Home › Technical articles

Tiếng Việt

PowerFlex 755T/755TS fault codes (TotalFORCE): how codes are numbered, common faults and safe reset

TDL Industrial Automation · Last updated:

TotalFORCE drive codes live in the 750-RD102 workbook, and the prefix shows which port raised them (10xxx inverter, 12xxx power layer, 13xxx/14xxx converter, nnxxx options). 19 common codes, what to check and how to reset safely.

On the PowerFlex 755T, 755TL, 755TM, 755TR and 755TS (TotalFORCE, firmware 10 and later), fault codes are no longer in the user manuals. Rockwell keeps every fault, alarm and event in the 750-RD102 workbook, PowerFlex Drives with TotalFORCE Control Conditions Reference Data, which goes with programming manual 750-PM101 (firmware 10.xxx…14.xxx). This article uses edition 750-RD102D-EN-P, whose Summary of Changes is dated 30 May 2025.

The code number tells you where the fault is

Rockwell calls faults, alarms and events conditions. Each sheet in 750-RD102 covers one port inside the drive, and the leading digits of a code are that port number:

Sheet Code format Part of the drive
Port 0 1…376, no prefix Main control (host): digital inputs, HIM/DPI ports, EtherNet/IP, safety jumpers, hardware configuration, internal fiber links
Port 9 9xxx DeviceLogix and embedded functions (TorqProve, sleep/wake…)
Port 10, 11 10xxx / 11xxx Motor side inverter control
Port 12 12xxx Inverter power layer: power module, DC precharge, fans, temperatures, DC fuses
Port 13 13xxx Line side converter control
Port 14 14xxx Converter power layer: AC precharge, LCL filter, main breaker, AC fuses
Options nnxxx Option modules: I/O, encoder, universal feedback, safety, TLink
  • On the "Port 10, 11" sheet each condition has two codes: 10001 and 11001 are both "Power Loss". Per migration guide 750-RM102, port 10 holds the primary motor control profile and port 11 is used when a secondary motor control mode is configured.
  • Port 13 and Port 14 rows describe the line side converter: Ln power modules, AC precharge, LCL filter. Some Port 14 rows name 755TR and 755TL drives and 755TM bus supplies (for example 14135), and 750-RM102 Table 3 lists 755TS ports only up to 12. So a 13xxx or 14xxx code points to the supply side, not the motor side.
  • On the Options sheet, "nn" is the port number of the slot the module is installed in, 04 to 08 (RD102 Port 0, codes 267–270: the port number is the first two digits of the code; 750-RM102 Table 3). The same nn code means different things on different modules: nn005 is "Relay0 Life" on an I/O module but "STO Fault" on a 20-750-S3, so always read the Option column.
  • The Numeric List sheet lists every code in number order. Set Excel to search the whole workbook, not just the open sheet, as QA77928 and the Introduction sheet advise.

Condition types

The Condition Type column tells you how the drive reacts:

  • Resettable Fault: the drive trips; a reset clears it once the cause is gone.
  • Non-Resettable Fault: a reset alone is usually not enough. The Action column for this group mostly says power down or cycle power and check configuration, jumpers or fiber-optic connections, then replace the named board or module if the fault persists. Only a few call for a parameter redownload (301, 302) or firmware work (307, 309, 324, 10111 / 11111, 13067).
  • Configurable: the response is set by the parameter in the Configuration Parameter column, with the choices in Configurable Action. Example: 10003 "Motor Overload" uses 10:200 [Mtr OL Action] (Ignore, Alarm, Flt Minor, FltCoastStop, Flt RampStop, Flt CL Stop); converter-side 13003 "Phase Loss Det" uses 13:176 [LSCPhLossDetActn] (Ignore, Type 2 Alarm, Ride Thru, Major Fault).
  • Alarm 1 / Alarm 2 (type 1 / type 2 alarms): warnings. Alarm 1 includes many early threshold warnings such as 10002 "Mtr Ovrld Alarm"; Alarm 2 includes many configuration conflicts such as 104 "Port 4 Cfg".
  • Minor Fault (on Port 9, e.g. 9014 "TP Encls Config") and Event, a log entry rather than a fault (e.g. 77 "Drive Reset", 351 "Net Link 1 Down").

The Fault Action column also states whether the fault opens the main circuit breaker and whether it can reset automatically. TDL's advice: do not set a configurable fault to Ignore just to get through a shift; that switches the protection off.

Codes commonly seen in plants

Every code and display text below matches 750-RD102 exactly; the explanations are TDL's own. Search the code in the workbook for full detail.

Code Display Text Type Usual meaning What to check
10001 / 11001 Power Loss Configurable (10:270) DC bus below the power loss level for longer than the set time Supply voltage, dips when big loads start; 10:272 / 10:273 (level/time A), 10:276 / 10:277 (level/time B)
10106 / 11106 UnderVoltage Configurable (10:285) 10:13 [DC Bus Memory] below 10:286 [UnderVltg Level] Compare 10:13 with the bus measured at the test points
10107 / 11107 OverVoltage Resettable, no auto reset DC bus above 0:28 [DCBusThresh Act] Decel time, high inertia, bus regulator, brake resistor wiring and settings
10005 / 11005 Input Phase Loss Configurable (10:289) Excess DC bus ripple: lost input phase, cyclic load or speed loop tuning Fuses and lugs on all three phases; load trend
13003 Phase Loss Det Configurable (13:176) Detects a lost input phase: from line currents while modulating, or from line-to-line voltages while stopped Balance and disturbances on the three-phase supply
10003 / 11003 Motor Overload Configurable (10:200) Electronic motor overload tripped; Alarm 1 10002 "Mtr Ovrld Alarm" usually comes first 10:401 [Motor NP Amps] against the nameplate; mechanical load
10028 / 11028 Drive OverLoad Resettable 10:357 [Drive OL Count] above 100% (10027 is the Alarm 1 of the same name) Sizing, derating for temperature/altitude, cabinet filters
10093 / 11093, 10092 / 11092 HW OverCurrent / SW OverCurrent Resettable Output current above the hardware level (HW) or the 1 ms rating (SW) Short in cable/motor, insulation test, output contactor switching while running, flying start 10:70, encoder
10016 / 11016 (V: 10017 / 11017, W: 10018 / 11018) Phase U to Grnd Resettable Ground fault on one phase between drive and motor Rotate the output leads: fault follows the wire = cabling; stays = suspect the drive
12026 (converter: 14026) Ground Flt Resettable Ground current above 25% of the power module rating Terminations, taped splices, ground wires; megger motor and cable disconnected
10094 / 11094 Heatsink OvrTemp Resettable Heatsink at 100% of its limit (about 115…120 °C) Filters, fans, intake air temperature, hot-air recirculation
12065 Main Blower Flt Resettable, opens main breaker Heatsink fan below threshold speed Replace the fan per the service manual, reset its predictive maintenance counter
12006 (converter: 14006) Precharge Fault Resettable, opens main breaker DC bus not up in time after precharge Bus rise time; for 14006, external bus capacitance within limits
1 Auxiliary Input Resettable Input assigned to DI Aux Fault is open Which input 0:115 [DI Aux Fault] uses; external interlock chain
340 (and 341) Net IO Fault / Net Idle Fault Configurable (0:360 / 0:361) Network I/O connection timed out; 341 = PLC sending idle Cables, switches, network; 341 is normal when the PLC goes to Program
35 Port 1 DPI Loss Configurable (0:204) Lost the HIM in port 1 (cradle on the control pod) HIM cable; use the remove function before unplugging
nn034 / nn000 (Single Incremental Encoder) Pri VelFdbk Loss / Open Wire Loss Configurable (nn:3 [Fdbk Loss Cfg]) Primary velocity feedback lost; or a channel equals its complement Encoder wiring; open wire detection needs differential signals
nn005 (20-750-S3) STO Fault Resettable Safety module detected Safe Torque Off What is requesting STO: E-stop, guard door, safety program
87 Safety Brd Fault Non-Resettable Safety option module reported a fault Enable jumper; the module's event queue; reset or cycle power

Step by step

  1. Read the queue on the HIM or in Connected Components Workbench: fault queue, plus alarm and event queues if needed. The code prefix shows which port raised it.
  2. Record before clearing: photo, time, whether the drive was running or decelerating, and the parameters the Fault column names, such as 0:3 [DC Bus Volts], 10:363 [Heatsink Temp] or 10:357 [Drive OL Count]. Clearing the queue is itself logged as 21 "Clr Fault Queue", but the earlier faults are gone.
  3. Look it up across the whole workbook: Fault, Action and Fault Action columns.
  4. Fix the cause, then reset. A fault that returns straight after a reset means the cause is still there.
  5. Reset safely. A reset can restart the motor immediately if a run command from the PLC, an input or the network is still present. Clear the hazard zone and follow site lockout and permit-to-work rules. With auto restart enabled (0:60 [Auto Retry Fault], 0:61 [Auto Rstrt Tries], 0:62 [Auto Rstrt Delay]), a fault may have reset itself several times; when tries run out the drive shows 15 "AuRsts Exhausted" and the original fault is in the queue.
  6. Non-resettable faults: follow the Action column, usually power down or cycle power and check configuration, jumpers or fiber-optic connections; the named board or module is replaced only if the fault persists. Before opening the cabinet, isolate, wait the capacitor discharge time on the drive label and confirm with a meter.

When it is hardware

For some codes the Action column points to replacing parts per service manual 750-TG100 (755T) or 750-TG101 (755TS): 12017 "Gate Drive Flt" (Mn power module), 12051 "Bus PosFuseBlown" (find the cause, replace both DC link fuses), 12137 "Pwr Struc Fault" (replace the drive).

TDL does not repair circuit boards. Replacement modules, boards or drives go through Rockwell Automation or a Rockwell-authorised service provider; TDL can help narrow down the fault, back up and restore the configuration, and recheck the system afterwards.

Before calling for support

Record the catalog number (bulletin 20G or 20J) and firmware; code, text, type, port and time; photos of the fault and event queues; whether it repeats or lines up with a supply event or start; and a parameter backup.

On a 755TS in Integrated Motion mode, conditions are reported as CIP Motion codes; the CIP Motion Mapping sheet maps the two numbering schemes (e.g. 1 "Auxiliary Input" is condition code 523, subcode 35). Planning a move from 755 to 755TS: see PowerFlex 755 to 755TS migration.

Need an engineer on site: request support.

Frequently asked questions

Where do I look up PowerFlex 755TS fault codes?

On the PowerFlex 755T, 755TL, 755TM, 755TR and 755TS with firmware 10 and later, fault codes are no longer in the user manuals but in the 750-RD102 workbook, which goes with programming manual 750-PM101. Set Excel to search the whole workbook, not just the open sheet.

Why does each PowerFlex 755T fault have two codes, 10xxx and 11xxx?

On the "Port 10, 11" sheet each condition has two codes; for example 10001 and 11001 are both "Power Loss". Per 750-RM102, port 10 holds the primary motor control profile and port 11 is used when a secondary motor control mode is configured.

What do 13xxx and 14xxx fault codes mean on a PowerFlex 755T?

Port 13 is the line side converter control and port 14 is the converter power layer (AC precharge, LCL filter, main breaker, AC fuses). A 13xxx or 14xxx code points to the supply side, not the motor side.

How do I deal with a Non-Resettable fault on a PowerFlex 755T?

Follow the Action column in 750-RD102: usually power down or cycle power and check configuration, jumpers or fiber-optic connections; the named board or module is replaced only if the fault persists. Before opening the cabinet, isolate, wait the capacitor discharge time on the drive label and confirm with a meter.

Should I set a configurable fault to Ignore to keep the machine running?

No: setting a configurable fault to Ignore just to get through a shift switches that protection off. The response is set by the parameter in the Configuration Parameter column, for example 10:200 [Mtr OL Action] for 10003 "Motor Overload".

Sources

  • Rockwell Automation, 750-RD102D-EN-P, PowerFlex Drives with TotalFORCE Control Conditions Reference Data, 05/2025 — Excel workbook, Summary of Changes dated 30 May 2025; sheets Introduction, Numeric List, Port 0, Port 9, Port 10, 11, Port 12, Port 13, Port 14, Options, CIP Motion Mapping
  • Rockwell Automation, 750-PM101, PowerFlex Drives with TotalFORCE Control Programming Manual (firmware 10.xxx…14.xxx) — referenced by the workbook; links to the workbook at the top of its second page (per QA77928)
  • Rockwell Automation, 750-RM102A-EN-P, PowerFlex 755 Drive to PowerFlex 755TS Drive Migration Guide, 04/2024 — Preface, Table 3 "PowerFlex 755TS Drive Device Port Assignments" and Table 8 "Motor Control Mode Parameters" (ports 10 and 11)
  • Rockwell Automation, 750-TG100, PowerFlex 750-Series Products with TotalFORCE Control Hardware Service Manual (755T) — Rockwell has since replaced this manual with 750-TG102, 750-TG103 and 750-TG104 (stated on page 1 of the current PDF)
  • Rockwell Automation, 750-TG101, PowerFlex 750TS-Series Products with TotalFORCE Control Hardware Service Manual (755TS)
  • Rockwell Automation Knowledgebase QA77928 (public), PowerFlex 755T / TL / TM / TR / TS list of fault codes, published 1 July 2025
  • Rockwell Automation, TotalFORCE Programming Manual online edition — Additional Resources (where the Conditions Reference Data workbook is listed)

Read 26 October 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.

Related services: Breakdown support & maintenance