Read the LED and the HIM first
| Status LED | Meaning |
|---|---|
| Green | Running without an alarm |
| Green/Amber | Running with an alarm |
| Green flashing | Ready, no inhibit, no fault, no alarm |
| Amber | Ready with an alarm |
| Red/Amber | Inhibited: cannot start because of a Stop command |
| Red flashing | A resettable fault has occurred |
| Red | A non-resettable fault has occurred |
| Amber flashing | Ready, tuning enabled on the next start |
| Red/Green | Firmware is being downloaded |
Source: Table 125, p. 199.
- Port number in front of the code: when the fault comes from a device in a DPI port, the port number is shown first. Port 7, fault 26 is displayed as 7026 (p. 109).
150-SM6 module: one LED (>) shows the source, red for the controller and yellow for the motor, and the other three give a code from 0 to 7; one code covers several faults, so read the exact code on a HIM or in software (pp. 199–200).- Codes 71 to 77 (Start, Slow Speed, Stop Option, Coast, Clear Fault, Fault, Param Change) are event codes, not faults (pp. 204, 213–214).
- "Starting" with no output: one or more phases missing, or an isolation contactor that does not pick up; the Aux relay controlling the isolation contactor must be set to "Normal" (p. 214).
Fault and alarm buffers
- Parameters 138 to 142 hold the last five fault codes and parameters 143 to 147 the last five alarm codes, newest first (p. 201).
- On the
20-HIM-A6 , the DIAGNOSTIC folder lists the last five faults and the last 100 alarms; select one and press ENTER to see the date and time it occurred (p. 203). - The same buffers are available in Connected Components Workbench software (p. 203).
Is the fault enabled?
Faults and alarms are switched on bit by bit: parameter 136 [Starter Fault En], 137 [Starter Alarm En], 230 [Motor Fault En] and 231 [Motor Alarm En] (p. 110). In parameter 230 every motor fault is disabled by default except Overload, Power Qual and Open Load (p. 111). So a jam, stall or underload will not trip the starter unless someone enabled its bit. Shorted SCR, SCR Overtemp, CT Loss, HAL ID, NVS Error, V24 Loss, VControl Loss, Power Pole PTC and I/O Config are always enabled (pp. 205–206).
Common fault codes
| Code | Name | Usual causes | What to check |
|---|---|---|---|
| 1, 2, 3 | Line Loss A / B / C | Missing supply phase, high-impedance line connection, motor not connected properly, unstable supply | Loose line and load connections, blown fuse, open line leads, power quality (p. 210) |
| 4, 5, 6 | Shorted SCR A / B / C | Shorted power module; detected in the prestart check | Resistance check on p. 215; replace the power module if necessary (pp. 205, 210) |
| 7, 8, 9 | Open Gate A / B / C | Open gate circuit, loose gate lead (during start or stop) | Resistance check; gate leads TB5, TB6, TB7 firmly seated on the control module (p. 210) |
| 10 / 60 | SCR Overtemp / Power Pole PTC | Blocked ventilation, duty cycle exceeded, fan failure, ambient too high, failed thermistor | Ventilation, duty cycle, fan; let the controller cool (pp. 210, 213) |
| 11, 12, 13 | Open Bypass A / B / C | Low control voltage, inoperable bypass in the power module | Control supply; TB2…TB4 and TB5…TB7; no auxiliary set to "external bypass" (p. 210) |
| 14 / 15, 16, 17 | No Load / Open Load A / B / C | Load-side power wiring lost; start command cycled while the motor was still rotating (prestart only) | Load-side connections; motor windings (p. 210) |
| 18 / 42 | Voltage Unbal / Current Imbal | Supply unbalance above the set value, delay too short | Power system; delay time (p. 210) |
| 19 / 20 | Overvoltage / Undervoltage | Line voltage above or below the set value, abnormal regulation, settings not suited | Power system; level and delay (p. 210) |
| 21 | Overload | Motor overloaded, overload settings not matched to the motor | Load; overload class, Motor FLC and actual motor current (p. 210) |
| 22 | Underload | Broken shaft, belt or grating, pump cavitation | Machine, pump, settings (p. 210) |
| 23 | Jam | Motor current above the jam level for the set time while running | Source of the jam or excess load; jam time (p. 210) |
| 24 | Stall | Motor not at full speed at the end of the ramp time | Pump, drive components and loading; settings (p. 210) |
| x026 | Exp Removed | Expansion module loose, removed or defective; a HIM unplugged while its Logic Mask bit is set | Re-seat or replace the module and tighten its screws (pp. 194, 211) |
| 30, 31, 32 | CT Loss A / B / C | Loose CT cable between power section and control module, failed current feedback | TB2 (A), TB3 (B), TB4 (C) firmly seated; replace the control module and/or power section (p. 211) |
| 33 | HAL ID | Loose cables to the power section, incompatible power section | Connectors seated; power section (p. 211) |
| 34 | NVS Error | Memory corrupted, or an option module error (7034, 8034, 9034) | Load defaults and reload the parameters; option module cables (p. 211) |
| 36 / 37 | V24 Loss / VControl Loss | Loose connection at control terminals 1 (+L1) and 2 (-L2), low line voltage; for V24 also too much load on the internal 24 V | Control power within specification, connections and grounding; replace the control module (p. 211) |
| 52, 53, 54 | Power Quality A / B / C | Supply unstable or distorted, high-impedance line or load connection: the phase SCRs are not firing properly | Supply capability to start and stop the motor; loose connections on line or motor side (pp. 128, 212) |
| x058 | Ground Fault | Ground fault current above the set level, delay too short | Power system and motor; ground fault levels and delay (p. 212) |
| x059 | Motor PTC | Motor ventilation blocked, duty cycle exceeded, PTC open or shorted | Motor cooling; after it cools, the PTC resistance (p. 212) |
| 62 | Test Fault | HOLD TO TEST, PUSH TO RESET button held 3 to 10 seconds, or stuck | Press the button for less than 2 seconds to reset; free a stuck button or replace the control module (p. 213) |
| 100…199 | System Faults | Control module wiring, defective control module | Ground terminal to earth, RC snubbers on inductive loads in the control circuit; replace the control module (p. 214) |
"x" is the port number of the expansion module (p. 214). Ground Fault and Motor PTC need the optional
Checks, step by step
- Record before resetting: LED state, the code with its port number, parameters 138 to 147 and the time stamps in the DIAGNOSTIC folder.
- Supply faults (1–3, 18–20, 52–54): line and load connections, fuses, the power system and the delay settings (pp. 210, 212). If Line Loss is disabled, the manual suggests enabling Undervoltage to limit motor damage from phase loss (p. 127).
- Shorted SCR (4–6): disconnect main and control power, mark the wires and record the parameters, then measure line to load on each phase (
L1-T1 ,L2-T2 ,L3-T3 ) with an ohmmeter. Above 5,000 Ω is good; otherwise replace the power assembly (p. 215). In a wye connection a single shorted SCR is not detected until the unit is started (p. 205). - Open Gate, CT Loss, HAL ID (7–9, 30–33): remove the control module from the power section and check that TB2 to TB7 are firmly seated, as Table 131 lists for each code (pp. 210–211).
- Temperature (10, 60, x059): ventilation, duty cycle, fan, ambient. For Motor PTC, the
150-SM2 input responds at 3400 Ω ± 150 Ω and trips on a short circuit at 25 Ω ± 10 Ω (p. 254). - Load faults (21–24): overload class, service factor and Motor FLC against the nameplate, then the machine (pp. 205, 210). Parameter 188 [Stall Delay] runs after the ramp time, default 10.0 s (p. 119).
- Control power (36, 37, 100…199): control voltage at terminals 1 and 2, grounding, RC snubbers (pp. 211, 214).
Clearing faults safely
Fix the cause first; a reset does not correct it (p. 201). Ways to clear a fault (p. 201):
- Press HOLD TO TEST, PUSH TO RESET for less than 2 seconds. Holding it 3 to 10 seconds creates Test Fault 62, and more than 10 seconds starts tuning mode (p. 199).
- A N.O. push button on Option Input #1 (terminal 11) or #2 (terminal 10), programmed for Clear Fault in parameter 56 [Input 1] or 57 [Input 2], or an input on a
150-SM4 module. - Cycle control power. NVS Error is not cleared this way; it needs a parameter change or loading defaults (p. 206).
- Automatic restart, below.
An overload fault cannot be reset until parameter 18 [Motor Therm Usage] falls below parameter 80 [OL Reset Level] (p. 201), default 75 % (p. 114); parameter 20 [Time to OL Reset] shows the time left (p. 114).
Auto restart. Parameters 135 [Strtr Restart En] and 264 [Motor Restart En] enable automatic restart fault by fault; all bits are disabled by default. Parameter 133 [Restart Attempts] sets the number of tries and 134 [Restart Dly] the delay; for an overload the restart waits for parameter 18 to fall below parameter 80 (p. 133). Auto-restart can start the motor without warning; follow the plant's permit and lockout rules.
Hazardous voltage is present in the motor circuit even when the
When it is hardware
- Shorted SCR test below 5,000 Ω: replace the power assembly; spare parts are listed in publication
150-TD009 (p. 215). - Open Gate after the resistance check, Open Bypass from an inoperable bypass: replace the power module (p. 210).
- CT Loss with a failed current feedback circuit: control module and/or power section (p. 211).
- HAL ID with an incompatible power section (p. 211).
- V24 Loss, VControl Loss, System Faults, a stuck Test button: replace the control module (pp. 211, 213–214).
A failed power switching component can single-phase the motor; the manual recommends an isolation contactor or shunt-trip breaker on the line side, and a function check after any short circuit (pp. 7–8).
Before calling for support
Note the catalog number, the firmware, the codes and time stamps in the buffers, and the parameter values. If the starter's own overload is disabled, external motor overload protection should be used (p. 214), and two-speed or multiple motors need separate overload relays (p. 98); if that relay is an E300, see E300 trip and warning codes. Need an engineer on site: breakdown support.
Frequently asked questions
What does a red LED on an SMC-50 mean?
Steady red means a non-resettable fault and flashing red a resettable fault; red/amber means the starter is inhibited by a Stop command (
What is fault 7026 on an SMC-50 ?
The first digit is the port and 26 is Exp Removed: the module in port 7 was removed, is loose or is defective. Re-seat or replace it and tighten its screws (pp. 109, 211).
Why does my SMC-50 not trip on jam or stall?
In parameter 230 [Motor Fault En] all motor faults are disabled by default except Overload, Power Qual and Open Load, so the Jam and Stall bits must be enabled (p. 111).
How do I reset a fault on an SMC-50 ?
After fixing the cause, press HOLD TO TEST, PUSH TO RESET for less than 2 seconds, use an input programmed for Clear Fault, or cycle control power (pp. 199, 201). An overload resets only when parameter 18 falls below parameter 80 [OL Reset Level] (p. 201).
Sources
- Rockwell Automation,
150-UM011F-EN-P ,SMC-50 Soft Starters User Manual, 04/2025 — pp. 7–8, 98, chapter 5 "Protection and Diagnostic Functions" (pp. 109–133), p. 194, chapter 10 "Diagnostics" (pp. 199–207), chapter 11 "Troubleshooting" (pp. 209–215), p. 254
Read 13 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.