Home › Technical articles

Đọc bằng tiếng Việt

Adding FactoryTalk Optix alongside FactoryTalk View SE: reports, databases and MQTT without replacing SCADA

TDL Industrial Automation · Last updated:

From Rockwell's November 2026 blog and OPTIX-AT001E (09/2026): View SE keeps alarming, historian access and control-room operation; Optix adds PDF reports, ODBC databases, MQTT, OPC UA and web clients; how Optix reads Logix tags, where it runs, Optix panels in PlantPAx 5.40, feature tokens, the deployment port, Remote Access and what TDL checks first.

Many plants run a FactoryTalk View SE system that does its job: operators watch the process, acknowledge alarms and run the plant from the control room. What the plant now asks for is often something else: a PDF report at the end of a shift, process data in a SQL database, values published to an MQTT broker for a MES or cloud project. Replacing a working SCADA system for that is a large step. Rockwell's FactoryTalk Optix can be added next to View SE instead, an approach Rockwell describes in its blog post Best of both worlds: modernize your HMI/SCADA system (10 November 2026). This article follows that post and Rockwell's FactoryTalk Optix Solutions application technique, publication OPTIX-AT001E-EN-P (September 2026), and only says what those two sources say. For the product-by-product comparison, see FactoryTalk View SE vs ME vs Optix.

Adding FactoryTalk Optix next to FactoryTalk View SEThree tiers. At the top, the controllers: ControlLogix, CompactLogix, Micro800, MicroLogix and third-party PLCs through drivers. Two branches go down from the controllers. The left branch goes to FactoryTalk View SE on the operator workstations: centralized alarming, historian access, control-room operations; this part stays as it is. The right branch, through EtherNet/IP, drivers or OPC UA, goes to the FactoryTalk Optix Runtime on a PC, server or panel: OPC UA server and client, data logger, alarms, PDF reports, HTML5 web clients. The documents show no direct link between the two. From Optix, four destinations: databases (embedded SQLite, InfluxDB, ODBC to MySQL and MS SQL Server), MQTT (publish/subscribe client, embedded broker), REST servers, Azure Event Grid. Based on Rockwell's blog of 10 November 2026 and publication OPTIX-AT001E-EN-P (09/2026).Adding FactoryTalk Optix next to FactoryTalk View SEControllersControlLogix · CompactLogix · Micro800 · MicroLogix · third-party PLCs through driversLogix tags, drivers, OPC UAFactoryTalk View SEoperator workstations, unchanged• centralized alarming• historian access• control-room operationsFactoryTalk Optix Runtimeadded: PC, server or panel• OPC UA server and client• data logger, alarms, PDF reports• HTML5 web clientsdata outDatabasesembedded SQLite,InfluxDB, ODBC toMySQL andMS SQL ServerMQTTpublish/subscribeclient, embeddedbrokerREST serversREST connectivityAzure Event GridAzure connectivityBased on Rockwell Automation's blog of 10 November 2026 and Rockwell OPTIX-AT001E-EN-P, 09/2026, pp.26, 28, 91–93 (read 23 November 2026). The documents show no direct link between View SE and Optix. Figure:drawn by TDL.
Figure 1: Adding FactoryTalk Optix next to FactoryTalk View SE. On a phone, swipe sideways to see the whole figure.

1. What stays on FactoryTalk View SE

The application technique describes this split for PlantPAx, Rockwell's distributed control system for process industries. In a typical PlantPAx system, operator workstations running FactoryTalk View SE client software provide centralized alarming, historian access and control-room operations. The controller handles process execution, alarming logic and state management (p. 26).

Both sources state that PlantPAx 5.40 and later supports FactoryTalk Optix target devices; the application technique names an OptixPanel Standard operator panel or an ASEM 6300P Panel PC, as local or field panels where operators need quick access to local data. These panels connect to ControlLogix process controllers over EtherNet/IP. The document states that you do not need to modify PlantPAx controller logic or supervisory architectures to add them (p. 26).

The blog makes the same point for View SE in general. View SE remains the platform for supervisory visualization, alarming, system-wide control and operator interaction, and Optix is added alongside it for reporting, edge and connectivity uses, without changing the core supervisory system or the operators' workflows. If the alarm philosophy or the displays themselves need work, that is a separate project; see SCADA upgrade with ISA-101 and ISA-18.2.

2. What FactoryTalk Optix can add

The blog lists what Optix adds next to View SE: PDF reports, dashboards from real-time or historical data, connections to local or remote databases through ODBC, sharing information with higher-level systems, edge connectivity with protocols such as MQTT, data context through OPC UA information modelling, built-in third-party drivers, and remote support through FactoryTalk Remote Access. The application technique describes Optix as a cloud-enabled HMI and IIoT platform with OPC UA at the core, for both machine-to-machine and machine-to-cloud communication (pp. 7, 12). The features that matter for a plant that keeps View SE are listed in the runtime sizing guide (pp. 91–93) and the connectivity list (p. 28):

What the plant asks for Optix feature named in OPTIX-AT001E Page
Shift or batch report as a file Basic PDF reporting 92
Logging values for trends and reports Data logger, with embedded SQLite included 91–92
Writing data to a plant database ODBC support for MySQL and MS SQL Server; external InfluxDB 28, 92
Sending data to MES or cloud projects MQTT client for publish/subscribe, plus an embedded MQTT broker; REST servers; Azure Event Grid 28, 93
Sharing data with other systems OPC UA server and OPC UA client 28, 92
Screens in a browser HTML5 graphic rendering for web clients, with a secure web server 28, 91
Charts and data views Core framework, graphics, data controls and charts, included in every base package 91

Alarming with alarm history, recipes, an event logger, audit signature and Active Directory authentication are also listed as runtime features (pp. 91–92). Each feature carries a token value, covered in section 5.

The application technique does not list dashboards as a separate feature; a dashboard is built from the graphics, charts and data controls above and viewed on a panel, a workstation or a web client.

3. How Optix gets its data

Optix lists preferred connectivity to ControlLogix, CompactLogix, Micro800 and MicroLogix controllers (p. 28). Tags come from the Logix project: in the Configure Communications wizard you add an RA EtherNet/IP station and import tags either online from the controller or offline from a Studio 5000 Logix Designer project file (.ACD, .L5X or .L5K) (p. 85). Third-party drivers cover Beckhoff TwinCAT, CODESYS, Mitsubishi MELSEC, Modbus, Omron EtherNet/IP and FINS, serial communication, and Siemens S7 TCP and S7 TIA PROFINET (p. 28); details per driver are in FactoryTalk Optix drivers for Siemens, Mitsubishi, Omron and Modbus. Optix can also act as a client to any OPC UA server (p. 28).

One point the plant should know before design: neither the blog nor OPTIX-AT001E describes a direct connection between Optix and FactoryTalk View SE. In the architecture it shows, both the View SE workstations and the Optix devices work from the controllers (p. 26). So the design question is which controllers and which tags Optix reads, not how Optix plugs into View SE. Where a third-party OPC UA client already reads the Logix system, FactoryTalk Linx as an OPC UA server is another path worth reading about.

4. Where the Optix runtime runs

A runtime target device is either a computer with an open operating system (an ASEM 6300 industrial computer, or any PC or virtual machine running Windows or Linux) or a device with Optix embedded, whose operating system is closed (p. 9). The entitlement table lists the Embedded Edge Compute Module (1756-CMEE1Y1), OptixPanel Compact, OptixPanel Standard, ASEM 6300 industrial PCs, OptixEdge Standard, and x64 industrial PCs and servers (pp. 15–16).

For a plant that keeps View SE, two placements follow from the document:

  • A runtime on a PC or server next to the SCADA servers, for reports, database logging, MQTT and web clients.
  • Local or field panels in a PlantPAx 5.40 or later system, as described in section 1. PlantPAx Process Library v5.20 and v5.30 have objects and faceplates for Optix; v4.10 has no Optix content (p. 26).

High availability is possible as a three-node cluster of runtime computers on Ubuntu Linux 22.04.5 LTS, using an extended token package (p. 26). It protects the Optix runtime layer only, not the controller, I/O or network paths, and in version 1.8 the embedded database is not synchronized between nodes; data that must survive a failover belongs in a supported external database (pp. 25–26).

5. Licensing, deployment and remote access

To use Optix you need a myRockwellAutomation account and access to FactoryTalk Hub, where entitlements are allocated to an organization (pp. 7, 12). FactoryTalk Optix Studio comes in two options: Standard, installed locally, needs no activation or entitlement; Pro is a cloud-based editor on a subscription that adds cloud version control, multi-user work and remote deployment (p. 13).

The runtime is licensed by feature tokens. Each feature has a base or extended token value, the application's features add up, and the runtime entitlement must cover the total; the Runtime Sizing Calculator on FactoryTalk Hub recommends the package (pp. 15, 17, 91). Controller connections, web clients, PDF reports, database connections and MQTT publisher or subscriber connections all count (pp. 15, 91–93). An application runs full-featured for 2 hours on the target computer without a runtime entitlement, which is enough for a bench test but not for production (p. 14).

Deployment from Optix Studio goes through the Application Update Service on the target, which needs TCP port 49100 reachable and a username with a password (p. 83). For remote support, FactoryTalk Remote Access uses a VPN managed from the web-based Remote Access Manager, with two-factor authentication, TLS and audit logs, and reaches the device without opening inbound firewall ports (pp. 78, 80). Inside the application, Optix uses role-based access control, local users or Active Directory, and OPC UA with X.509 certificates and TLS (pp. 80–81). Port planning for the rest of the FactoryTalk system: FactoryTalk and Logix firewall ports.

What we check first

This is TDL's practice, not a Rockwell Automation requirement.

  • We write down what the plant wants out of the new layer: which reports, for whom, how often, which database, which MQTT broker and who owns the topics.
  • We record the versions in place: FactoryTalk View SE, controller firmware, PlantPAx and Process Library where PlantPAx is used, and the Optix version planned.
  • We list the controllers and tags Optix will read, and check the added communication load on each controller before anything is connected.
  • We decide where the runtime sits on the network, and which firewall paths it needs: port 49100 for deployment, the database, the MQTT broker, and outbound Remote Access.
  • We size the runtime entitlement with Rockwell's calculator from the feature list, and run the application on a test PC within the 2-hour limit before the plant orders anything.
  • We plan users, roles and OPC UA certificates together with the plant's IT and OT teams.

How TDL approaches it

TDL Industrial Automation is a System Integrator in the Rockwell Automation PartnerNetwork. Through our SCADA and historian work and legacy HMI/SCADA migration service, we help plants decide what stays on FactoryTalk View SE and what a new layer should take, then design, build and test that layer. For remote support we use the approach on our secure remote access page. Where reports and data flows feed a wider data project, Unified Namespace and MQTT explains the next step.

Frequently asked questions

Does adding FactoryTalk Optix mean replacing FactoryTalk View SE?

No. The application technique describes PlantPAx systems where View SE operator workstations keep centralized alarming, historian access and control-room operations, and Optix devices are added as local or field panels without modifying controller logic or supervisory architectures.

Does FactoryTalk Optix connect directly to FactoryTalk View SE?

Neither Rockwell's blog nor OPTIX-AT001E describes such a connection. In the architecture it shows, View SE workstations and Optix devices both work from the controllers, and Optix reads Logix tags through an RA EtherNet/IP station or other systems through OPC UA.

Can FactoryTalk Optix write process data to SQL Server?

Yes. The document lists ODBC support for MySQL and MS SQL Server, plus external InfluxDB and an embedded SQLite database. External database connections are a sized feature, so they count toward the runtime entitlement.

Can FactoryTalk Optix send data to an MQTT broker?

Yes. Optix has an MQTT client for publish and subscribe and an embedded MQTT broker. MQTT publisher and subscriber connections are counted per broker connection in the token sizing.

Which PlantPAx version supports Optix panels?

PlantPAx 5.40 and later supports an OptixPanel Standard operator panel or an ASEM 6300P Panel PC as local or field panels. Process Library v5.20 and v5.30 have Optix objects and faceplates; v4.10 has none.

Sources

  • Rockwell Automation blog, Best of both worlds: modernize your HMI/SCADA system, Sue Burtch, 10/11/2026 — sections "FactoryTalk View SE + FactoryTalk Optix" and "PlantPAx + FactoryTalk Optix"
  • Rockwell Automation, OPTIX-AT001E-EN-P, FactoryTalk Optix Solutions application technique, 09/2026 (supersedes OPTIX-AT001D-EN-P, 01/2026) — pp. 7, 9, 12–17, 24–26, 28, 78, 80–81, 83, 85, 91–93

Read 23 November 2026. This article paraphrases the sources; read the original documents and the FactoryTalk Optix Help for your release before designing a system. The link opens the latest edition in Rockwell's literature library; page numbers refer to the edition cited.

Related services:
SCADA & historian Rockwell Automation (Allen-Bradley)