Express Setup button has three modes (p. 27–32):
- Short Press (Setup flashes green, seconds 1–5): port Gi1/3 (Fa1/3 on the B and DB models) blinks. The switch becomes a DHCP server on VLAN 1000 at 192.168.1.254 and gives the computer 192.168.1.1. Setup is finished in the WebUI, then the switch is power-cycled.
- Medium Press (flashes red, seconds 6–10): the switch asks a DHCP server for an address on VLAN 1; setup must be completed within 10 minutes, in the WebUI or Logix Designer. Logix Designer supports only this mode.
- Long Press (flashes green and red, seconds 16–20): factory defaults. All configuration files in internal memory and on the SD card are overwritten.
A switch that already has a non-default configuration leaves Short Press with Setup red for 10 seconds (p. 30). Pressing the button under power can cause an arc, and in a hazardous location an explosion (p. 29).
In the WebUI, the first login uses the default credentials printed in
In Logix Designer the switch is added under Ethernet with the Stratix AOP 19.01.07 or later, at its DHCP address (p. 28, 37–39). The default connection is Input Data; Data adds output tags that can disable ports and, in Run mode, override the WebUI or CLI. The Logix Designer Express Setup page requires a new password, which is also the CIP password (p. 41).
4. VLANs and Smartports
VLAN 1 is the default management VLAN; IDs 1002–1005 are reserved, up to 256 VLANs can be configured, and the WebUI allows 32 SVIs (p. 200). At least one switch port must belong to the management VLAN. Smartport roles go on right after initial setup, before devices are connected; a role that does not match the device can lower QoS or shut the port down (p. 175). Each role needs a VLAN: access for Automation Device, native for Switch for Automation (p. 176).
5. DLR, PRP and CIP Sync
DLR. One ring on the 10DP, 20DB and 20DP, two on the 10DN and 20DN (p. 85). A ring has at least one supervisor and up to 49 ring nodes. In the WebUI the Ring ID is 1 or 2, the ring ports are an adjacent pair N and N+1 with N odd, and supervisor precedence, beacon interval (default 400 µs) and beacon timeout (default 1960 µs) are set (p. 80–81, 85). Rockwell recommends the Multiport Automation Device Smartport role on ring ports (p. 85). Ring design rules: DLR vs PRP.
PRP. Only the 10DN and 20DN (p. 16). The 5200 supports one PRP channel group as a RedBox: Gi1/1 to LAN A, Gi1/2 to LAN B (p. 156). Devices are configured before the PRP cables are connected; the Node and VDAN tables hold 512 entries each (p. 155, 157). PRP infrastructure switches need an MTU of 1506 bytes or more (
CIP Sync. The Full-firmware models support IEEE 1588 PTP (
6. Saving, backup and restore
WebUI changes reach only the running configuration until Save Configuration is clicked (
- File. Administration > Backup & Restore copies the configuration to or from a TFTP, SFTP, FTP or HTTP location. A configuration copied to the switch takes effect only after a reload (p. 218–219).
- SD card. Only the
1784-SDHC8 is supported. Sync copies the configuration, the IOS image or both from internal flash to the card, manually, on each change, after a prompt or daily (p. 220–221, 268). The WebUI cannot sync back from the card (p. 220); Logix Designer's SD Flash Sync page lists both directions (p. 222). A locked card cannot be synced (p. 268). - Swap Drive. The synced card from a failed switch goes into a powered-off, factory-defaulted replacement, which starts with the original image and configuration (p. 268–269).
- Logix Designer. Save/Restore moves the configuration between switch, controller project and file (p. 223).
Firmware goes on in Install mode from one .bin file, with about 1.3 GB free, followed by a reload (p. 275).
7. Replacing a Stratix 5700 with a Stratix 5200
On 15 November 2026, Rockwell's product pages showed Stratix 5700 models discontinued on 1 September 2024, each with a Stratix 5200 as Engineering Replacement:
- Same power terminal blocks and cable orientation; clearance 25.4 mm instead of 50.8 mm (p. 5, 14).
1784-SDHC8 card instead of1784-SD1 ;1783-SFP100T not supported (p. 11).- Spanning tree defaults to Rapid PVST+, not MST as on the legacy switches (p. 17).
- The startup file is startup-config.cfg instead of config.text (p. 16).
- No FlexLinks, no routed (Layer 3) ports (p. 18–19).
The Stratix Migration Assistant, in FactoryTalk Vault for members of a FactoryTalk Hub organization, converts the 5700's config.text (vlan.dat and dmuser.txt are not needed) once the source and destination catalog numbers are chosen, and writes a log file (p. 27–28). The conversion is not exact: credentials and QoS settings are not carried over. Run Express Setup first, test the new file, then load it through Backup & Restore and reload (p. 28–31).
What we check first
This is TDL's practice, not a Rockwell requirement.
- We back up the old switch's configuration and photograph the indicators and cabling.
- We match the catalog number to the job: DLR rings, PRP, CIP Sync, copper speed.
- We agree the IP plan, management and CIP VLANs with the plant, and keep the static address outside any DHCP range.
- We check who else writes to the switch: AOP output tags, the WebUI, the CLI.
- We save the configuration, sync it to the SD card and keep a file copy with the PLC backup.
Stratix work at TDL
TDL Industrial Automation is a System Integrator in the Rockwell Automation PartnerNetwork. On the P&G Cabuyao servo capper, a Stratix 5200 managed switch was configured with a Device Level Ring and Smart Port settings for the connected devices. Our Stratix and VLAN service package ends with network diagrams and configuration files handed over. Related: firewall ports, Rockwell PLC security, industrial networks.
Frequently asked questions
What is the default IP address of a Stratix 5200?
In Short Press Express Setup the switch acts as a DHCP server at 192.168.1.254 on VLAN 1000 and gives the connected computer 192.168.1.1. In Medium Press it takes an address from the plant's DHCP server instead.
Can a Stratix 5200 be set up from Studio 5000 Logix Designer?
Yes, after a Medium Press Express Setup, with the Stratix AOP version 19.01.07 or later. DLR, however, is configured only in the WebUI.
Which Stratix 5200 models support DLR and PRP?
DLR: one ring on
Why did my Stratix 5200 lose its settings after a restart?
WebUI changes stay in the running configuration until Save Configuration is clicked, and the switch starts from its startup configuration.
What replaces a Stratix 5700?
Rockwell's product pages name a Stratix 5200 as Engineering Replacement, for example
Sources
- Rockwell Automation,
1783-UM012N-EN-P , Stratix 5200 and 5800 Managed Switches User Manual, 10/2025 — p. 13–16, 21, 27–41, 80–81, 85, 155–157, 175–176, 200, 218–224, 227, 238, 268–269, 275 - Rockwell Automation,
1783-TD002H-EN-P , Stratix Ethernet Device Specifications Technical Data, 09/2026 — p. 23–25 - Rockwell Automation,
1783-RM001D-EN-P , Stratix Switch Migration Guide, 02/2026 — p. 5, 8, 11, 14–19, 27–31 - Rockwell Automation, product pages:
1783-CMS10DN ,1783-CMS20DN ,1783-CMS10DP ,1783-CMS20DP ,1783-CMS20DB ,1783-CMS10P ,1783-CMS10B ,1783-CMS6P ,1783-CMS6B ,1783-BMS10CGN ,1783-BMS20CGN ,1783-BMS10CGP
Read 15 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.