Ultra5000 (2098-IPD) drive fault codes: reading E codes on the seven-segment display, DeviceNet LEDs and fixes

TDL Industrial Automation · Last updated:

How to read E codes on the Ultra5000 seven-segment display, the half-circle display, address settings 96/97/99, the DeviceNet LEDs, common codes (E04, E05, E09, E10, E20, E34, E37, E58…), what to check and how to plan the replacement.

An Ultra5000 intelligent positioning drive (Bulletin 2098-IPD) reports a fault on its seven-segment Status LED display: it flashes an E, then the two-digit error code one digit at a time, and repeats until the problem is cleared (2098-IN001E-EN-P, p. 5-2). E, 3, 4 means E34. Without any code, the same display also shows when the drive is ready, when it is in boot mode and when its firmware needs an upgrade (p. 4-4). The full code list is in chapter 5, "Maintaining Your Ultra5000" (pp. 5-2 to 5-6), followed by DeviceNet troubleshooting up to p. 5-10. The end-of-life pages show the 2098-IPD drives discontinued in 2013 with no replacement catalog number named by Rockwell; see for example 2098-IPD-010.

What the display tells you first

With the Logic Power (PWR) LED on (pp. 4-4, 5-2):

Status display Meaning What to do
Segments cycling in a full circle Drive ready Nothing
Half circle, address switches at MSD = 9, LSD = 9 Boot mode Set the address switches back to a normal address (p. 4-2)
Half circle, address switches at a normal address Firmware requires an upgrade In Ultraware: File > Upgrade Firmware (p. 4-5)
Flashing E and two digits Drive has an error Read the code below

Symptoms without a code (pp. 5-2 to 5-3):

  • PWR off: no AC power or auxiliary logic power; check the AC supply or the auxiliary +5 V logic power. If power is present, the internal power supply has failed: call your Allen-Bradley representative.
  • Seven-segment display not cycling: firmware corrupt. Set the node address to 99 and reload the firmware.
  • Small segment cycling: the node address is set to 99, or the firmware is corrupt (set 99, reload firmware, then cycle power).
  • Motor jumps when first enabled: motor wiring error or wrong motor selected.
  • Digital I/O not working: I/O connections, I/O power source and I/O type (sinking or sourcing).

The serial address switches (MSD and LSD) have special settings read at power-up: 96 stops user programs from running, useful when a program causes a communication loss; 97 resets all firmware objects, including those created by a user program, to factory defaults; 99 is boot mode, where the only action is a firmware upgrade with Ultraware. Settings 1 to 63 are for normal operation. Cycle power after changing a switch (p. 4-2).

Common error codes

Code Name in the manual Usual causes What to check
E04 Motor Overtemperature Motor thermostat trips: high motor ambient or excessive current; motor wiring; wrong motor selected Continuous torque rating at ambient (40 °C max), motor cooling, wiring, motor selection (p. 5-3)
E05 IPM Fault Shorted motor cable or winding, drive too hot, above continuous power rating, bad IPM output, short circuit or overcurrent Cable continuity, turn the motor by hand, vents, fan and space around the drive, reduce acceleration (p. 5-3)
E09 Bus Undervoltage Low AC line or AC power input Incoming AC level, glitches or line drops; a UPS on the AC input (p. 5-3)
E10 Bus Overvoltage Excessive regeneration, including a motor driven by an external mechanical source; AC input too high; output short circuit; shorted motor cable or winding Deceleration or motion profile, larger system, resistive shunt, input voltage within specification (p. 5-4)
E11 Illegal Hall State Incorrect phasing or bad connections Hall phasing and wiring, 5 V supply to the encoder (p. 5-4)
E14 DeviceNet Comm Fault Drive lost communication with the DeviceNet interface DeviceNet LEDs and network, below (p. 5-4)
E17 / E26 User-Specified Current Fault / User-Specified Velocity Fault User-set average current or velocity level exceeded Use a less restrictive setting (pp. 5-4, 5-5)
E18 Overspeed Fault Motor above 125 % of maximum rated speed Cable noise, tuning (p. 5-4)
E19 Excess Position Error Position error limit exceeded Feed forward gain, following error limit or time, position loop tuning (p. 5-4)
E20 Motor Encoder State Error Illegal encoder transition, or bad encoder Shielded twisted-pair cable, routing away from noise, system grounds; replace the motor or encoder (p. 5-4)
E21 Auxiliary Encoder state error Illegal transition on the auxiliary encoder Shielded twisted-pair cable, routing, ground connections; replace a bad encoder (p. 5-5)
E22 Motor Thermal Protection Fault Internal filter protecting the motor from overheating tripped Acceleration, duty cycle, time allowed for motion, larger drive and motor, tuning (p. 5-5)
E23 IPM Thermal Protection Fault Internal filter protecting the drive tripped Same checks as E22 (p. 5-5)
E24 Excess Velocity Error Velocity error limit exceeded Time or size of allowed error, acceleration, tuning (p. 5-5)
E29 Encoder Output Frequency Exceeded Encoder output above the user maximum (encoder output mode set to software only) Output Encoder Limit and encoder output divider parameters (p. 5-5)
E34 Ground Fault Wiring error, motor internal ground short, internal malfunction Motor power wiring; test with the motor cable removed (p. 5-5)
E35 Precharge Fault Low AC input voltage AC voltage on all phases (p. 5-5)
E36 Power Circuitry Overtemperature Excessive heat in the power circuitry Same checks as E22 (p. 5-5)
E37 AC Line Loss One or more AC input phases missing AC voltage on all phases (p. 5-6)
E39 Self-sensing Commutation Startup Error Motion needed for self-sensing startup obstructed Hard limits at startup, self-sensing current, motor or encoder wiring with wiring diagnostics (p. 5-6)
E58 Excess CPU Load User functions in the sequencer take too much time Remove the user function from the sequencer or make it smaller (p. 5-6)

For E04: the drive faults when the motor thermostat input opens. A motor without a thermostat signal can be set in software so the drive ignores the input (p. 2-27). Codes listed as Reserved (for example 01 to 03, 06 to 08, 40 to 57 and 59 to 99) mean: call your Allen-Bradley representative (pp. 5-3 to 5-6).

DeviceNet status LEDs (-DN drives)

On 2098-IPD-xxx-DN and -HVxxx-DN drives (pp. 5-6 to 5-7):

LED State Meaning and action
Module Status Flashing red Recoverable fault: power cycle or reset the drive
Module Status Steady red Unrecoverable fault: check for a power-up error; replace the drive
Network Status Off Not powered or not on-line: check the Module Status LED, other nodes and the data rate
Network Status Flashing red I/O connection timed out: re-initiate I/O messaging from the master, reduce traffic or errors
Network Status Steady red Duplicate MAC ID or bus-off: unique addresses, media installation, same data rate on every node

The DeviceNet node address is set with the MSD and LSD rotary switches (00 to 63, or PGM) and the data rate with its own switch (125, 250 or 500 kbit/s, AUTO or PGM); an address above 63 makes the drive use a value stored in non-volatile memory (p. 3-13). For a node that keeps going bus-off, the manual's order is: data rate, another node address, the tee tap, topology, then power noise with an oscilloscope (p. 5-8).

Checks, step by step

  1. Record before any reset: the code, the catalog number (-DN, HV or neither), the LED states and the address switch setting.
  2. Power faults (E09, E35, E37): measure the incoming AC at the drive, on all phases for E35 and E37 (pp. 5-5, 5-6); for E09 also check the supply for glitches or line drops, or fit a UPS (p. 5-3).
  3. E05 and E10: with all power and motor connections removed, check continuity from the DC bus to U, V and W. If there is continuity, look for wire fibers between the terminals or send the drive for repair (pp. 5-3, 5-4). For E10, also disconnect the motor power cables from the drive: if the faults stop, replace the cable (p. 5-4).
  4. E34: disconnect the motor power cable from the drive and enable with the current limit set to 0. If the fault clears, the cause is wiring or the motor; if it remains, call your Allen-Bradley representative (p. 5-5).
  5. Encoder faults (E11, E20, E21): shield and twisted pairs, routing away from noise, grounds, Hall wiring.
  6. Program-related faults (E17, E26, E29, E58): the user settings or user program. If a running program blocks communication, address setting 96 stops it from starting at power-up (p. 4-2).

Clearing faults safely

Find and correct the cause first; the error display repeats until the problem is cleared (p. 5-2). Before working on the drive, measure the DC bus voltage or wait the full time on the warning label on the front of the drive (p. 5-1). When first applying power during commissioning, the manual says to disconnect any load so the motor is free of all linkages (p. 4-3); do the same when powering a repaired or replaced drive for the first time. Clearing a fault can restart the machine: follow the plant's permit and lockout rules.

When it is hardware

  • PWR off with power present: internal power supply malfunction (p. 5-2).
  • Display not cycling and a firmware reload at address 99 does not help: the manual's next action is to call your Allen-Bradley representative (p. 5-2).
  • E05 or E10 with continuity from the DC bus to U, V or W and no wire fibers: send the drive for repair (pp. 5-3, 5-4).
  • E34 that remains with the motor cable removed and the current limit at 0 (p. 5-5).
  • Steady red Module Status LED on a -DN drive: replace the drive (p. 5-6).

Planning the replacement

The Ultra5000 runs a user program written in a compiled ANSI C subset with a library of motion functions, in 512 Kbytes of user program memory (p. A-6). Any replacement means moving that program as well as the drive, so keep a copy of the program and the Ultraware configuration now. The end-of-life page of each 2098-IPD catalog number gives the Rockwell lifecycle status, and the current Kinetix families for Kinetix 300/350/6000 and Ultra3000 drives (not the Ultra5000) are compared in Kinetix servo drive migration. For an engineer on site: breakdown support.

Frequently asked questions

How do I read an Ultra5000 error code?

The seven-segment Status LED flashes an E, then the two-digit code one digit at a time, and repeats until the problem is cleared (2098-IN001E-EN-P, p. 5-2). E, 3, 4 means E34.

What does a half circle on the Ultra5000 display mean?

With the address switches at 99, the drive is in boot mode: set the switches back to a normal address. With a normal address, the firmware requires an upgrade, done in Ultraware with File > Upgrade Firmware (pp. 4-2, 4-4, 4-5).

What is E34 Ground Fault on an Ultra5000?

A wiring error, a motor internal ground short or an internal malfunction. Disconnect the motor power cable from the drive and enable with the current limit set to 0: if the fault clears, the cause is wiring or the motor; if it remains, call your Allen-Bradley representative (p. 5-5).

What does E10 Bus Overvoltage mean on an Ultra5000?

Too much regenerated energy, AC input too high, or a short circuit at the output or in the motor cable or winding. Check the deceleration profile and the shunt; for a short, remove all power and check continuity from the DC bus to U, V and W (p. 5-4).

Sources

  • Rockwell Automation, 2098-IN001E-EN-P, Ultra5000 Intelligent Positioning Drives Installation Manual, 04/2002 — pp. 2-27, 3-13, 4-2 to 4-5, chapter 5 "Maintaining Your Ultra5000" (pp. 5-1 to 5-10), p. A-6

Read 13 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.