Quick reference
| Running system | Target named by Rockwell | What can be kept | Rockwell documents |
|---|---|---|---|
| SLC 500, 1746 I/O | CompactLogix 5380 + Compact 5000 I/O | Field wiring (via 1492 conversion system), existing mounting holes | |
| MicroLogix 1500 | CompactLogix 5370 (L1/L2) | 1769 I/O — L2 only | |
| MicroLogix 1000/1100/1200/1400 | Micro800 | Logic, converted with the tool in Connected Components Workbench | |
| CompactLogix |
CompactLogix 5380 | 1769 I/O, run as a remote rack via |
|
| CompactLogix |
CompactLogix 5370; 5380 + |
1769 I/O (with 5370) | |
| PanelView Standard / Enhanced | PanelView Plus 7 | Application, imported into FactoryTalk View ME | |
| FLEX I/O (1794) | FLEX 5000 (5094) | Similar mounting footprint; wiring must be moved by hand | |
| ControlNet | EtherNet/IP | ControlNet fibre (connectors usually replaced) | |
| ControlLogix | 1771 I/O racks during the transition, via |
The numbers above are public Rockwell Automation publications. Each path is detailed below; page numbers refer to the editions TDL uses.
SLC 500 → CompactLogix 5380: keep the wiring, change in steps
Hardware. The 1492 conversion system lets you keep the field wiring: the removable terminal block of the 1746 module plugs straight into a conversion module, with a Compact 5000 module underneath (
Changing in steps.
Controller and memory.
Program. RSLogix 500 v12 saves straight to an .ACD file; older versions use the RSLogix Project Migrator (
MicroLogix
MicroLogix 1500 → CompactLogix 5370 L1/L2. Rockwell lists MicroLogix 1500 as discontinued (
MicroLogix 1000/1100/1200/1400 → Micro800. Converted with the MicroLogix to Micro800 Converter in Connected Components Workbench (
CompactLogix 1768-L4x → CompactLogix 5380
PanelView Standard / Enhanced → PanelView Plus 7
- Application: the .pba file (or the .pva if the .pba is lost) is imported into FactoryTalk View Studio ME, with scaling to the new resolution; results are written to convert.log (
2711P-AP006F p. 43–48). - Communications: PanelView Plus 7 has Ethernet only; applications on serial links must move to EtherNet/IP (
2711P-AP005F p. 2, p. 34). DH+,DH-485 , Remote I/O, DeviceNet and ControlNet are no longer available on the new terminal (2711P-AP006F p. 55). - What must be fixed by hand: bit arrays become memory tags, strings are limited to 82 characters, "retain last state" is gone, multistate objects number from 0 instead of 1 (p. 10, p. 45).
- Panel cut-outs: no Plus 7 terminal fits the cut-out of a PanelView 300/300 Micro; some fit directly, others need an adapter kit — and these kits are for the Performance line only (p. 19, p. 39). Replacing an AC-powered terminal with a Plus 7 Standard requires an additional 24 V DC power supply (p. 21).
Upgrading from PanelView Plus 6 to Plus 7 is a different case (migrating a FactoryTalk View ME project).
FLEX I/O → FLEX 5000
FLEX 5000 runs on EtherNet/IP only; Remote I/O, ControlNet and DeviceNet adapters all map to the
ControlNet → EtherNet/IP
PLC-5 and 1771 Remote I/O
The
How TDL does it
Survey and fix the path according to the documents for the exact product line in service; convert the program and bench-test it; FAT; where the system can be split into sections, replace them one at a time in shutdown windows set by the plant. Replacing a single CPU or module follows the same process on a smaller scale.
Frequently asked questions
Does upgrading SLC 500 to CompactLogix 5380 mean rewiring?
Not necessarily: the 1492 conversion system keeps the field wiring, the removable terminal block of the 1746 module plugs straight into a conversion module, and the conversion chassis bolts into the existing holes. Check first that
Does RSLogix Project Migrator convert an SLC program completely?
The tool produces a syntactically correct program but does not guarantee the original intent: suspect rungs are flagged PCE; indirect file addressing, SFC, STI/DII interrupts, HSC instructions and Modbus MSG are not converted. Timers move to a 1 ms time base so presets are multiplied by the old time base, and every direct read of .PRE/.ACC must be reviewed by hand.
What do MicroLogix 1100 and 1400 controllers migrate to?
Rockwell names Micro800 as the target, with the program converted by the MicroLogix to Micro800 Converter in Connected Components Workbench. Status files, indirect/indexed addressing for S, I and O files, controller and I/O configuration, interrupts and passwords are not converted; MCR, SQC, SQL and SQO have no equivalent yet.
Does PanelView Plus 7 support serial or DH+ communication?
No. PanelView Plus 7 has Ethernet only; applications on serial links must move to EtherNet/IP, and DH+,
Can the 1771 I/O racks be kept when replacing a PLC-5 with ControlLogix?
Yes, during the transition, through a
Sources
- Rockwell Automation,
MIGRAT-PP004C-EN-E , SLC 500 to CompactLogix 5380 Control System Migration Profile, 08/2020 — p. 2, 6–7 - Rockwell Automation,
1492-SG010B-EN-P , 1746 SLC I/O to Compact 5000 I/O Conversion System Selection Guide, 02/2021 — p. 3–4, 9–11 - Rockwell Automation,
1746-RM003F-EN-E , SLC 500 Hardware Migration Reference Manual, 01/2022 — p. 8, 17–18 - Rockwell Automation,
5069-AP001A-EN-P , SLC to CompactLogix Programming Migration Application Profile, 08/2020 — p. 11–13, 46–47, 50, 61, 73–74 - Rockwell Automation,
MIGRAT-PP015B-EN-E , MicroLogix 1500 Controller to CompactLogix 5370 Controller Migration Profile, 07/2023 — p. 1, 3 - Rockwell Automation,
2080-RM002D-EN-E , MicroLogix Controllers to Micro800 Controllers Migration Guide, 02/2026 — p. 43–48, 52, 130 - Rockwell Automation,
MIGRAT-PP037A-EN-E , CompactLogix1768-L4x Controller to CompactLogix 5380 Controller Migration Profile, 11/2018 — p. 3 - Rockwell Automation,
1769-SG003A , CompactLogix System Selection Guide, 03/2022 — p. 14 - Rockwell Automation,
2711P-AP005F-EN-P , Legacy PanelView Terminals to PanelView Plus 7 Terminals Catalog Number Conversions, 07/2022 — p. 2, 34 - Rockwell Automation,
2711P-AP006F-EN-P , Legacy PanelView to PanelView Plus 7 Migration Guide, 02/2025 — p. 10, 19, 21, 39, 43–48, 55 - Rockwell Automation,
5094-RM001A-EN-P , FLEX I/O to FLEX 5000 I/O Migration Guide, 11/2024 — p. 13–14, 16–20, 27, 29, 47 - Rockwell Automation,
ENET-WP003A-EN-P , Modernizing from ControlNet to EtherNet/IP, 02/2020 — p. 2–5 - Rockwell Automation,
1756-UM514C-EN-P , ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual, 06/2014 — p. 13–15, 101–103 - Rockwell Automation,
5069-TD001P , Compact 5000 I/O and Specialty Modules Specifications, 2026 — p. 26 - Rockwell Automation,
CNET-RM001A , ControlNet to EtherNet/IP Migration — p. 21–27 - Rockwell Automation,
1756-DHRIO product page on rockwellautomation.com (discontinuation date)
This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.