PanelView Plus 6 / 1000 to PanelView Plus 7: replacements, cut-outs, power and the ME application

TDL Industrial Automation · Last updated:

PanelView Plus 6 and earlier PanelView Plus terminals are discontinued. The replacements Rockwell names for each model (read 2 November 2026), choosing PanelView Plus 7 Standard or Performance, cut-out adapter kits, 24 V DC power, Ethernet-only communications, converting the FactoryTalk View ME application (.apa, .mer, versions, ActiveX, fonts, firmware) and the swap steps.

PanelView Plus 6 terminals and the earlier PanelView Plus terminals are shown as discontinued on Rockwell Automation's product pages, and for the 700 to 1500 models checked here Rockwell names a PanelView Plus 7 terminal as the replacement. The FactoryTalk View Machine Edition (ME) application moves across: restore the .apa archive or convert the .mer runtime file, open it in a current FactoryTalk View Studio ME, fix what the new terminal does not support, and create a new .mer for the terminal's firmware. The hardware needs its own checks: the panel cut-out, the 24 V DC supply and an Ethernet-only connection to the controller.

Which PanelView Plus do you have?

Three older families are still common in panels:

  • PanelView Plus, the generation before PanelView Plus 6. Rockwell's page for 2711P-T10C4D1, described only as a PanelView plus terminal, shows it discontinued on 31 December 2012 with no replacement named.
  • PanelView Plus 6, sizes 400 and 600, and 700 to 1500. They run Windows CE 6.0; catalog numbers ending in 9 add extended features such as a media player and Office file viewers. Every size comes with AC or DC input, and the 700 to 1500 models can take a communication module for DH+/DH-485, ControlNet or a second Ethernet port.
  • PanelView Plus 6 Compact (2711PC, 400 to 1000), limited to 1 controller, 25 screens and 200 alarms.

The catalog number on the nameplate decides the path. The table shows what Rockwell's product pages listed on 2 November 2026 for common DC touch and keypad models.

Old terminal Status on Rockwell's page Replacement named by Rockwell Status of the replacement
PanelView Plus 6 700 touch, 2711P-T7C4D8 Discontinued 30/12/2021 2711P-T7C22D9P, Performance 7 in. Active
PanelView Plus 6 1000 touch, 2711P-T10C4D8 Discontinued 30/12/2021 2711P-T10C22D9P, Performance 10.4 in. Active
PanelView Plus 6 1000 keypad, 2711P-K10C4D8 Discontinued 30/09/2022 2711P-B10C22D9P, Performance 10.4 in. keypad/touch Active
PanelView Plus 6 1250 touch, 2711P-T12C4D8 Discontinued 30/12/2021 2711P-T12W22D9P, Performance 12.1 in. widescreen, 1280 × 800 Active
PanelView Plus 6 1500 touch, 2711P-T15C4D8 Discontinued 30/09/2021 2711P-T15C22D9P, Performance 15 in. Active
PanelView Plus 6 400 keypad, 2711P-K4M20D8 Discontinued 30/12/2022 No planned replacement –
PanelView Plus 6 600 touch, 2711P-T6C20D8 Discontinued 30/09/2021 No planned replacement –
PanelView Plus 6 Compact 1000 touch, 2711PC-T10C4D8 Discontinued 30/12/2021 2711P-T10C21D8S, Standard 10.4 in. Active

Two details in this table change the work. The keypad model is replaced by a keypad and touch terminal, so operators get a touch screen as well. The 1250 is replaced by a widescreen 12.1-inch terminal, so every screen of the application has to be laid out again to use the wider display. The Performance replacements in the table are all described on their product pages as Windows 10 IoT Core terminals, which limits what the application may contain (see Series B below).

The AC touch models follow a longer chain. For 2711P-T7C4A8, 2711P-T10C4A8 and 2711P-T15C4A8, Rockwell names an AC PanelView Plus 7 Performance terminal that was itself discontinued on 30 November 2021, and that terminal's listed replacement is the 24 V DC model in the table; the HMI article traces the 1000 case. A listed replacement can itself be discontinued later, so check the product page again on the day you order.

From PanelView Plus 6 to PanelView Plus 7Six groups of old terminals, the replacement Rockwell names for each and what to check before ordering: adapter kit, 24 V DC supply, resolution and the limits of the Standard family.From PanelView Plus 6 to PanelView Plus 7ROCKWELL REPLACEMENTCHECK700, 1000,1500 touchPanelView Plus 7 Performancetouch, same nominal sizeadapter kit2711P-RAAT7, RAAT10, RAAT15;24 V DC supply1000 keypadPerformance 10.4 in. keypadand touch, 2711P-B10C22D9Padapter kit 2711P-RAAK10;operators also get a touch screen1250 touchPerformance 12.1 in. widescreen1280 × 800, 2711P-T12W22D9Pevery screen laid out again;adapter kit 2711P-RAAT12AC touchmodelsthe replacement chain ends at a24 V DC Performance terminaladd a 24 V DC power supplyin the panelCompact 1000PanelView Plus 7 Standard10.4 in., 2711P-T10C21D8Sno adapter kit; 1 controller,100 screens, 500 alarms400 and 600no planned replacementfrom Rockwellchoose by size, input typeand application limitsBased on Rockwell product pages (read 2 November 2026), Rockwell2711P-AP004F, VIEW-IN002C and 2711P-UM007I. Figure: drawn by TDL.
Figure 1: From PanelView Plus 6 to PanelView Plus 7. On a phone, swipe sideways to see the whole figure.

PanelView Plus 7 Standard or Performance

Rockwell sells PanelView Plus 7 in two families, both designed in FactoryTalk View Studio ME:

Item PanelView Plus 7 Standard PanelView Plus 7 Performance
Input Touch only Touch, or keypad and touch
Application limits 1 controller, 100 screens, 500 alarms No limit on controllers, screens or alarms
Operating system Windows CE 6.0 Series A: Windows CE 6.0. Series B (Series C for stainless steel): Windows 10 IoT Core
Power 24 V DC (18 to 30 V), non-isolated, 35 W max 18 to 30 V DC isolated, 50 W max; AC (100 to 240 V) only on aluminium Series A
FactoryTalk View ME 8.0 or later; Series C hardware 8.x or later, Series D 13.x or later 8.x or later
Cut-out adapter kits Must not be used Available for PanelView Plus 6 700 to 1500 cut-outs

Rockwell's PanelView Plus 6 to PanelView Plus 7 conversion guide (2711P-AP004F, April 2021) names a Performance terminal with an adapter plate as the primary replacement for the 700 to 1500 models, and a Standard terminal as the secondary option for the 700, 1000 and 1500 sizes. It gives no recommended Performance conversion for the 400 and 600 models. The guide was written before some of the replacements it lists were discontinued, so take its tables as a map and the product page as the answer.

A Standard terminal fits when the application stays within its limits and the panel can be cut for the new size. A keypad, more than one controller, more than 100 screens or the adapter kits all point to Performance. The software side of the choice, ME versus FactoryTalk Optix, is covered in FactoryTalk View SE vs ME vs Optix.

The panel cut-out and the power supply

The new terminal can need a smaller opening than the old one. A PanelView Plus 6 1000 touch terminal needs a cut-out of 224 × 305 mm (height × width); a PanelView Plus 7 10.4-inch touch terminal, Standard or Performance, needs 224 × 269 mm. Rockwell's adapter kits close that gap without cutting the panel:

Old cut-out Adapter kit New terminal
PanelView Plus 6 700 touch 2711P-RAAT7 6.5 in. touch
PanelView Plus 6 700 keypad or keypad/touch 2711P-RAAK7 6.5 in. keypad/touch
PanelView Plus 6 1000 touch 2711P-RAAT10 10.4 in. touch
PanelView Plus 6 1000 keypad or keypad/touch 2711P-RAAK10 10.4 in. keypad/touch
PanelView Plus 6 1250 touch 2711P-RAAT12 12.1 in. touch
PanelView Plus 6 1250 keypad or keypad/touch 2711P-RAAT12K 12.1 in. touch
PanelView Plus 6 1500 touch 2711P-RAAT15 15 in. touch
PanelView Plus 6 1500 keypad or keypad/touch 2711P-RAAK15 15 in. keypad/touch

The kits are for PanelView Plus 7 Performance terminals only. Rockwell warns that a Standard terminal installed with them can have its bezel damaged and its seal compromised. To keep the NEMA Type 4X rating, the instructions give a torque of 3.90 N·m (30 lb·in) for the adapter plate nuts and ask for no sealing compound on the gasket. The Performance manual also sets a panel thickness of 1.5 to 4.8 mm and minimum clearances of 51 mm above, 102 mm below and 25 mm at the sides (102 mm on the side with the SD card slot). At VinWonders Nha Trang, TDL replaced a PanelView Plus 1250 on a roller coaster console with a PanelView Plus 7 Performance 12-inch terminal and its adapter kit, without cutting the console.

Then the power. PanelView Plus 6 700 to 1500 terminals accept 18 to 32 V DC (70 W max) or 100 to 240 V AC. The PanelView Plus 7 DC range is 18 to 30 V, and Series B Performance and all Standard terminals are DC only. Where the old terminal ran on AC, add a 24 V DC supply; the Performance manual lists 2711P-RSACDIN (85 to 265 V AC input), 1606-XLP95E and 1606-XLP100E.

Communications: Ethernet only

PanelView Plus 7 terminals communicate over Ethernet only, and Rockwell states that PanelView Plus 6 applications set to serial communication must be changed to Ethernet. There is no DH+, DH-485 or ControlNet module for the new terminal. For other protocols, Rockwell points to its Encompass partners and names Anybus and ProSoft Technology gateways. The other route is to put the controller on EtherNet/IP; the controller-side options are in upgrade paths for legacy Allen-Bradley systems. On the PVEP DMDP-A platform, ControlNet bridge modules were replaced with 1756-EN2TR EtherNet/IP modules and the PanelView Plus 6 terminals with PanelView Plus 7 Performance.

Inside the application, communications are set up in FactoryTalk Linx, formerly called RSLinx Enterprise. The drivers, devices and shortcuts the terminal uses are set on the Runtime (Target) tab of the Communication Setup editor, and when the .mer is loaded the terminal asks whether to replace its communication settings with the ones defined in the application. If the new terminal shows no data after the swap, follow PanelView Plus 7 shows no data from the PLC. Third-party controllers are reached through KEPServer on both families.

Converting the FactoryTalk View ME application

Find the right file. An .apa file is an archive made by the FactoryTalk View ME Application Manager; restoring it creates the development application again, with its security configuration. If only the .mer runtime file is left, it can be converted back to a development application when it was created with FactoryTalk View ME 5.00 or later and its conversion setting allows it: a .mer can be set to always allow conversion, to never allow it, or to require a password. Conversion restores the shortcuts and the runtime communication configuration, not the communication setup of the original design computer. When the old terminal has failed, the application may still be recoverable from it, as at the WindStarZ ride at VinWonders Grand Park, where TDL loaded the recovered application onto a PanelView Plus 7 Standard terminal.

Open it in a current Studio. An application from an earlier version is converted to the current version when it is opened, and after that earlier versions of Studio cannot open it, so keep the original archive. IP addresses with a leading zero must be corrected first, because FactoryTalk Linx reads them as octal.

Resize the screens. Apart from the 7-inch and 15-inch models, PanelView Plus 7 terminals have a higher resolution than PanelView Plus 6. An application that is not resized runs in the top-left corner of the screen; resizing means reworking the layout of each display, especially when moving to a widescreen terminal.

Check what Series B does not do. On Windows 10 IoT Core, Rockwell's release notes list: third-party ActiveX controls are not supported (only the FactoryTalk View ME ActiveX controls are); the web browser ActiveX control becomes a button that opens Microsoft Edge; data logs and recipes cannot be stored on a network share; third-party applications, .exe files and autorun are not supported; screenshots, the screen saver and Office file viewers are gone; ViewPoint runs without HTTPS. Count every ActiveX control and data log path in the application before choosing Series B.

Fonts. By default only plain fonts are installed on the terminal, so bold or italic text that looks correct in Studio can be cut off at runtime. The bold and italic versions are on Rockwell's font CDs and can be transferred to the terminal as .ttf or .ttc files with the ME Transfer Utility.

Create the runtime file for the terminal. In Create Runtime Application, "Save as type" selects the ME Station version of the target. An earlier ME Station cannot run a .mer made for a later version, so match the firmware on the terminal. If the application uses a feature that version does not support, validation fails, no .mer is created and the reasons are written to a ValidationResults text file.

Firmware. Rockwell's release notes say Series B Performance terminals do not ship with firmware pre-installed, and the user manual asks for the firmware to be updated with FactoryTalk View ME Station before the terminal goes onto a production network. It is installed from a USB storage device or with ControlFLASH or ControlFLASH Plus, using files from Rockwell's Product Compatibility and Download Center. Standard terminals are updated from a storage device, with a firmware upgrade card or over the network.

Moving a FactoryTalk View ME application to PanelView Plus 7Eight steps from the top: back up the .mer and .apa, restore or convert, open in the current Studio, resize the screens, replace unsupported items, set the Runtime (Target) shortcut, create the .mer for the terminal's version, load and test every screen.Moving a FactoryTalk View ME application to PanelView Plus 71Back upcopy the .mer from the terminal with the ME Transfer Utility,find the matching .apa, photograph every screen2Restore or convertrestore the .apa in Application Manager; a .mer from 5.00 or later, if conversion is allowed3Open in the current Studio MEkeep the original, earlier Studio versions cannotreopen it; fix IP addresses with a leading zero4Resize the screenshigher resolution except at 7 and 15 in.; not resized, it runs in the top-left corner5Replace unsupported itemsthird-party ActiveX and network-share data logs (Series B), bold and italic fonts6Set up Ethernet communicationsdrivers, devices and shortcuts on the FactoryTalk Linx Runtime (Target) tab7Create the .merselect the terminal's ME Station version; read the ValidationResults file on errors8Load and testanswer Yes to replacing the communication settings, test every screen with the operatorsAn earlier ME Station cannot run a .mer created for a laterversion: build the .mer for the firmware on the new terminal.Based on FactoryTalk View ME 16.00 and FactoryTalk Services Platform 6.60 help,Rockwell 2711P-AP004F, 2711P-RN005C and 2711P-UM007I. Figure: drawn by TDL.
Figure 2: Moving a FactoryTalk View ME application to PanelView Plus 7. On a phone, swipe sideways to see the whole figure.

Step by step

  1. Record the old terminal. Catalog number and series from the nameplate, firmware, the ME version used for the .mer, the controller path, and a photo of every screen.
  2. Back up. Copy the .mer from the terminal with the ME Transfer Utility and find the matching .apa. If only the .mer exists, check that it converts before going further. FactoryTalk AssetCentre can keep these files afterwards.
  3. Choose the terminal. Look up the replacement on Rockwell's product page, then check Standard against Performance, the cut-out, the adapter kit and the power supply.
  4. Convert on the bench. Restore or convert, resize, replace unsupported objects and fonts, set the Runtime (Target) shortcut, and create the .mer for the terminal's firmware.
  5. Test before the shutdown. Load the .mer on the new terminal and run it against the controller, or a test controller, screen by screen with the operators.
  6. Swap. Fit the adapter kit, wire 24 V DC and Ethernet, load the .mer, answer Yes to replacing the communication settings, and test again on the real machine.
  7. Archive both applications, old and new, with the runtime files.
Checks before the swapSix groups of checks before the shutdown: panel cut-out, power supply, communications, firmware and version, application features, backups.Checks before the swapPanel cut-outold 1000 touch: 224 × 305 mmnew 10.4 in.: 224 × 269 mmadapter kits for Performance onlyPower supplyPanelView Plus 6 700–1500:18–32 V DC or ACPanelView Plus 7: 18–30 V DCAC only on Performance Series ACommunicationsEthernet only; DH+, DH-485,ControlNet through a gatewayor a controller on EtherNet/IPFirmware and versionSeries B ships without firmware; buildthe .mer for the version on the terminalApplication featuresActiveX, data log paths, fonts, the screenand alarm limits of the Standard familyBackups.mer, .apa, photos of every screen; archiveboth the old and the new applicationBased on Rockwell 2711P-UM006I, 2711P-UM007I, 2711P-UM008K,2711P-RN005C, 2711P-AP004F and VIEW-IN002C. Figure: drawn by TDL.
Figure 3: Checks before the swap. On a phone, swipe sideways to see the whole figure.

TDL's work on these upgrades is described on the PanelView Plus HMI migration page and in the PanelView Plus 6 to Plus 7 service package. PanelView Standard, PanelBuilder32 and other HMI platforms are covered in legacy HMI/SCADA migration paths, and controller upgrades on the Rockwell upgrade page.

Frequently asked questions

What replaces a PanelView Plus 6 1000?

For the DC touch model 2711P-T10C4D8, Rockwell's product page names the PanelView Plus 7 Performance 2711P-T10C22D9P, shown as active on 2 November 2026. The keypad model 2711P-K10C4D8 is replaced by the keypad and touch terminal 2711P-B10C22D9P. The AC touch model 2711P-T10C4A8 follows a longer chain, through a discontinued AC PanelView Plus 7 terminal, that ends at the same 24 V DC terminal 2711P-T10C22D9P.

Can I load my PanelView Plus 6 .mer file straight onto a PanelView Plus 7?

Plan on converting it. Most PanelView Plus 7 sizes have a higher resolution, and an application that is not resized runs in the top-left corner of the screen; Series B terminals do not support third-party ActiveX controls. Restore or convert the application in a current FactoryTalk View Studio ME, fix these items, and create the .mer for the ME Station version on the terminal, since an earlier ME Station cannot run a .mer made for a later version.

Will the PanelView Plus 7 fit the old panel cut-out?

A PanelView Plus 7 Performance terminal fits PanelView Plus 6 700 to 1500 cut-outs with Rockwell's adapter kits, such as 2711P-RAAT10 for the 1000 touch model. Standard terminals must not be installed with these kits; with a Standard terminal the panel is cut for the new size.

Does PanelView Plus 7 support DH+, DH-485 or ControlNet?

No. PanelView Plus 7 terminals use Ethernet only, and serial applications must be changed to Ethernet. Rockwell points to partner gateways from Anybus and ProSoft Technology for other protocols; the alternative is to move the controller onto EtherNet/IP.

Are ActiveX controls supported on PanelView Plus 7?

Series B Performance terminals, on Windows 10 IoT Core, support only the FactoryTalk View ME ActiveX controls; third-party ActiveX controls are not supported, and the web browser control becomes a button that opens Microsoft Edge. The Performance replacements Rockwell lists for the PanelView Plus 6 700 to 1500 models in the table are Windows 10 IoT Core terminals, so count the ActiveX controls in the application before ordering.

Sources

Read 2 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.