AVEVA ABCIP driver (OI.ABCIP, formerly DASABCIP): connecting InTouch and System Platform to ControlLogix

TDL Industrial Automation · Last updated:

From AVEVA's Communication Drivers Pack 2026 docs: DAServer, OI Server and Communication Driver, supported Allen-Bradley families, the PORT_CIP, ENB_CLX, BACKPLANE_CLX, LOGIX5000_CLX tree, device groups, InTouch and System Platform item addressing, $SYS$ items and common connection faults.

AVEVA InTouch HMI and System Platform read Allen-Bradley controllers through the ABCIP Communication Driver, which older systems know as the ABCIP OI Server (OI.ABCIP) and, before that, as the DASABCIP DAServer. It is a Windows program that talks CIP to the controllers without RSLinx and serves InTouch, Application Server and OPC clients. This article follows AVEVA's Communication Drivers Pack 2026 documentation. Where these products sit in AVEVA's range: What is AVEVA.

1. One driver, three names

AVEVA's 2026 documentation explains the naming: the I/O server was first called a DAServer (Data Access Server), later an OI Server, and is now a Communication Driver. The OI Server added multiple instances; AVEVA states there is no significant functional difference between an OI Server and a Communication Driver. Older AVEVA examples call the ABCIP DAServer DASABCIP.

The driver is configured in the OI Server Manager, also called Communication Drivers Core, inside the Operations Control Management Console (OCMC), formerly the System Management Console (SMC). With ABCIP installed, the console shows the default instance as OI.ABCIP.1. The pack is not supported on 32-bit Windows; for compatibility the documentation points to AVEVA's Technology Matrix.

2. Controllers and networks

Family Reached through, as documented
ControlLogix 1756-ENET, ENBT, EN2T or EWEB in the chassis, or ControlNet through a 1756-CNB or CN2 bridge
GuardLogix (1756-L6xS) 1756-ENBT or EWEB, or ControlNet through a 1756-CNB or CN2
CompactLogix built-in EtherNet/IP port (5069, 1769, 1768), or a 1761-NET-ENI (1769, 1768)
FlexLogix 1788-ENBT or 1788-CNC daughter card
MicroLogix built-in port on the 1100 and 1400; 1761-NET-ENI or DH485 routes for the 1000, 1200 and 1500
PLC-5, SLC 500 DH+ through a 1756-DHRIO or ControlNet; an SLC 500 also through its 5/05 Ethernet port or a 1761-NET-ENI

The networks are Ethernet, ControlNet, DH+, DH485 and DeviceNet; DeviceNet data comes only through the controller's own scanner. A ControlLogix rack can route to a second ENB on another subnet, one hop only, and a Device-Level Ring is joined through a 1783-ETAP.

The highest firmware in AVEVA's table of tested Logix firmware is v28, on the 1756-L73, 1756-L83E and 1769-L36ERM; AVEVA says it retests the driver after major Rockwell firmware releases.

3. The hierarchy: port, ENB module, backplane, processor

The OI Server Manager tree copies the physical path to each controller: it starts with PORT_CIP, and every branch ends in a processor node.

ABCIP driver: from InTouch to the ControlLogix slotAt the top, InTouch HMI uses an Access Name made of node, application and topic, and System Platform uses an OPCClient object or PCS; InTouch reaches the ABCIP driver over SuiteLink or DDE, System Platform over OPC or PCS. In the middle, the OI Server Manager tree: PORT_CIP, ENB_CLX with the IP address of a 1756-EN2T as Host Name, BACKPLANE_CLX, LOGIX5000_CLX with Slot Number 0, then a device group, the topic with its Update Interval. At the bottom, EtherNet/IP to the EN2T module in an example ControlLogix chassis with the controller in slot 0. Based on the AVEVA Communication Drivers Pack 2026 documentation.ABCIP driver: from InTouch to the ControlLogix slotInTouch HMIAccess Namenode, application, topic = device groupSystem PlatformOPCClient object or PCSPCS item: scope:topic.itemABCIP driver (OI.ABCIP): the OI Server Manager treePORT_CIPthe PC's Ethernet port for CIP, one per driverENB_CLXHost Name: IP address of the 1756-EN2T, ConnectionTimeout 2,000 msBACKPLANE_CLXthe chassis backplaneLOGIX5000_CLXSlot Number 0, Reply Timeout 15 s, Max CIP Connections 4Device groupset on the processor node; the topic: name up to 32characters, Update Interval (ms)SuiteLink or DDEOPC or PCSEtherNet/IPControlLogix chassis (example)Slot 0Logix controllerSlot 1I/O moduleSlot 21756-EN2TSlot 3I/O moduleBackplane: from the EN2T to the controller in slot 0Based on AVEVA, Communication Drivers Pack 2026 documentation: ENB_CLX, BACKPLANE_CLX,LOGIX5000_CLX, Device group definitions, Access data using DDE (read 14 November 2026). Timeouts, slot andconnection count are the defaults; the slot layout is an example. Figure: drawn by TDL.
Figure 1: ABCIP driver: from InTouch to the ControlLogix slot. On a phone, swipe sideways to see the whole figure.
Object Represents Settings (range, default)
PORT_CIP the PC's Ethernet port for CIP; one per driver Maximum Queued Msgs 1–40, default 4, only for MicroLogix and SLC 500 without CIP connections
ENB_CLX 1756-ENET, ENBT, EN2T or EWEB module Host Name: IP address or host name, never blank; Connection Timeout 10–10,000 ms, default 2,000
BACKPLANE_CLX the chassis backplane; one per ENB_CLX none
LOGIX5000_CLX the controller Slot Number 0–16, default 0; Reply Timeout 1–300 s, default 15; Max CIP Connections 1–31, default 4

A CompactLogix with a built-in port uses ENB_CPLX, with the controller's own IP address, then BACKPLANE_CPLX and LOGIX_CPLX. Older networks hang off the backplane: CNB_CLX and PORT_CN (channel A or B, ControlNet address 1–99), or DHRIO_CLX and PORT_DHP (channel, node address 0–77 octal, link ID).

On the processor node:

  • Max CIP Connections: queued messages are spread over this many connections. Each one uses controller resources; AVEVA's example says that at 31 connections data updates became extremely sluggish.
  • Optimization: No optimization reads by tag name, with the fastest startup and slowest reads. Optimize for read, the default, builds message blocks in the controller, so startup is longest and reads fastest. Optimize for startup time works only up to firmware 20; from firmware 21 the driver switches to Optimize for read and logs a warning.
  • Optimize User Defined Data Types (off by default): reads a whole structure of 488 bytes or less in one packet, and is not supported on UDTs with a member whose External Access is None.
  • Use Persisted Tags (on by default): keeps the tag database in a file and reuses it while the controller's tag database version is unchanged.

4. Device groups: the topics clients use

Device groups are created on the processor node. For DDE and SuiteLink clients a device group is the topic, and each controller needs at least one; for OPC clients it is the optional access path.

  • Name: unique, up to 32 characters.
  • Update Interval: how often, in milliseconds, the driver polls the group. AVEVA advises against polling everything near zero and suggests several groups by how fast values change. The default group runs at 1,000 ms.
  • Support Unsolicited Messages: off by default; it needs message instructions in the controller, connected ones for Logix. With an Update Interval of 0 the topic is read once and then only by unsolicited messages.

Two global parameters, which apply to all instances in the server group, matter here: Slow Poll Interval (10,000 ms) while a device is unreachable, and Poke Mode, whose ABCIP default, Optimization Mode, writes only the last value poked to an item.

5. How InTouch and System Platform address the items

Logix items use the controller's tag names: Tag.Member, Tag[3], Program:MainProgram.Tag, module tags such as Local:6:O.Data.31, a bit as Tag.5, and a block of a one-dimensional array as Tag[0],L10. Tag names can be up to 40 characters; structures nest up to 20 levels.

  • InTouch: each I/O tag uses an Access Name with a node name (only when the driver runs on another computer), an application name taken from the driver instance, and a topic, which is the device group. AVEVA does not recommend Advise all items because it affects performance.
  • OPC clients: the instance's ProgID, for example OI.ABCIP_0001.1, the device group as access path, and an item ID made of the node names of the OI Server Manager tree, separated by periods, then the item.
  • System Platform: AVEVA's Application Server 2026 guide says the OPCClient object should replace legacy DI objects such as ABCIP; since System Platform 2023 its HierarchyPath attribute and a default scan group let a DINetwork object be replaced without reconfiguring existing I/O references. Through PCS, Application Server addresses scope:topic.item, with the default scope OI$<instance>$<computer>.

The documented client protocols are OPC, SuiteLink, DDE/FastDDE and PCS. In the same pack, OPC UA sources go through the Gateway Communication Driver and MQTT through the MQTT Communication Driver. For the firewall, AVEVA lists TCP 5413 for SuiteLink and TCP 135 plus 49152–65535 for OPC; the same page lists further ports for PCS.

6. Diagnostics: system items, the Diagnostics node, the Logger

System items start with $SYS$ and are read like other items:

System item What it shows
$SYS$Status 1 while the connection to the device is intact, 0 on error; SuiteLink reads it at the processor node, and for OPC the root level is always good
$SYS$ErrorCode, $SYS$ErrorText 0 connected, above 0 connecting or initializing, below 0 an error
$SYS$ErrorCount items in the device group without good quality
$SYS$Licensed 0 means no valid licence: items stop updating and turn Bad
$SYS$UpdateTagInfo, $SYS$BrowseTags write true to reload the tag database; write 1 to allow online OPC browsing, off by default

An active driver has a Diagnostics node under Configuration in the OCMC; its Device Groups view shows each group's update interval, actual update time and items with errors. Errors go to the Logger; the driver adds two codes, -10001 PLC not connected and -10002 PLC times out. To see whether a device answers, AVEVA suggests the DASSend and DASReceive log flags, and warns against leaving extra flags on in production.

7. Connection problems the documentation lists

Logger message or symptom Cause given by AVEVA AVEVA's fix
Connection … refused the target is not a ControlLogix Ethernet module check the device at that address
Message … timed out no reply within the Reply Timeout: the device is off line check its network connection
Failed to initialize Listen Socket another program, such as RSLinx, uses the same CIP port, so unsolicited messages cannot arrive close it and restart the driver
Failed to add block … External Access=None the tag does not exist, or a UDT member is set to None set the member to Read Only or Read/Write, or create the tag
ExtSTS=0113 the controller's Connection Manager cannot support more connections look up codes in AVEVA's Logix5000 error table

Also documented:

  • Tags in a routine imported into a running controller are rejected until 1 is written to $SYS$UpdateTagInfo; AVEVA does not support online routine changes. After a full download, the driver pauses, reloads the tag database and resumes.
  • A remote OPC client that shows no updates or logs COM error 0x80040202 points to DCOM identity or guest-only access settings, or to a firewall blocking DCOM call-backs on port 135.
  • Without a licence the driver runs in demo mode for 120 minutes, then stops updating and sets items Bad.
  • The 2026 release notes list a known issue: upgrading to System Platform 2026 from 2023 R2 SP1 or its patches resets a driver's configuration set to the default, and the fix is Use Another Configuration Set.

What TDL checks first

These are our own working habits on an existing InTouch or System Platform system, not AVEVA requirements:

  • We note the driver version, the instance names and the application and topic of every Access Name that points to ABCIP.
  • We redraw the tree against the real network: ENB module addresses, processor slots and every ControlNet or DH+ bridge.
  • We compare controller firmware with AVEVA's tested firmware table and look for Optimize for startup time on controllers at firmware 21 or later.
  • We read $SYS$Status, $SYS$ErrorText and $SYS$ErrorCount per device group before anyone touches the network.
  • We add up the CIP connections the driver opens next to the HMIs, other SCADA and messages using the same controller.
  • We archive the configuration set before an upgrade.

How TDL approaches it

TDL Industrial Automation is a System Integrator member of the AVEVA Partner Ecosystem. Our AVEVA service page describes connecting the AVEVA software we build and maintain to Allen-Bradley and other control systems; see also connecting existing PLCs to SCADA. Faults above the driver: InTouch HMI troubleshooting and System Platform troubleshooting. The same connection on Ignition: Ignition Allen-Bradley Logix driver.

Frequently asked questions

Is OI.ABCIP the same driver as DASABCIP?

It is the ABCIP driver under a later name. AVEVA's 2026 documentation says the I/O server was first called a DAServer, then an OI Server, which added multiple instances, and is now a Communication Driver.

Does the ABCIP driver need RSLinx?

No, AVEVA states that it does not. If RSLinx uses the same CIP port on that computer, the driver cannot receive unsolicited messages.

What goes into an InTouch Access Name for ABCIP?

The node name if the driver runs on another computer, the application name of the driver instance, and a topic equal to a device group configured on the controller node.

Which item shows that the driver has lost a ControlLogix?

$SYS$Status on the processor node: 1 while the connection is intact and 0 on error. $SYS$ErrorText gives the detailed state.

Why did all ABCIP items turn Bad two hours after start-up?

That matches demo mode: without a licence the driver runs for 120 minutes, then stops updating and sets items Bad. $SYS$Licensed then reads 0.

Sources

Read 14 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system.