Status of the 1756-ENBT
The
Replacing an Ethernet module is not simply a matter of pulling the old module and inserting a new one: the new module is a different catalog number in the Studio 5000 I/O tree, so the project has to be edited and downloaded again, and every device talking to this module (HMI, SCADA, other PLCs, drives) needs its connection checked.
The three current replacements — how they differ
Figures from
| Ports | 1 × RJ45 10/100 | 1 × RJ45 10/100 | 2 × RJ45 10/100 | 2 × RJ45 10/100/1000 |
| CIP / TCP connections | 128 / 64 | 256 / 128 | 256 / 128 | 528 / 512 |
| Topology | star | star | star + Device Level Ring (DLR) | star + DLR + PRP |
| Typical role | 1:1 replacement | 1:1 replacement on a star network | DLR ring for distributed I/O, drives | large networks, 1 Gb, PRP redundancy, many HMI/SCADA clients |
Read the table in this order of questions:
- Is the existing network a star or a ring? Star network on ordinary switches →
1756-EN2T is sufficient and the cheapest. A DLR ring already in place or planned with POINT I/O, PowerFlex, Stratix →1756-EN2TR (two ports, closes the ring itself). - How many connections is the ENBT carrying? The ENBT has only 128 CIP / 64 TCP; many systems run close to this limit without anyone having recorded it (SCADA, a historian, a few HMIs and PLC-to-PLC exchange are enough to reach it). The EN2T/EN2TR double this; the EN4TR has about four times the CIP connections and eight times the TCP connections. If the system has ever lost HMI connections when a client was added, go straight to the EN4TR.
- Is system-level network redundancy (PRP) or 1 Gb speed required for a large SCADA/historian? →
1756-EN4TR . This is also the module that goes with ControlLogix 5580 (1756-L8xE ) when ports are needed beyond the embedded port.
What to do when replacing — checklist
- Check firmware and Studio 5000 version on PCDC (compatibility.rockwellautomation.com): which firmware the new module needs, and whether the Studio 5000 version in use has a profile for that catalog number. The EN2T/EN2TR have profiles from older RSLogix 5000 versions; the EN4TR only has a profile in recent Studio 5000 versions — a system still running an old RSLogix 5000 may need the software upgraded as well; PCDC gives the exact minimum version.
- Back up the project (.ACD) and the old module's configuration (IP, subnet, gateway, produced/consumed connection table).
- In the project: replace the module in the I/O tree, keep the old IP address, reset electronic keying (Compatible Module), and review every produced/consumed tag and MSG instruction routed through this Ethernet path.
- Check every partner device: FactoryTalk View HMI, SCADA (AVEVA, Citect, WinCC), OPC server, neighbouring PLCs — their connections point to the IP and slot, not to the module catalog number, so most need no change; but each one must be tested after the swap.
- Replace on site in a short shutdown window: pull the old module, insert the new one (firmware and IP loaded beforehand in the workshop), download the project, check the LINK/NET LEDs, test communications.
When not to replace 1:1
- Systems with more than one ENBT in the same chassis to separate networks (separate SCADA, separate I/O): keep the architecture and replace each module with the corresponding EN2T/EN2TR — do not merge them into one EN4TR just because "it has more connections", as this also removes the network segmentation.
- The controller is also an older-generation
1756-L6x running RSLogix 5000: replacing the Ethernet module is only the first step; plan a migration of the controller as well to 5570/5580 (see1756-L71 ,1756-L83E ) rather than investing piecemeal.
Frequently asked questions
When was the 1756-ENBT discontinued?
Rockwell lists the
Can a 1756-ENBT be replaced with a 1756-EN2T ?
Yes: on a star network with ordinary switches, the
How many connections does the 1756-ENBT support?
According to
When should I choose a 1756-EN4TR instead of an EN2T or EN2TR?
When system-level network redundancy (PRP) or 1 Gb speed is required for a large SCADA/historian, or when the system has lost HMI connections as clients were added. It is also the module that goes with ControlLogix 5580 (
Does moving to a 1756-EN4TR require a Studio 5000 upgrade?
Possibly: the EN4TR only has a profile in recent Studio 5000 versions, so a system still running an old RSLogix 5000 may need the software upgraded as well. PCDC gives the exact minimum version and the firmware the module needs.
Sources
- Rockwell Automation,
1756-TD003R , 1756 ControlLogix Communication Modules Specifications Technical Data, 01/2025 — p. 4–6, 12–13, 41 - Rockwell Automation, Product Compatibility and Download Center (PCDC)
- Rockwell Automation, lifecycle page for each catalog number
1756-ENBT ,1756-EN2T ,1756-EN2TR ,1756-EN4TR on rockwellautomation.com
Read 25 September 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.