FactoryTalk Activation is how Rockwell Automation software gets its licence: an activation ties the product licence to a device, such as a hard disk, an Ethernet adapter or a dongle, and FactoryTalk Activation Manager is the tool that downloads, serves, borrows, renews and rehosts those activations. Below: the activation types, the binding (host ID), activation servers and their ports, the seven-day grace period, the messages the help lists with their actions, and rehosting to a new PC. This article follows the FactoryTalk Activation Manager 5.03.00 help (last update July 2026) and the 5.03.00 release notes.
1. How activation works
The help says activation binds the licence of a Rockwell Automation software product to a specific device so the product can run in production. Without an activation, some products do not run at all, some run with reduced functions, and some run for a limited time and then shut down, with or without a warning. The activation is protected by a signature built from machine information at installation; if that signature is tampered with, damaged or deleted, the software does not work, and a corrupted activation has to be rehosted to bind the licence again.
Activation files are kept by default in C:\Users\Public\Documents\Rockwell Automation\Activations (the drive letter can differ). FlexNet licence files end in .lic; CodeMeter (WIBU) data files end in .WibuCmRac and .WibuCmRaU. In a node-locked file the HOSTID line holds the binding of the machine the activation is locked to; a concurrent file names the server, the number of activations and, if the product can be borrowed, the maximum borrow time in hours (BORROW=48 in the help's example). The glossary defines "bound" as a licence linked to a computer, virtual machine or dongle host ID.
Activation Manager runs two services, FactoryTalk Activation Helper and FactoryTalk Activation Service, and depends on NetworkProvider, Windows Management Instrumentation, WMI Performance Adapter, CodeMeter Runtime Server and Rockwell Application Services (needed for logging only).
2. Activation types and dongles
| Type | What the help says |
|---|---|
| Node-locked | Locked to one piece of hardware (Ethernet card, hard disk or dongle) and usable only on that computer. Not every product supports it. |
| Concurrent | Every computer running the software needs a network connection. The software fetches an activation from a designated activation server at start-up and returns it to the pool at shutdown. |
| Borrowed | A concurrent activation checked out to a computer or dongle for a set time, the borrow term. The device can then leave the network; at the end of the term the software is no longer activated and the activation goes back to the pool by itself. |
| Capacity | A concurrent activation counted by a capacity of the product, such as tags, users or computers. |
A dongle-bound activation activates software on any computer the dongle is plugged into. The help lists four Rockwell dongles:
| Catalog number | Name | Storage |
|---|---|---|
| FlexNet | 8 GB | |
| CodeMeter CmStick Compact | None | |
| CodeMeter CmStick | 8 GB | |
| CodeMeter CmCard SD | 4 GB |
Some products need a specific dongle type; with the wrong one the message "Different dongle type needed" names FlexNet or CmStick.
3. Activation server, search path and ports
An activation server is any computer that hosts concurrent activations and shares them on the network. A server operating system is not required, although the help says one manages licences better. A network can have several servers, and each client lists the servers it uses in Path to Activations; the order of that list matters for check-out speed. For a backup server, the help locks the activations to a dongle, puts the same activation files on both servers, lists both servers on every client with the primary first, and moves the dongle to the backup if the primary fails.
| Program | Port | Rule in the help |
|---|---|---|
| lmgrd.exe (Flexera licence daemon) | One TCP port in 27000–27009, default 27000 | Inbound; a non-default port is set in each licence file |
| flexsvr.exe (Rockwell vendor daemon) | One more TCP port, negotiated at runtime | Inbound and outbound |
| FTActivationWebsocketService.exe | TCP 27100 | Inbound and outbound |
| codemeter.exe (CodeMeter runtime server) | TCP and UDP 22350 | Inbound and outbound; CodeMeter also needs Internet access to its time server (cmtime.codemeter.com, .us or .de) |
Setup adds Windows Firewall exceptions for lmgrd.exe and flexsvr.exe. The firewall rules for a whole FactoryTalk system are in FactoryTalk and Logix firewall ports.
The Activation Server Status box (Rockwell Activation icon in the taskbar, Check Servers Now) shows Unresponsive when the computer cannot talk to the server, and Needs update when the server is not on the latest FactoryTalk Activation version. The server log lists licence file locations, bindings, licence types, who checked out, borrowed or returned activations, and borrow and exclude errors; it is overwritten when the server restarts, so save a copy first. If the server does not refresh, the help restarts the FactoryTalk Activation Helper and FactoryTalk Activation Service in Windows Services.
4. Network loss and the grace period
When the connection drops, the computer tries to reconnect to the server three times, 60 seconds apart, and a two-hour TCP timeout on the local computer runs before concurrent activations are checked back in to the server. Network loss, configuration errors, hardware failure, too few activations or any other activation failure do not stop critical Rockwell software at once: it keeps running for a seven-day grace period. A message appears when the grace period starts, every four hours while it runs, at each start-up during it, when it expires, and when an activation is found and the grace period ends. The help says all Rockwell software that affects running systems provides a grace period; design-only products may or may not.
5. Messages and symptoms, with the help's actions
| Message or symptom | Cause in the help | Action in the help |
|---|---|---|
| "Requested too many concurrent activations" | More concurrent activations requested than the product needs | Rehost part of them, or rehost all and request the right number |
| Activation checkout is denied | All activations checked out; activation file modified; invalid licence in the file; Options file restricts access; activation not on the servers in the path | Wait for a return or buy more; rehost; renew; edit the Options file; add the right server to Path to Activations |
| Activations do not appear in the available list | Activation expired; dongle driver missing; rehosted before being returned; server not reachable or stopped | Request a new one; run Install Dongle Driver.bat; refresh the server; fix the path or connection |
| Server unresponsive, concurrent count gone | Rehosting a borrowed activation | Advanced, Refresh This Server, Refresh Server |
| Activation appears as non-renewable | A renewal was blocked, but the database marked it as renewed | Ask Rockwell technical support to reset the activation status |
| Activations not always available on one computer | Bound to a VPN or virtual machine adapter, a docking station or an adapter that powers down | Rehost and bind to a device that is always present |
| Disk drive binding not offered | Only the boot drive is listed when there are several disks | Use the boot drive or the Ethernet MAC ID |
| Cannot borrow | Product does not support borrowing; server not in the path; wrong borrow term; EXCLUDE_BORROW or BORROW_LOWWATER in the Options file | Check the product, path, term and Options file |
| Cannot return a borrowed activation | Wrong path; server has pending changes; clock changed; already returned | Fix the path; refresh; set the client clock as the help explains; check the list |
| Error Borr.010 "Server License not found" | CodeMeter server address removed from the client's search path after borrowing | Keep the server it was borrowed from in the search path until the return |
| Excessive start-up time | Microsoft Loopback Adapter; dead entries in Path to Activations; server stopped; VM network type | Check Microsoft hotfix 979612; remove or reorder paths; refresh; use a bridged network on the VM |
| One computer takes too many activations | Capacity activations are first come, first served | Add MAX count feature HOST name to the Options file |
The Available Activations table shows Total as "n/a" for a concurrent activation that cannot be used because of a disconnected Ethernet card or dongle, or a dongle driver that does not match the hardware. CodeMeter activations expire at a set hour, minute and second, but Activation Manager shows the expiry as the start of that day, so an expired CodeMeter activation can still look available; CodeMeter Web Admin (Container, Licenses) shows the real time. FlexNet activations expire at the end of the day. Activation messages go to the FactoryTalk Diagnostics Local Log, and the command-line utility FTACmdUtility returns 0 on success and numbered codes for each failure, for example 13 (rehost unsuccessful) and 14 (renewal did not succeed).
6. Moving software to a new PC
Rehosting removes the activation from its host and returns it so it can be downloaded again. The help limits it to unexpected or infrequent events, such as a computer upgrade or failure: each serial number can be rehosted on the website three times in any 12 months, and a fourth time needs a call to technical support. Do it on the physical computer that holds the files, and never rehost a borrowed activation: return it first.
- Old PC with Internet: Manage Activations, Rehost Activations; for a concurrent activation with more than one, you can rehost only part of the quantity.
- Old PC without Internet: a data file (default FTAManagerData.xml) carried on removable media to an Internet PC, in four phases; both PCs need the same Activation Manager version and the whole quantity is rehosted.
- No Internet anywhere: Rockwell technical support does the rehost. CodeMeter activations cannot be rehosted manually.
- Old PC dead: after a hard drive crash the help says to contact technical support; for a damaged or deleted activation file, have the binding, serial number and product key ready for them.
On the new PC, Get New Activations needs the serial number and product key from the Activation Certificate. The default binding is usually the right one; a MAC ID is typed as 12 characters without spaces or colons, and a dongle is activated one at a time. Activations requested for the wrong computer, dongle or product are rehosted and requested again.
7. Virtual machines, renewals and versions
Activation Manager 5.03.00 runs on physical hardware or a virtual machine. On VMs the help names three points: an activation bound to a virtual network adapter may not always be available, the VM's network type can slow CodeMeter activations (use a bridged connection), and a borrowed CodeMeter or FlexNet activation activates only applications on the machine that borrowed it, never another virtual or physical machine. Borrowed CodeMeter activations are not visible to Remote Desktop users on a Windows Server client, and Rockwell recommends not using Windows Server on computers that borrow activations or point to an activation server.
Automatic renewal is enabled by default and checks for renewals every 24 hours on computers with time-limited activations and Internet access. Version 5.03.00 installs CodeMeter runtime 8.40b and Flexera 11.19.9.0. Security fixes for Activation Manager are listed in Rockwell vulnerabilities by product. On ThinManager, FactoryTalk Activations are one of two licence modes: see what is ThinManager.
What we check first
This is TDL's practice, not a Rockwell requirement.
- We open Find Available Activations and note product, serial number, expiry, location and Total for every activation before anyone changes anything.
- We copy the bindings from Advanced, Show Bindings, and compare them with the hardware: boot disk, MAC IDs, dongle serial, and whether any binding sits on a VPN, virtual or dock adapter.
- On clients we check Path to Activations: dead entries, order, and that the server answers in Check Servers Now.
- We check the firewall between client and server for TCP 27000–27009, the negotiated flexsvr port and TCP/UDP 22350.
- If a grace-period message is showing, we write down when it started and fix the activation within the seven days.
- Before a PC is replaced, we return borrowed activations, rehost on the old PC and keep the Activation Certificates with the serial numbers and product keys.
FactoryTalk licence support at TDL
TDL Industrial Automation is a System Integrator in the Rockwell Automation PartnerNetwork. Our breakdown support covers troubleshooting on site or remotely on Allen-Bradley systems; see also Rockwell Automation system integrator in Vietnam and, for the activation of FactoryTalk Linx Gateway, FactoryTalk Linx Gateway as OPC UA server.
Frequently asked questions
How long does FactoryTalk software run without an activation?
The help gives a seven-day grace period for Rockwell software that affects running systems, after a network loss, hardware failure, too few activations or another activation failure. A message appears every four hours and at each start-up during the grace period. Design-only products may or may not have one.
How do I move a FactoryTalk activation to a new computer?
Rehost it on the old computer with Manage Activations, Rehost Activations, then use Get New Activations on the new one with the serial number and product key. Each serial number can be rehosted on the website three times in any 12 months; a fourth time needs Rockwell technical support.
What is the host ID in FactoryTalk Activation?
It is the binding: the hard disk, Ethernet MAC ID, virtual machine or dongle that the activation is locked to. In a node-locked activation file it is the HOSTID line, and Advanced, Show Bindings copies it for technical support.
Which ports does FactoryTalk Activation use?
One TCP port in 27000–27009 for lmgrd.exe (default 27000), one more TCP port negotiated at runtime for flexsvr.exe, TCP 27100 for the WebSocket service and TCP and UDP 22350 for CodeMeter.
Why does Activation Manager say "Requested too many concurrent activations"?
More concurrent activations were requested for the product than it needs. The help says to rehost part of them and keep the right number on the computer, or rehost all and request the correct number.
Sources
- Rockwell Automation, FactoryTalk Activation Manager Help 5.03.00 (last update July 2026): Contents, How FactoryTalk Activation works, Types of activations, Supported dongle types, Service dependencies, Firewall ports and rules, Configure the FactoryTalk Activation server, Network connectivity failure, Set up a backup activation server, Rehost Activations page, Rehost activation considerations, Requirements and restrictions for borrowed activations, Activation file details, Command-line utility return values and the Troubleshoot pages
- Rockwell Automation, FactoryTalk Activation Manager 5.03.00 Release Notes (last update July 2026): System requirements and Application notes
Read 15 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.