Two separate jobs: program and I/O
A
- Program: convert the RSLogix 5 file into a Studio 5000 Logix Designer project (.ACD), then review, correct and test it.
- I/O hardware: keep the 1771 racks during a transition period, or replace them fully with ControlLogix I/O / distributed I/O on EtherNet/IP.
The two decisions are linked from the very first step: Rockwell's tool asks for the I/O strategy before it generates the new project.
Converting the program with Logix Designer Export
Logix Designer Export is built into RSLogix 5: open the project, Save As, and choose the .ACD format (
In the export dialog the engineer selects the controller family, the controller catalog number and the target firmware/software revision (p. 13), then the I/O strategy (p. 14–15):
- Keep Existing I/O — retains the I/O modules and devices of the old project; the tool automatically adds a bridge device so that Logix can scan the existing
PLC-5 I/O. - Update All I/O — Rockwell's preferred option: migrates the modules to the latest ControlLogix/CompactLogix I/O family, with no bridge device. If the I/O is placed in remote racks, all remote I/O generated by the tool is on EtherNet/IP.
What the tool does, and what stays manual
Rockwell is explicit: the result is syntactically correct, but the intent of the original program can be lost, because of different rules for precedence, indexed addressing and I/O addressing (p. 9). Suspect rungs are flagged with a PCE instruction; instructions with no equivalent become UNK instructions. Both must be deleted and replaced with correct logic (p. 16–17).
| Item | How the tool handles it | Work required afterwards | Source ( |
|---|---|---|---|
| Languages | Converts ladder only | Rewrite SFC and structured text | p. 9, 22 |
| N files become DINT, sign-extended; B files become DINT with the upper 16 bits zero-filled | Review instructions that use masks, as they may behave differently; rework BSL, BSR and BTD on B files | p. 21, 25–26, 31 | |
| Timers | Converted to a 1 ms time base, presets scaled from the old time base (e.g. 0.01 s, preset 20 → 200) | Every reference to .PRE/.ACC generates a PCE and must be reviewed | p. 21, 32 |
| I/O | Creates matching I and O arrays (I:002 → I[2]) but leaves them empty | Map the new I/O tags into the arrays with CPS, BTD or MOV; Logix I/O updates asynchronously to the scan, so buffer it with CPS | p. 10, 19–20 |
| Block transfers (BTR/BTW) | Converted to MSG; rack/group/module ignored | Reconfigure the path; adjust 16 → 32 bit with RES/FAL | p. 57–58 |
| ControlNet I/O (CIO) | Converted to MSG, PCE generated | Reconfigure | p. 58 |
| MSG instructions | Only partially converted | Complete the Communication tab and the path to the device | p. 20, 41 |
| PID | Structure converted | Many parameters do not map directly — the loop must be verified | p. 41, PCE 114 |
| Main control programs (MCP) | Become event tasks, called by EVENT instructions in the continuous task | Check execution order | p. 23 |
| STI interrupt | Becomes a periodic task | Set its priority; S:2/1 (STI enable/disable) generates a PCE | p. 23 |
| PII input interrupt | Not supported in Logix; converted to a subroutine | Call the routine from your logic | p. 23–24 |
| Indirect addressing | Element and bit indirection converted; indirect file numbers (N[N7:0]:5) are not | Rewrite, for example with a multi-dimensional array if the files are consecutive | p. 46–47 |
| FOR/NXT/BRK | Structure is fundamentally different in Logix | Logic usually has to be restructured | p. 76 |
| AGA3, AGA7, API routines (CIR/COR instructions) | Not converted, PCE generated | Rebuild the gas flow calculations | p. 58, 76 |
| Comments | Instruction comments not converted; address comments become alias tags | Delete unused aliases to save memory | p. 21 |
The AGA3/AGA7/API row matters for gas stations: if the
Keep or replace the 1771 I/O
Keep the 1771 racks during a transition. The
Replace the I/O fully. This is the option Rockwell recommends in the conversion tool ("Update All I/O"). The new I/O sits in the ControlLogix chassis or is distributed on EtherNet/IP; if the old system uses ControlNet, the network should move to EtherNet/IP at the same time (see Upgrade paths for legacy Allen-Bradley systems). Existing enclosures can be kept and refitted inside; field wiring is re-terminated to the new drawings.
The HMI that comes with it
How TDL does it
- Start from the program that is actually running: upload from the
PLC-5 on site and compare it with the stored offline copy before converting. - Inventory: racks, I/O and block-transfer modules, networks (DH+, Remote I/O, ControlNet), MSG list, third-party devices, HMI.
- Convert and review: run Logix Designer Export, resolve every PCE/UNK, map the I/O, rewrite what the tool does not convert.
- Bench test: the new program runs on a real controller with simulated I/O and is checked function by function against the old system.
- FAT with operations, then cut over in a shutdown window; the cutover plan should include a fallback to the old system, agreed with the plant in advance.
- Handover: Logix project, as-built drawings, documentation and backup.
PLC-5 projects completed by TDL
- Pha Lai II Thermal Power Plant subsidiary systems (2020):
PLC-5 and Citect to ControlLogix and FactoryTalk View SE (Rockwell Automation as EPC contractor; TDL built the panels, carried out PLC/HMI programming and networking, and commissioned) for ash handling, flue-gas desulphurisation (FGD), electrostatic precipitator, soot blower, water and wastewater treatment. - Phu My Gas Distribution Station (2019):
PLC-5 /HIMA to an ICSS on redundant ControlLogix and AADvance. - PV Gas, other stations: an LBV station (2013), a loading arm system (2014), and the piping monitoring system at Ba Ria Gas Distribution Station (2014,
PLC-5 /RSView32 to redundant ControlLogix and FactoryTalk View).
SLC 500 follows the same approach — for example Dinh Co Gas Processing Plant, CC01 turbo expander (2019).
Frequently asked questions
Are RSLogix 5 and the 1756-DHRIO still sold?
According to the product pages on rockwellautomation.com (read 13 November 2026), RSLogix 5 programming software has been discontinued since 31 December 2025 and the
Which tool converts a PLC-5 program to ControlLogix?
Logix Designer Export, built into RSLogix 5: open the project, Save As, and choose the .ACD format (
Does Logix Designer Export convert the whole PLC-5 program?
No. The tool converts ladder only, and the result is syntactically correct but the intent of the original program can be lost (
Can the 1771 I/O racks be kept when moving to ControlLogix?
Yes, during a transition: the
Sources
- Rockwell Automation,
1756-RM085I-EN-P , ConvertingPLC-5 or SLC 500 Logic to Logix-Based Logic, 09/2025 — pp. 9–11, 13–17, 19–26, 31–32, 41, 46–47, 57–58, 76 - Rockwell Automation,
1756-UM514C-EN-P , ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual, 06/2014 — pp. 13–15, 101–103 - Rockwell Automation, RSLogix 5 and
1756-DHRIO product pages on rockwellautomation.com
Read 13 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.