FLEX I/O 4-Channel Analog Output Module 1794-OE4

Rockwell lifecycle statusEnd of Life – Rockwell announced discontinuation 28/02/2027 (read on 25 September 2026)
Replacement5094-OF8 — named by Rockwell Automation

The Engineering Replacement is 5094-OF8 (8 channels; 5094-RM001A p.18). When migrating, review the current loop load (5094-OF8 max 500 Ω, 5094-TD001M p.39), the INT to REAL data type change, and add the 5094-STB.

Key data

Channels4 AO, non-isolated
Output range4…20 mA; 0…20 mA; ±10 V; 0…10 V
Resolution12 bit + sign
Accuracy0.425% FS (current); 0.133% FS (voltage) @ 25 °C
Current load15…750 Ω
Isolation50 V continuous I/O–system; no channel-to-channel isolation
Operating temperature-20…+55 °C
Replacement categoryEngineering Replacement
Replacement5094-OF8 (5094-RM001A p.18)
Load note5094-OF8 maximum current load 500 Ω (5094-TD001M p.39)
Channel data after migrationFLEX I/O INT data → FLEX 5000 REAL data (default 0…100%); scaling in the program must be reviewed (5094-RM001A p.29)
Shield groundingFLEX 5000 requires the 5094-STB bar (5094-RM001A p.26)
FLEX 5000 requirementsEtherNet/IP only; ControlLogix 5580 / CompactLogix 5380 / 5480 controller; Studio 5000 Logix Designer v31 or later (5094-RM001A p.5; 14; 27)

Lifecycle status changes over time: confirm the current status on the Rockwell product page or in the Product Compatibility and Download Center before ordering.

Related services: Lifecycle review and spare parts Rockwell Automation upgrades

Other catalog numbers in this family: FLEX I/O (1794)

1794-AENT 1794-ACN15 1794-ACNR15 1794-IE8H 1794-OE8H