Home › End-of-life lookup › FLEX I/O (1794)

FLEX I/O 8-Channel HART Analog Input Module 1794-IE8H (discontinued)

Rockwell lifecycle statusEnd of Life – Rockwell announced discontinuation 31/03/2026 (read on 25 September 2026)
Replacement1794-IF8IH — named by Rockwell Automation

The lifecycle page names 1794-IF8IH as the Engineering Replacement; 5094-RM001A (p.18) proposes 5094-IF8IH on FLEX 5000.

Key data

Channels8 AI HART, no channel-to-channel isolation
Input range0…20 mA / 4…20 mA
Resolution16 bit
Accuracy0.1% FS @ 20 °C
NetworkControlNet or EtherNet/IP only; 1 HART device per channel
Operating temperature-20…+55 °C
Replacement categoryEngineering Replacement
Replacement1794-IF8IH
Migration path5094-IF8IH (5094-RM001A p.18)
Channel data after migrationFLEX I/O INT data → FLEX 5000 REAL data (default 0…100%); scaling in the program must be reviewed (5094-RM001A p.29)
HART softwareLogix Designer v32.02 or later with CompactLogix 5380 / ControlLogix 5580 (5094-RM001A p.28)
FLEX 5000 requirementsEtherNet/IP only; ControlLogix 5580 / CompactLogix 5380 / 5480 controller; Studio 5000 Logix Designer v31 or later (5094-RM001A p.5; 14; 27)

Lifecycle status changes over time: confirm the current status on the Rockwell product page or in the Product Compatibility and Download Center before ordering.

Related services: Lifecycle review and spare parts Rockwell Automation upgrades

Other catalog numbers in this family: FLEX I/O (1794)

1794-AENT 1794-ACN15 1794-ACNR15 1794-OE4 1794-OE8H