Home › End-of-life lookup › Legacy Rockwell Software (RSView32, PanelBuilder32, RSLogix 5, RSNetWorx)

RSLogix 5 Standard Software 9324-RL5300ENE (discontinued)

Rockwell lifecycle statusDiscontinued 31/12/2025 (read on 26 September 2026)
ReplacementStudio 5000 Logix Designer — named by Rockwell Automation

The Rockwell product page lists the category Engineering Replacement but names no catalog number. PLC-5 programs move to Studio 5000 Logix Designer with the Logix Designer Export in RSLogix 5; the tool converts ladder only (SFC and structured text are not converted) and inserts PCE instructions on rungs that need review (1756-RM085I p.9, 11, 16–17).

Key data

TypePLC-5 programming software
Replacement categoryEngineering Replacement (product page names no catalog number)
Migration directionStudio 5000 Logix Designer — Logix Designer Export in RSLogix 5 (1756-RM085I p.11)
Not convertedSFC · structured text (p.9)
Needs manual reviewPCE instructions inserted by the tool (p.16–17); timers change to a 1 ms time base (p.21), and every PRE/ACC reference in logic generates a PCE (p.32)

Lifecycle status changes over time: confirm the current status on the Rockwell product page or in the Product Compatibility and Download Center before ordering.

Related services: Lifecycle review and spare parts Rockwell Automation upgrades

Other catalog numbers in this family: Legacy Rockwell Software (RSView32, PanelBuilder32, RSLogix 5, RSNetWorx)

9301-2SE2100 9301-2SE3100 2711-ND3 9357-ENETL3 9357-CNETL3

Sources