Siemens, Mitsubishi, Omron, Modbus, BACnet drivers on Ignition, FactoryTalk Optix, AVEVA, N3uron and Kepware

TDL Industrial Automation · Last updated:

From each vendor's current documentation (Ignition 8.1 and 8.3, FactoryTalk Optix 1.8.0, AVEVA Communication Drivers Pack 2026, N3uron V1.22, Kepware): which driver covers Siemens S7, Mitsubishi MELSEC, Omron, Modbus, BACnet and OPC UA, the PLC families listed, what must be set in the PLC such as PUT/GET or SLMP, and how to choose by plant situation.

Ignition, FactoryTalk Optix, the AVEVA Communication Drivers, N3uron and Kepware all document drivers for Siemens, Mitsubishi and Omron controllers, and for Modbus, BACnet and OPC UA. The names differ, and so do the PLC families each driver lists and what must change in the PLC before it answers. The tables below use only each vendor's current documentation; "not found in docs" means we found no driver, not that the product cannot do it.

Four documented paths from a non-Rockwell PLC to the SCADAFour rows of three boxes joined by arrows from left to right. Row 1: a Siemens S7, MELSEC, Omron FINS or EtherNet/IP, Modbus TCP or BACnet/IP device goes through the platform's own driver (Ignition device connection, Optix driver, AVEVA Communication Driver, N3uron client module) to SCADA tags. Row 2: an S7-1200 or S7-1500 with its onboard OPC UA server enabled, read by the platform's OPC UA client with tag browsing. Row 3: PLCs of several brands through Kepware drivers in Kepware Server, read by the SCADA's OPC UA client. Row 4: a Modbus RTU or BACnet MS/TP device through a gateway or router to Modbus TCP or BACnet/IP, then the platform's driver. Based on the Ignition 8.1 and 8.3, FactoryTalk Optix 1.8.0, AVEVA Communication Drivers Pack 2026, N3uron V1.22 and Kepware documentation.Four documented paths from a non-Rockwell PLC to the SCADA1 · Driver in the platformSiemens S7, MELSEC,Omron, Modbus TCP,BACnet/IPPLC or device on EthernetPlatform driverIgnition device connection, Optixdriver, AVEVACommunication Driver, N3uronclient moduleSCADA tagsaddressed or browsed, asthe driver allows2 · OPC UA server on the PLCS7-1200 or S7-1500onboard OPC UA serverenabled (Ignition manual)Platform OPC UA clientbrowses the server's tagsSCADA tagsno address typed foreach tag3 · OPC server in betweenPLCs of several brandseach on its own protocolKepware driver per brandrunning in Kepware ServerSCADA OPC UA clientthe Ignition 8.3 manual hasa page for KEPServerEX4 · Serial device through a gatewayModbus RTU orBACnet MS/TP deviceserial portGateway or routerModbus RTU to Modbus TCP;BACnet MS/TP to BACnet/IPModbus TCP orBACnet/IP driverof the platformBased on Inductive Automation (Ignition 8.1 and 8.3), Rockwell Automation (FactoryTalk Optix 1.8.0), AVEVA(Communication Drivers Pack 2026), N3uron (V1.22) and PTC (Kepware) documentation, read15 November 2026. Figure: drawn by TDL.
Figure 1: Four documented paths from a non-Rockwell PLC to the SCADA. On a phone, swipe sideways to see the whole figure.

1. What was read

The versions read:

  • Ignition: the 8.1 and 8.3 user manuals, which are separate doc sets. The tables give each its own row.
  • FactoryTalk Optix: the FactoryTalk Optix 1.8.0 Help. Its Modbus driver page is labelled 1.7.x.
  • AVEVA: the AVEVA Communication Drivers Pack 2026, whose driver pages also use the name OI Server.
  • N3uron: the N3uron Knowledge Base V1.22.
  • Kepware: the PTC Kepware Drivers help center, whose driver pages print no release number.

2. Siemens, Mitsubishi and Omron controllers

Platform Siemens S7 Mitsubishi MELSEC Omron
Ignition 8.1 Siemens S7-300, S7-400, S7-1200 and S7-1500 drivers, S7 protocol over TCP/IP, no tag browsing Mitsubishi TCP (new in 8.1.28): iQ-R, iQ-F (FX5U), Q, L, F (FX3) Omron NJ driver; Omron FINS driver over TCP or UDP
Ignition 8.3 the same four drivers, absolute addressing only; Siemens Enhanced driver adds browsing, symbolic access and optimized blocks on S7-1200 and S7-1500 Mitsubishi TCP, same series Omron NJ driver; Omron FINS driver over TCP or UDP
FactoryTalk Optix 1.8.0 S7TCP: S7-1200 and S7-1500, S7-300 and S7-400 with offline tag import only; S7 TIA PROFINET: S7-1200 and S7-1500 MELSEC Q driver: "may support" MELSEC-Q and MELSEC-L; MELSEC FX3U driver OMRON EtherNet/IP: "may support" NJ, NX and NU; OMRON Fins: CJ and CP
AVEVA Communication Drivers 2026 SIDirect: S7-300, S7-400, S7-1200, S7-1500, TCP over Ethernet only, Legacy and Symbolic objects MELSEC: Q, QnA, L and iQ-R, Ethernet and serial OMRONFINS: CS1, CJ1, CJ2 and CP1 in CS1 mode; CV, CVM1 and CVM1D in CV mode
N3uron V1.22 Siemens Client: S7 300, 400, 1200, 1500, S7 protocol over TCP/IP not found in docs EtherNet/IP Client: Omron NJ/NX (from 1.22.0); FINS not found in docs
Kepware Siemens TCP/IP Ethernet: S7-200 via CP243, S7-300 and S7-400 via CP or NetLink, S7-1200, S7-1500; Siemens S7 Plus Ethernet: S7-1200 and S7-1500 with symbolic addressing Mitsubishi Ethernet: A, QnA, Q, L, FX3U, iQ-R and iQ-F, TCP/IP and UDP Omron NJ Ethernet: NJ301, NJ501, CJ1W-EIP21, NX series; Omron FINS Ethernet, FINS over UDP/IP

Points the docs add to the table:

  • Siemens symbolic access is a separate driver or object on three platforms: the Siemens Enhanced driver in Ignition 8.3 (not included on a Platform license; no such page in the 8.1 manual), the SIDirect Symbolic object in AVEVA, and Siemens S7 Plus Ethernet in Kepware, which uses S7 Comm Plus.
  • In Optix, S7TCP supports only non-optimized structures and S7 TIA PROFINET only optimized ones.
  • AVEVA's MELSEC page names the MC protocol for Q-series PLCs and SLMP for iQ-R. Its OMRONFINS page says connecting through an EIP Ethernet card is not supported.

3. Modbus, BACnet and OPC UA

Platform Modbus BACnet OPC UA server as the data source
Ignition 8.1 Modbus TCP, Modbus RTU over TCP, Modbus RTU serial BACnet driver, BACnet/IP over UDP OPC UA client connection (OPC Client > OPC Connections)
Ignition 8.3 Modbus TCP, Modbus RTU over TCP, Modbus RTU serial BACnet driver, BACnet/IP over UDP OPC UA Connection (Connections > OPC > Connections)
FactoryTalk Optix 1.8.0 Modbus driver: Modbus TCP and Modbus RTU not found in docs OPC UA client object that imports nodes from an OPC UA server
AVEVA Communication Drivers 2026 MBTCP: Modbus TCP/IP; serial Modbus controllers through a Modbus Bridge BACLITE: BACnet/IP over UDP/IP Gateway Communication Driver, OPC UA data source
N3uron V1.22 Modbus Client: Modbus TCP, Modbus RTU and RTU over TCP BACnet Client, BACnet/IP over UDP OPC UA Client
Kepware Modbus TCP/IP Ethernet; Modbus RTU Serial BACnet/IP OPC UA Client, described as a tunnel between OPC servers

Ignition and N3uron both say that BACnet devices on other media, such as MS/TP, are reached through a gateway or router. The Ignition 8.3 manual has its own page for connecting to KEPServerEX over OPC UA.

4. What has to be set in the PLC

Only what the driver pages say about the PLC side; no row means we found nothing.

PLC family Driver Protocol What to set on the PLC, per the docs
S7-1200, S7-1500 Ignition Siemens S7-1200 and S7-1500 drivers S7 over TCP/IP Optimized block access off; Full access (no protection) and PUT/GET permitted; only global DBs; the change may need the hardware configuration recompiled and downloaded
S7-1200, S7-1500 Ignition 8.3 Siemens Enhanced, Symbolic S7, symbolic PUT/GET and full access not needed: read access to read and browse, write access to write
S7-1200, S7-1500 AVEVA SIDirect Legacy object TCP over Ethernet PUT/GET enabled and optimized block access disabled in TIA Portal; the Symbolic object needs no pre-configuration
S7-1200, S7-1500 N3uron Siemens Client S7 over TCP/IP Optimized block access off; access level full; PUT/GET allowed
S7-1200, S7-1500 Optix S7TCP, online tag import not named Full access; PUT/GET from remote partner; "Only allow secure PG/PC and HMI communication" disabled if applicable
MELSEC iQ-R, iQ-F, Q, L Ignition Mitsubishi TCP MELSEC, SLMP connection over TCP GX Works3: online change Enable All (SLMP), data code Binary, an SLMP connection module with TCP; write to the PLC and power cycle
MELSEC F with FX3U-ENET Ignition Mitsubishi TCP MC procedure over TCP FX Configurator-EN: binary code, Always wait for OPEN, connection with TCP and Procedure Exist (MC)
Omron NJ, NX Optix OMRON EtherNet/IP EtherNet/IP Network Publish set to Publish only in Sysmac Studio, then tags exported to a TXT file
Omron FINS devices Ignition Omron FINS FINS over TCP or UDP Destination node is typically the last octet of the IP address, set with the dials on the device

5. Choosing by plant situation

A SCADA is already running

We start from the platform the plant already has and look for the PLC in its list. At SEHC, Modbus and BACnet equipment reached the AVEVA System Platform SCADA through KEPServerEX, as our air compressor and Admin Building pages describe.

Several PLC brands on one site

One pattern is a platform whose own list covers every brand on site; the tables show where the lists differ, for example no Mitsubishi module in the N3uron docs. The other is an OPC server in between: Kepware's driver pages describe connecting devices to OPC client applications such as HMI, SCADA and historians, and every platform above documents an OPC UA client.

The PLC has an OPC UA server

Both Ignition manuals note that some S7-1200 and S7-1500 devices have an onboard OPC UA server that can be enabled. Ignition then connects as an OPC UA client and browses the tags, instead of addressing each tag by hand. On the other platforms this path would use the OPC UA client in the table; the pages we read for them do not mention the S7 server.

Serial devices and gateways

Ignition's Modbus driver connects to devices directly over Ethernet or through a gateway device. AVEVA's MBTCP reaches serial Modbus controllers through a Modbus Bridge. At Yakult Vietnam the serial port of the existing Mitsubishi FX-series PLC is connected through a Modbus RTU to Modbus TCP gateway to a FactoryTalk Optix SCADA, and the PLC stays in control. More on register maps and gateways: Modbus RTU and TCP for SCADA and Bringing AHUs and air compressors into an FMCS SCADA.

When the PLC is replaced instead

At SEHC VD5 the Siemens PLCs, HMIs and serial converters had stopped working and were replaced with a CompactLogix 5370, then brought back into the FMCS SCADA. On the Vietsovpetro LP compressor a Siemens S5 control system was replaced with ControlLogix. The S5 does not appear in any of the Siemens driver lists above.

What we check first

This is TDL's practice, not a requirement of Inductive Automation, Rockwell Automation, AVEVA, N3uron or PTC.

  • We back up the PLC program before any change, as on the Yakult project.
  • We note the exact CPU, its firmware and the port the SCADA will use: built-in Ethernet, a communication module or a serial port.
  • We trace the network path from the SCADA server to the PLC, switch by switch.
  • We ask the plant whether a PLC-side change is allowed. Changing PUT/GET, optimized block access or the SLMP settings can mean a download to the PLC, and the Mitsubishi page asks for a power cycle.
  • We estimate the polling load: tags, rates and connections. The Ignition Omron NJ driver, for example, uses one CIP connection per concurrent request, two by default.
  • We agree on tag names and where the tag list comes from: a TIA Portal project, a GX Works CSV file or a Sysmac Studio export.

How TDL approaches it

TDL Industrial Automation is a System Integrator in the Rockwell Automation PartnerNetwork, a System Integrator member of the AVEVA Partner Ecosystem, an Ignition Certified Integrator and a Certified Integrator of N3uron. Our project pages linked above cover a Mitsubishi PLC kept in service at Yakult Vietnam, Modbus and BACnet equipment at SEHC, and two sites where Siemens controllers were replaced. More on these services: Connecting existing PLCs and equipment to SCADA and SCADA and historian.

Platform by platform, in more depth:

Frequently asked questions

Which platforms read an S7-1200 or S7-1500 by tag name?

Ignition 8.3 with the Siemens Enhanced driver, AVEVA with the SIDirect Symbolic object, and Kepware with the Siemens S7 Plus Ethernet driver. In Optix, the S7 TIA PROFINET driver is the one that supports optimized structures; its tags are created with the TagImporter.

Does the Siemens PLC need PUT/GET turned on?

For the Ignition Siemens drivers, the AVEVA SIDirect Legacy object, the N3uron Siemens Client and online tag import in Optix S7TCP, the docs say yes, together with full access. The SIDirect Symbolic object and Ignition's Siemens Enhanced driver in Symbolic mode do not need it. The change may need a download to the PLC.

Does "not found in docs" mean the platform cannot connect?

No. It means we found no driver for it in the documentation we read for that version. A newer release, another module or an OPC server in between may still cover it.

Can a Mitsubishi FX PLC be read without a Mitsubishi driver?

Yes. At Yakult Vietnam the serial port of the existing FX-series PLC reaches FactoryTalk Optix through a Modbus RTU to Modbus TCP gateway. Ignition, Optix and Kepware also list FX drivers: Ignition and Kepware through the FX3U-ENET module.

How do Omron NJ controllers connect?

Over EtherNet/IP. Ignition has the Omron NJ driver, Optix the OMRON EtherNet/IP driver, Kepware the Omron NJ Ethernet driver and N3uron the EtherNet/IP Client from 1.22.0. AVEVA's OMRONFINS page lists an NJ501 among its CS1-mode test hardware and does not support connecting through an EIP Ethernet card.

Sources

Read 15 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.