Ignition 8.3 historian types: SQL Historian, Core Historian, Historian Splitter and the read-only providers

TDL Industrial Automation · Last updated:

From the Ignition 8.3 user manual and Inductive Automation's blog of 21 October 2026: the history provider types (Core Historian on QuestDB, Internal Historian (Legacy) on SQLite, SQL Historian, Historian Splitter, Remote Historian, DB Table, OPC HDA, CSV, Simulator), where each keeps its data, which read or write, how to choose by situation and what changes when moving from 8.1 to 8.3.

In Ignition, tag history is stored and read through history providers, which the Ignition 8.3 user manual describes as "embedded options, external databases, and other storage types". Version 8.3 changed this part of the platform: it introduced the Core Historian, and the Tag Historian licence item was replaced by Historian Core and SQL Historian. On 21 October 2026, Inductive Automation published a blog post that walks through eight historian types. This article takes that list as its starting point and checks every type against the Ignition 8.3 user manual; where the blog and the manual differ in detail, the manual is used. What a process historian does in general: What is a process historian. Ignition itself: What is Ignition.

Ignition 8.3: where each historian type keeps its dataSix groups from top to bottom, sorted by where the data lives. Inside the Gateway: Core Historian is an embedded QuestDB database written to disk through a write-ahead log, without Store and Forward; Internal Historian (Legacy) is a local SQLite database. SQL database through a database connection: SQL Historian writes and reads, through Store and Forward; DB Table Historian only reads existing or custom-managed tables. Another Gateway over the Gateway Network: Remote Historian reads only, or reads and writes when Storage Allowed is on. Two providers at once: Historian Splitter writes to a first and a second connection, and queries go to the first unless a limit is set or it is unavailable. External sources, read-only: OPC HDA Historian reads an OPC HDA server and runs only on Windows; CSV Historian reads a CSV file. Nothing stored: Simulator Historian generates data on request for testing, training and demos. Based on the Ignition 8.3 user manual, History Providers page.Ignition 8.3: where each historian type keeps its dataInside the Gatewayembedded databaseCore Historian · QuestDB, written to disk through awrite-ahead log, no Store and ForwardInternal Historian (Legacy) · local SQLiteSQL databasethrough a database connectionSQL Historian · writes and reads, through Store and ForwardDB Table Historian · reads existing or custom-managedtables onlyAnother Gatewayover the Gateway NetworkRemote Historian · read only, or read and write whenStorage Allowed is onTwo providers at onceHistorian Splitterwrites to a first and a second connectionqueries go to the first, unless a limit is set or it is unavailableExternal sourcesread only, nothing storedOPC HDA Historian · OPC HDA server, Windows onlyCSV Historian · CSV fileNothing storedgenerated on requestSimulator Historian · testing, training, demosBased on the Ignition 8.3 user manual, Historian and History Providers pages (read 23 November 2026). Figure:drawn by TDL.
Figure 1: Ignition 8.3: where each historian type keeps its data. On a phone, swipe sideways to see the whole figure.

1. The types at a glance

The manual's History Providers page lists nine provider types: the eight in the blog plus the Internal Historian (Legacy), the SQLite-based historian that 8.3 keeps available.

Type Reads or writes Where the data lives What the 8.3 manual adds
Core Historian read and write embedded QuestDB time-series database, written to disk through a write-ahead log partitioning, deduplication, archiving, native aggregation; no Store and Forward (see section 2)
Internal Historian (Legacy) read and write local SQLite database for Edge devices, standalone or small systems; pruning by time or point limit; remote sync to another Gateway
SQL Historian read and write external SQL database such as MySQL, SQL Server or PostgreSQL partitioning, pruning, stale data detection, pre-processed partitions; needs the SQL Historian module as well as Historian Core
Historian Splitter writes to two the two providers it is configured with for redundancy, system migrations or archiving in several places
Remote Historian query only, or read and write a history provider on another Gateway, over the Gateway Network Storage Allowed decides whether it may store
DB Table Historian read only external or custom-managed SQL tables for third-party or legacy datasets
OPC HDA Historian read only an OPC HDA server Windows only; needs the OPC COM module
CSV Historian read only a CSV file no real-time tag history storage
Simulator Historian stores nothing generated on each request for testing, training and demos

Historians are created on the Gateway under Services > Historians > Historians: Create Historian, choose the type, name it and fill in its settings.

2. Historians that store data: Core, Internal (Legacy) and SQL

Core Historian. The manual calls it a historian "powered by QuestDB" that supports partitioning, deduplication, archiving and native aggregation. The blog describes it as an out-of-the-box historian that needs no configuration; the manual still lists a few settings worth deciding on purpose:

  • Partition Interval: week, month or year.
  • Mode: None keeps history indefinitely, Prune (the default) deletes partitions older than the Maintenance Age, Archive moves them to an Archive Folder. The Maintenance Age must be a whole multiple of the partition interval.
  • Data Deduplication: an incoming record with a matching key updates the existing entry instead of adding a new one.
  • Memory: by default the Core Historian takes 10% of total system memory when enabled.

The Core Historian writes straight to disk through a write-ahead log and, per the manual, does not use Store and Forward; it bypasses the buffering and retry used by the other historian types. The 8.1 to 8.3 upgrade guide words this differently: the Core Historian uses Store and Forward only if there are pending writes to the database. Where buffering during an outage matters, check the behaviour on a test Gateway.

Internal Historian (Legacy). A lightweight embedded historian on a local SQLite database, which the manual suggests for Edge devices, standalone systems or small systems. It prunes by a time limit or a point limit and can sync its history to a remote Gateway. The manual notes that SQLite-based historians do not record scan class execution data.

Only these two store tag metadata, and only for tags with Include Metadata set in the Tag Editor. On the Core Historian, metadata is needed for annotations, aggregates and the historian scripting functions.

SQL Historian. Stores tag history in an external SQL database through a database connection named in its Data Source setting. It supports partitioning, pruning by deleting old partitions, stale data detection (it tracks tag group executions so that a flat line caused by the system not running is not mistaken for an unchanging value) and pre-processed partitions, which aggregate data into smaller partition tables. The Internal Historian (Legacy) and the SQL providers always route data through Store and Forward, which queues records while the database cannot be reached. The same buffering idea in a separate historian product: Canary Historian architecture.

3. Moving and sharing history: Splitter and Remote

Historian Splitter. It writes the same tag history to a First Connection and a Second Connection. Queries go to the first connection unless Limit First Connection Query is set (with a length and units) or the first connection is unavailable. The manual names three uses: redundancy, system migrations and archiving data in more than one place. The blog's example is local Core storage with central SQL storage. This is history redundancy at provider level; Gateway redundancy is a separate topic: Ignition redundancy.

Remote Historian. It connects to another Gateway over the Gateway Network and uses a history provider there, named by its Gateway and Provider settings. With Storage Allowed off it only queries; with it on, it also stores, through a store-and-forward pipeline to the remote Gateway. The blog's use case is several Gateways whose history can be queried from one central place.

The blog also says that Ignition 2027 will add zero-data-loss historian redundancy to several historians, including the SQL and Core Historians. That was an announcement on 21 October 2026, not a feature of 8.3; it should not be part of a design until the release documents it.

4. Read-only providers: DB Table, OPC HDA, CSV and Simulator

  • DB Table Historian exposes columns of tables in a database connection as tags, so trends and history queries can read them. A path names the table, the value column and, optionally, the timestamp column (t_stamp if not given) plus a key column and an integer key value to filter rows. A typical use is a table filled by an SQL Bridge transaction group, which Tag History bindings generally cannot query otherwise.
  • OPC HDA Historian reads history from OPC HDA servers. It is supported only on Windows, needs the OPC COM module and cannot store or forward tag history.
  • CSV Historian reads a CSV file given by a File Path setting: a timestamp column followed by value columns, with tag names in the header row.
  • Simulator Historian stores nothing. It builds a result from the tag path in the form function_period_amplitude_resolution (Ramp, Sine, Cos, Square or Realistic), and the same parameters and time range always return the same data, which suits screen and chart testing.

5. Choosing by situation

The manual does not give a selection guide, so the list below is our reading of the documented features:

  • One machine or a small site with no SQL server: the Core Historian, which needs no external database. The Internal Historian (Legacy) remains for Edge devices and existing small systems.
  • A plant that already runs an SQL server and wants history in its own tables: the SQL Historian, with Store and Forward buffering while the database is down.
  • Several Gateways and one central view: Remote Historian connections to the central Gateway's provider, or a Splitter writing local and central copies.
  • Moving from an old historian to a new one: a Historian Splitter writing to both while the new one fills up.
  • Old data in SQL tables, an OPC HDA server or CSV exports: DB Table, OPC HDA or CSV Historian, read-only, so the old data can be trended next to the new.
  • Building screens before the plant is connected: the Simulator Historian.

6. When a Gateway moves from 8.1 to 8.3

The 8.1 to 8.3 upgrade guide lists the historian changes: the Tag Historian licence item is replaced by Historian Core and SQL Historian; the SQLite-based Internal Historian (Legacy) is still available; historical paths now use sys for the Gateway and prov for the tag provider, while drv paths from 8.1 still work and the SQL Historian still needs drv; the Store and Forward Primary Store Maintenance Value is set to zero (unlimited) and 8.1 quarantine exports cannot be imported. 8.3 Gateways cannot store data to 8.1 Gateways over the Gateway Network, which matters for remote history providers. After the upgrade, the guide asks to check that historical data is still being stored. The full upgrade: Upgrading Ignition 8.1 to 8.3.

What we check first

This is TDL's practice, not an Inductive Automation requirement.

  • Which history providers the Gateway already has, and which tags store history to each.
  • Whether the plant has an SQL server, who runs and backs it up, and whether IT wants history in SQL tables.
  • How long history must be kept, and whether old partitions should be pruned or archived to another disk.
  • How many Gateways there are, whether they share a Gateway Network, and where the central history should live.
  • Old history that must stay readable: SQL tables, an OPC HDA server, CSV exports.
  • Scripts and reports that query history with drv paths or 8.1 functions, before any 8.3 upgrade.

How TDL approaches it

TDL Industrial Automation is an Ignition Certified Integrator. We choose the historian from where the data has to live and who has to read it, test retention and queries on a test Gateway, and only then point production tags at it. More: Ignition SCADA integrator in Vietnam and SCADA and historian.

Frequently asked questions

What is the Core Historian in Ignition 8.3?

It is the historian introduced in 8.3: an embedded QuestDB time-series database that writes to disk through a write-ahead log and supports partitioning, deduplication, archiving and native aggregation. It needs no external database. The Historian pages say it does not use Store and Forward; the 8.1 to 8.3 upgrade guide says it uses it only when writes to the database are pending.

Does Ignition still support logging history to an SQL database?

Yes. The SQL Historian stores tag history in an external database such as MySQL, SQL Server or PostgreSQL, routes data through Store and Forward and needs the SQL Historian module in addition to Historian Core.

What is the Historian Splitter for?

It writes tag history to two providers at the same time. The manual names redundancy, system migrations and archiving in several places; queries go to the first provider unless a limit is set or it is unavailable.

Can Ignition show history from another historian or from old tables?

Yes, read-only. The DB Table Historian reads SQL tables, the OPC HDA Historian reads OPC HDA servers (Windows only) and the CSV Historian reads CSV files.

What happens to the 8.1 internal historian after upgrading to 8.3?

The upgrade guide says the SQLite-based Internal Historian (Legacy) is still available in 8.3, alongside the new Core Historian.

Sources

Read 23 November 2026. Apart from two short quoted phrases from the user manual, this article paraphrases the sources; read the original documents before designing or working on a system.