SMC Flex (150-F) soft starter fault codes: reading the LCD and fault buffer, Shorted SCR, Line Loss and fixes

TDL Industrial Automation · Last updated:

How to read a fault on the SMC Flex soft starter LCD, the five-fault buffer, common codes (Line Loss, Shorted SCR, Open Gate, Overload, Jam, Stall, Ground Fault…), the shorted SCR test, safe fault clearing and when a module needs replacing.

An SMC Flex soft starter (Bulletin 150-F) shows a fault on its built-in three-line, 16-character LCD: the first line says the unit has faulted, the second gives the fault number and the third the fault text, for example "Faulted / Fault #1 / Line Loss A" (150-UM008J-EN-P, p. 99). The unit trips and stops on every fault in the fault definitions table (p. 101). The full list is Table 42, "Fault Code Cross-reference" (p. 100), and the causes and fixes are in Table 44, "SMC Fault Display Explanation" (pp. 104–105).

Read the display first

  • Fault on the LCD: stays on screen as long as control power is applied. Pressing Esc moves you to other menus, but the controller stays faulted (p. 99).
  • Alarm: many protections have an alarm (pre-fault) level as well as a fault level, for example undervoltage, overvoltage, unbalance and jam. An alarm shows on the LCD, the HIM, over communication if used, and on an alarm contact (pp. 19–20). The "Diagnostics" menu holds "Alarms", "Faults" and "Device Revision" (p. 78).
  • Auxiliary contacts: the four outputs Aux #1 to Aux #4 can be programmed as Fault or Alarm, N.O. or N.C., so the PLC or a lamp can see the trip (pp. 25, 101).
  • Display blank, "Stopped 0.0 Amps" or "Starting" with no rotation: not a fault code; see the symptom tables (p. 105). If all three phases are missing when a start is given, the LCD shows "Starting" and the motor does not turn (p. 101).

Fault buffer

The controller keeps the five most recent faults. View them in the fault queue, or read Fault 1 (Parameter 124) to Fault 5 (Parameter 128); Fault 1 is the current fault and Fault 5 the oldest (p. 100). Write them down before cycling control power, because cycling control power clears the active fault (p. 99).

Common fault codes

Code Display Usual causes What to check
1, 2, 3 Line Loss A / B / C Missing supply phase, motor not connected properly (prestart fault) Loose line and load connections, blown fuse, open line leads, power quality (p. 104)
4, 5, 6 Shorted SCR A / B / C Shorted power module; starting is prohibited Shorted SCR test; replace the power module if necessary (pp. 101, 104)
7, 8, 9 Open Gate A / B / C Open gate circuit or loose gate lead; the controller tries to start three times before shutting down Resistance check; gate lead connections to the control module (pp. 24, 104)
10 / 11 PTC Pwr Pole / SCR Overtemp Blocked ventilation, duty cycle exceeded, fan failure, ambient too high, failed thermistor Ventilation, duty cycle, fan; wait for the controller to cool (p. 104)
12 Motor PTC Motor ventilation blocked, motor duty cycle exceeded, PTC open or shorted Motor cooling and duty cycle; PTC resistance at terminals 23 and 24 (pp. 22, 104)
13, 14, 15 Open Bypass A / B / C Low control voltage, inoperable bypass in the power module Control supply; TB2…TB4 and TB5…TB7 on the control module; Aux 1–4 not set to External Bypass (p. 104)
16, 17, 18, 40 No Load A / B / C, No Load Load-side power wiring lost All load-side connections and motor windings (p. 104)
19 Line Unbalance Supply unbalance above the set value, delay too short Power system; delay time (p. 104)
20 / 21 Overvoltage / Undervoltage Supply voltage above or below the set value, abnormal regulation, settings not suited Power system; level and delay settings (p. 104)
22 Overload Motor overloaded, overload settings not matched to the motor Load; overload class and Motor FLC (p. 104)
23 Underload Broken shaft, belt or toolbit, pump cavitation Machine and pump system (p. 104)
24 Jam Motor current above the jam level Source of the jam; jam delay time (p. 104)
25 Stall Motor not at full speed at the end of the ramp time Pump system, drive components and loading; settings (p. 104)
26 Phase Reversal Supply not in ABC sequence Power wiring (p. 104)
27, 28, 29 Coms Loss P2 / P3 / P5 Communication cable disconnected at the serial (DPI) port Cable to the controller (pp. 100, 104)
30, 31, 32 Network P2 / P3 / P5 DPI network loss, raised by the network outside the controller Reconnect each DPI device (pp. 101, 104)
33 Ground Fault Ground fault current above the set level Power system and motor; ground fault settings (p. 104)
35, 36, 37 Power Loss A / B / C Missing supply phase (prestart) Open line, blown line fuse (p. 104)
38 Hall ID Loose cables to the power section, wrong power module Connectors seated on the control module; power module (p. 105)
39 NVS Error Controller memory corrupted Load defaults and reload the parameters; replace the control module if necessary (p. 105)
41, 42, 43 Line Loss A / B / C SCR conduction is discontinuous: line distortion or a high-impedance connection Supply capability to start and stop the motor; loose line or motor connections (pp. 101, 105)
44 / 45 / 46 V24 Recovery / V24 Loss / V Control Internal 24 V supply low or out of range, control voltage sensing error Control power level and connections including ground; replace the control module (p. 105)
128…209 System faults Control module wiring, defective control module Ground terminal, RC snubbers on inductive loads in the control circuit; replace the control module (p. 105)

Phase loss, overvoltage and undervoltage protection are off during braking; jam and underload are off during slow speed and braking (p. 101). Jam and underload only work when Motor FLC is programmed (p. 86).

Checks, step by step

  1. Record before resetting: the LCD text, Fault 1 to Fault 5 (Parameters 124–128) and what the machine was doing.
  2. Supply faults (1–3, 35–37, 41–43): line and load connections, fuses, line leads; for 41–43 also line distortion and high-impedance connections on the line or motor side (pp. 104–105).
  3. Shorted SCR (4–6): with main power disconnected and the wires marked, measure line to load on each phase (L1-T1, L2-T2, L3-T3) with an ohmmeter; the reading should be above 5,000 Ω (p. 106).
  4. Check Line Load (energized test): only authorized, electrically qualified persons, with power applied, no start command and no motor connected. Measure L1…T1, L2…T2 and L3…T3: on a 480 V system each reads 277 V; if phase A is shorted the readings are 0, 480, 480. For 600 V: 347 V, or 0, 600, 600 (p. 107).
  5. Temperature (10–12): controller or motor ventilation, duty cycle, fan running, ambient; for Motor PTC, the PTC resistance. The PTC input trips above 3400 Ω ± 150 Ω and also on a short circuit below 25 Ω ± 10 Ω (pp. 22–23, 104).
  6. Load protections (22–25): overload class and Motor FLC against the nameplate, then the machine: belts, pump, binding (pp. 104–105).
  7. Ground Fault (33): needs an external core balance sensor, for example 825-CBCT on 5…480 A units, and the level (Parameter 73), delay (74) and inhibit time (75) set for the application (pp. 21–22, 104).
  8. Communication (27–32): the cable at each DPI port. Control through DPI is disabled by factory default; to give control, set the Logic Mask in the Communication group (p. 101).

Clearing faults safely

Correct the cause first: resetting does not fix it (p. 99). The manual lists these ways to clear a fault (p. 99):

  • "Clear Fault" in Main Menu / Diagnostics / Faults.
  • Hold Esc on the control module keypad for 3 seconds (firmware 6.001 or later).
  • Press Stop on a connected HIM. A stop from the HIM always stops the motor and clears the fault, regardless of Logic Mask.
  • A N.O. reset push button on Option Input #2 (terminal 15) programmed for Clear Fault.
  • Cycle control power.

An overload fault cannot be reset until Motor Thermal Usage (Parameter 12) is below 75 % (p. 99). Overload Reset (Parameter 47) can be Manual or Auto (p. 17), and Figure 17 gives an auto reset time for each trip class (p. 18). Before choosing Auto, check what the start circuit does once the fault resets itself (the manual does not describe this), and follow the plant's permit and lockout rules.

The manual's hazard notes: hazardous voltage is present in the motor circuit even when the controller is off, so disconnect main power before working on the controller, motor or control devices (p. 103). Hazardous voltage is present on L1, L2, L3, T1, T2, T3, T4, T5 and T6 (p. 28). Disconnect the controller from the motor before an insulation resistance test of the windings; IR test voltage can destroy the SCRs, and no megger measurement should be made on the controller (p. 103).

When it is hardware

  • Shorted SCR test below 5,000 Ω, or Shorted SCR that does not clear: replace the power module (pp. 104, 106). A power pole includes the SCRs and the bypass contactor (p. 109).
  • Open Gate after the resistance check, and Open Bypass from an inoperable bypass: replace the power module (p. 104).
  • SCR Overtemp or PTC Pwr Pole with a failed thermistor: power module or control module (p. 104).
  • Hall ID with the wrong power module installed (p. 105).
  • NVS Error that returns after loading defaults, V24 or V Control faults, and system faults 128…209: replace the control module (p. 105).

Renewal part numbers for control modules and power poles are in Appendix A (p. 109).

Before calling for support

Note the catalog number, the firmware in "Device Revision" (p. 78), the five faults in the buffer, the parameter values, and readings from the checks above. Where an SMC Flex feeds a two-speed motor or several motors, the manual calls for separate overload relays for each speed, or individual overload protection for each motor (p. 32); if that relay is an E300, see E300 trip and warning codes. Need an engineer on site: breakdown support.

Frequently asked questions

What does Shorted SCR mean on an SMC Flex?

Codes 4, 5 and 6 mean a shorted SCR was detected in phase A, B or C, and starting is prohibited (p. 101). With main power disconnected, the line-to-load resistance of each phase should be above 5,000 Ω; if not, replace the power module (pp. 104, 106).

What is the difference between Line Loss 1–3 and Line Loss 41–43?

Codes 1 to 3 are prestart faults for a missing supply phase or a motor not connected properly. Codes 41 to 43 mean SCR conduction is discontinuous, from line distortion or a high-impedance connection (pp. 101, 104–105).

Why can I not reset an Overload fault on an SMC Flex?

The overload fault cannot be reset until Motor Thermal Usage, Parameter 12, is below 75 % (p. 99). Let the motor cool, then check the load and the overload class and Motor FLC settings (p. 104).

How do I clear a fault on an SMC Flex?

After fixing the cause: "Clear Fault" in the Diagnostics menu, hold Esc for 3 seconds (firmware 6.001 or later), Stop on a HIM, a reset button on Option Input #2 programmed for Clear Fault, or cycle control power (p. 99).

Sources

  • Rockwell Automation, 150-UM008J-EN-P, SMC Flex User Manual, 04/2025 — pp. 17–25, 28, 32, 78, 86, chapter 8 "Diagnostic Capabilities" (pp. 99–101), chapter 9 "Troubleshooting" (pp. 103–107), p. 109

Read 13 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.