A Kinetix 5100 servo drive (E 003, or A plus a code for a warning, for example A 014 (
Where the fault shows
On the drive
| Where | What you see |
|---|---|
| Five-digit display | E nnn = fault, A nnn = warning (p. 450) |
| Drive Status screen | The state Fault when a fault or warning occurred during operation (p. 121) |
| MOD indicator | Flashing red: major or minor recoverable fault; steady red: major unrecoverable fault (pp. 449–450) |
| NET indicator | Flashing red: an Exclusive Owner connection timed out; steady red: duplicate IP address (p. 450) |
The fault record holds five entries: ID274 (P4.000) FaultRecordN is the most recent, ID275…ID278 (P4.001…P4.004) are older and read-only. Setting ID274 to 0 erases all records, so write them down first (p. 127).
In KNX5100C software
KNX5100C connects to the drive by a mini-USB cable (p. 17). In the Function List, "Fault Information" shows the current fault with possible causes and corrective actions; "Show Faults" refreshes it, "Fault Reset" resets it, and the "Fault History" tab lists the latest codes recorded in the drive (pp. 452–453).
In Logix Designer
Logix Designer supports the drive only with ControlMode ID117 (P1.001) set to IO Mode (0x0C) (p. 189). The Kinetix 5100 is a simple I/O device on EtherNet/IP, not an integrated-motion (CIP) drive (p. 197). Major faults and warnings appear in the Status field of the "Module Info" tab (p. 453). With the Add-On Instruction library, the status type raC_UDT_Itf_K5100_Sts carries the bits Faulted and Warning and the active codes FaultCode and WarningCode (p. 501). Error code 101 from one of these instructions means "Drive is faulted": it is an instruction error, not a drive code (p. 524).
Common fault and warning codes
Names, types, causes and checks below are from
| Code | Name in |
Type | Causes listed | What to check |
|---|---|---|---|---|
| E 001 | Over current | Recoverable | Current above 1.5 times the drive's rated peak output: output short, motor wiring, IGBT error, control parameters, unreasonable command | Drive-to-motor wiring and shorts; heat sink temperature; parameters above default (return to default, then adjust); longer acceleration or a command filter |
| E 002 | Over voltage | Recoverable | Main circuit voltage above the rated allowable voltage; the drive may be damaged | Main input voltage; if it persists, contact your distributor or Rockwell |
| E 003 | Under voltage | Recoverable | Main input voltage too low, or no voltage to the power circuit | Main input voltage and input wiring |
| E 005 | Regeneration error | Recoverable | Shunt resistor missing or its value too low; ID158 (P1.053) ShuntResistorPower not 0 with no shunt resistor; regenerative switch transistor may be shorted | Shunt resistor connection; ID157 (P1.052) ShuntResistorValue and ID158; set ID158 to 0 when no shunt resistor is used |
| E 006 / E 02C | Motor overload / Drive overload | Recoverable | Motor or drive rating exceeded, control parameters, accel/decel settings, motor–encoder wiring | Load against motor and drive size, mechanical vibration, tuning, accel/decel, wiring. Example: 200 % average load for more than 8 seconds gives E 006 (p. 439) |
| E 011 | Encoder error | Unrecoverable | Encoder wiring, loose connector, damaged encoder | Encoder wiring and connectors at drive and motor; replace the motor if the encoder is damaged |
| A 014 / A 015 | Reverse limit warning / Forward limit warning | Warning | Limit switch activated, or the servo system is unstable | Move the axis away from the switch; control parameters and inertia ratio |
| E 016 | IGBT overheat | Recoverable | Load above the drive rating, or drive output short-circuited | Overload or high motor current; output wiring |
| E 022 | Input voltage phase loss | Recoverable | Abnormal input voltage | Main power input wiring; if it persists, contact your distributor or Rockwell |
| E 030 | Exceed torque limit | Recoverable | ID162 (P1.057) CrashProtectionTorqueThreshold and ID163 (P1.058) CrashProtectionFilterTime set wrongly | Set ID162 to 0 if the function is not used, otherwise raise both values |
| A 060 / A 061 / A 06A | Absolution position lost / Encoder under voltage / Absolute position is not initialized | Warning | Absolute position not initialized, battery undervoltage, first use or battery change | Battery; home or initialize the absolute position |
| E 083 | Excessive over current | Recoverable | Output above 95 % of hardware overcurrent: output short, motor wiring, unreasonable acceleration time in the command | Drive-to-motor wiring and shorts; a smoother command |
| E 085 | Shunt resistor error | Recoverable | Shunt resistor not operating while the DC bus stays at 400 V for over 110 ms | Shunt resistor connection; recalculate and reset ID157 (P1.052) and ID158 (P1.053) |
| E 601 | Duplicate IP address | Unrecoverable | IP address already in use | Set an unused IP address |
| E 602 | Control connection loss fault | Unrecoverable | Faulty or disconnected Ethernet cable, controller lost power | Ethernet cable and connection, controller operation |
| E 60B / E 611 | Motor selection match error / Feedback serial comms | Unrecoverable | Wrong motor selection or encoder wiring; for E 611 also motor vibration | Motor selection, encoder wiring, feedback shield (E 611); if it persists, replace the motor (E 611: motor or encoder) |
For A 014 and A 015, the digital input table in the user manual pairs the reverse and forward limit switches with these two codes the other way round (p. 436), so check which switch is actually open; the same table says the limit alarm clears once the input turns back on. Autotuning faults E 08A, E 08B and E 08C are in Table 78 (p. 211).
Checks, step by step
- Record before resetting: the code, the fault records or the "Fault History" tab, and the MOD and NET states.
- Supply (E 002, E 003, E 022): main input voltage and input wiring.
- Overcurrent (E 001, E 083): drive-to-motor wiring and shorts, then the acceleration time.
- Regeneration (E 005, E 085): shunt resistor wiring, ID157 (P1.052) and ID158 (P1.053).
- Feedback and network (E 011, E 611, E 601, E 602): encoder cable and connectors; IP address, Ethernet cable and controller. NET steady red means a duplicate IP address (p. 450).
Safe Torque Off faults
The STO connector carries STO_A (S1, S1C), STO_B (S2, S2C), the bypass pins SB+ and SB– and the safety status output SS+ and SS– (p. 415). The drive does not run without either a safety circuit or the bypass jumpers, which are installed by default (p. 417).
| Code | Name in |
Type | When it is posted | What to check ( |
|---|---|---|---|---|
| E 500 | STO enabled | Recoverable | Both STO inputs off for more than 10 ms (p. 412) | Whether STO was requested; bypass wiring if STO is not used; STO wiring |
| E 501 | STO_A signal loss | Unrecoverable | STO_A off for more than 1 second while STO_B is on (p. 412) | STO_A wiring |
| E 502 | STO_B signal loss | Unrecoverable | STO_B off for more than 1 second while STO_A is on (p. 412) | STO_B wiring |
| E 503 | STO self-diagnostic error | Unrecoverable | The STO self-diagnostic fails, for example STO circuit or wiring (p. 413) | Wiring per the manual; if it persists, contact your distributor or Rockwell |
E 500 can be reset only with both inputs on, and then needs a Fault Reset from raC_xxx_K5100_MAFR or the DI.ARST input; E 501, E 502 and E 503 can be reset by cycling power (p. 414). Bit 0 (Servo Ready) of ID107 (P0.046) ServoOutputStatus shows the STO input status in KNX5100C (pp. 411–412). After troubleshooting or maintenance that can affect STO, run the STO function to confirm it works (p. 413).
Clearing faults safely
- Warnings (A nnn) clear by themselves when the cause is corrected (p. 454).
- Major recoverable faults: "Reset Module" in Logix Designer, the DI.ARST input, "Fault Reset" in KNX5100C, writing 0 to ID101 (P0.001) FltWarnCode, or the raC_xxx_K5100_MAFR instruction (p. 454). The reset input and the MAFR instruction do not clear a fault that is still active (pp. 434, 506).
- Major unrecoverable faults: cycle power; if the fault persists, contact your distributor or Rockwell (p. 454).
- How the motor stops on a fault is set by ID675 (P1.032) MotorStopMode (p. 454).
Do not defeat the drive fault circuits; find the cause first. Before working on the drive, measure the DC bus voltage or wait the time on the warning label; the CHARGE indicator is on while the bus is above 50 V DC (p. 449). Clearing a fault can restart motion: follow the plant's permit and lockout rules.
When it is hardware
- E 017 Abnormal EEPROM: contact your distributor or Rockwell (
2198-RD001 ). - E 034 Encoder communication error: change the motor (
2198-RD001 ). - E 600 Boot failure and E 604 Watchdog fault: cycle power (control power for E 604), update the drive firmware, then contact your distributor or Rockwell if it persists (
2198-RD001 ). Firmware upgrade is in Appendix B (p. 477). - E 555 Malfunction of the system and E 60C Internal fault: contact your distributor or Rockwell if they persist (
2198-RD001 ).
Planning notes
- Wire the digital outputs Servo Alarm (0x07) and Warning (0x11) to the PLC. Servo Alarm does not turn on for limit switches, communication error, undervoltage or fan error; the Warning output covers those (pp. 438–439). Early Warning for Overload (0x10), set with ID161 (P1.056), comes on before E 006 (p. 439).
- KNX5100C cannot change the configuration while the controller holds an I/O connection: check "Inhibit Module" first (p. 197).
- Before calling for support, note the hardware and firmware versions from the Version Information screen, shown as
h 01.002 F 01.102in the manual's example (p. 121), the motor catalog number and what the machine was doing.
The Kinetix 5300 uses a different code system (F…, nF…, SF…): see Kinetix 5300 fault codes. For an engineer on site: breakdown support.
Frequently asked questions
What is the difference between E and A codes on a Kinetix 5100?
E plus a code is a fault and turns the servo off; A plus a code is a warning, which clears by itself once the cause is corrected (
What does E 500 STO enabled mean on a Kinetix 5100?
Both STO inputs were off for more than 10 ms. Check whether STO was requested, the STO wiring, and the bypass wiring if STO is not used. E 500 can be reset only with both inputs on, followed by raC_xxx_K5100_MAFR or the DI.ARST input (pp. 412, 414).
What is E 602 on a Kinetix 5100?
E 602 Control connection loss fault: communication with the controller was lost through a faulty or disconnected Ethernet cable or a controller that lost power.
How do I reset a Kinetix 5100 fault?
A recoverable fault is reset with "Reset Module" in Logix Designer, the DI.ARST input, "Fault Reset" in KNX5100C, ID101 (P0.001) = 0 or raC_xxx_K5100_MAFR; an unrecoverable fault needs a power cycle (p. 454). Clearing a fault can restart motion, so follow the plant's permit and lockout rules.