Ultra3000 (2098) servo drive fault codes: reading E codes on the seven-segment display, SERCOS/DeviceNet LEDs and fixes

TDL Industrial Automation · Last updated:

How to read E codes on the Ultra3000 seven-segment display, the flashing L, the SERCOS and DeviceNet LEDs, common codes (E05, E09, E10, E20, E30, E34, E37, E43, E50…), what to check and how to plan the replacement.

An Ultra3000 servo drive (Bulletin 2098) reports a fault on its seven-segment status display: it shows an E, then flashes the two-digit error code one digit at a time, and repeats until the problem is cleared (2098-IN003E-EN-P, p. 4-3). E, 2, 0 means E20. A flashing L is not a fault code: the drive is in an overtravel condition and motion is restricted. The full list is in chapter 4, "Troubleshooting Status Indicators" (pp. 4-3 to 4-8). Rockwell lists the 2098-DSD drives as discontinued; each end-of-life page, such as 2098-DSD-010, gives the replacement Rockwell lists.

What the display tells you first

With the Logic Power LED on (p. 4-3):

Status display Drive type Meaning
Segments cycling in a full circle 2098-DSD-xxx, -xxxX, -HVxxx and DeviceNet (-DN) drives Drive ready
Fixed 4 SERCOS drives (-SE) Drive ready
Flashing E and two digits All Drive has an error
Flashing L All Overtravel condition, motion restricted

If the PWR indicator is off, check the AC power or the auxiliary +5 V logic power. On 2098-DSD-005, -010 and -020 drives with external +5 V auxiliary power, PWR on with the status display off can mean the auxiliary supply is too low: the manual asks for 5.10 to 5.25 V measured at the drive terminals (p. 4-3).

Common error codes

Code Name in the manual Usual causes What to check
E04 Motor Overtemperature Motor thermostat trips: high ambient or excessive current, wiring, wrong motor Continuous torque rating at ambient (40 °C max), cooling, motor wiring and selection (p. 4-4)
E05 IPMFault Shorted motor cable or winding, drive too hot, above continuous rating, IPM failure Cable continuity, turn the motor by hand, vents and fan, reduce acceleration (p. 4-4)
E06 Hardware Overtravel (SERCOS only) Dedicated overtravel input inactive Wiring, motion profile (p. 4-4)
E09 Bus Undervoltage Low AC line or AC power input Incoming AC level, glitches or line drops (p. 4-4)
E10 Bus Overvoltage Excessive regeneration or AC input too high Deceleration profile, shunt wiring and fuse, larger system (p. 4-5)
E11 IllegalHall State Hall phasing or connections Hall wiring, 5 V supply to the encoder (p. 4-5)
E18 Overspeed Fault Motor above 125 % of maximum rated speed Cable noise, tuning (p. 4-5)
E19 Excess Position Error Position error limit exceeded Feedforward gain, following error limit, position loop tuning (p. 4-5)
E20 Motor Encoder State Error Illegal encoder transition: noise, bonding, bad encoder Shielded twisted-pair cable, routing, grounds, high-frequency bond of motor to panel (p. 4-6)
E22 Motor Thermal Protection Fault Internal motor thermal filter tripped Acceleration, duty cycle, motion time, size, tuning (p. 4-6)
E23 IPM Thermal Protection Fault Internal drive thermal filter tripped Same checks as E22 (p. 4-6)
E30 Encoder Communication Fault No communication with an intelligent encoder Motor selection, automatic identification support, encoder wiring (p. 4-7)
E34 Ground Fault Wiring error, motor ground short, internal fault Motor power wiring; test with motor cable removed (p. 4-7)
E35 Precharge Fault Low AC input voltage or internal fault AC voltage on all phases (p. 4-7)
E37 AC Line Loss One or more AC input phases missing AC voltage on all phases (p. 4-7)
E39 Self-sensing Commutation Startup Error Motion for self-sensing startup obstructed Hard limits at startup, self-sensing current, wiring diagnostics (p. 4-8)
E40 / E41 230V / 460V Shunt Protection Fault Shunt resistor ineffective or excessive regeneration Shunt connected, shunt fuse, resistance value, motor not driven mechanically (p. 4-8)
E43 Drive Enable Input (SERCOS only) Software enable with hardware input inactive, or input dropped while enabled Drive Enable input active whenever the drive is enabled through software, or disable the Drive Enable Input fault (p. 4-8)
E50 Duplicate Node Fault (SERCOS only) Two drives with the same SERCOS node address Unique node address on every drive (p. 4-8)

E05 has one more cause on 2098-DSD-005, -010 and -020 drives with external +5 V auxiliary power: enabling less than 1.0 second after main AC is applied (p. 4-4). Codes listed as RESERVED (E07, E08, E38 and others) mean: call your Rockwell representative (pp. 4-4, 4-7, 4-8).

The documentation update 2098-DU003B-EN-P (09/2006) adds E44, a lost-motion fault on applications with Stegmann feedback: absolute position in the drive is incorrect after a line-loss condition; cycle power and re-home the drive if it was homed in the same power cycle (p. 2 of the update).

SERCOS and DeviceNet status LEDs

LED State Meaning
SERCOS Module Status Flashing red-green DC bus low: normal on auxiliary power only, otherwise read the error code
SERCOS Module Status Flashing red / steady red Recoverable fault / unrecoverable fault
SERCOS Network Status Flashing red No communication: loose or broken fiber, or receive and transmit swapped
SERCOS Network Status Flashing green Still establishing communication, or node address does not match the controller
DeviceNet Module Status Flashing red / steady red Recoverable fault (power cycle or reset) / unrecoverable fault
DeviceNet Network Status Flashing red I/O connection timed out
DeviceNet Network Status Steady red Duplicate MAC ID or bus-off: check addresses, media and data rate

Source: pp. 4-9 to 4-10.

Checks, step by step

  1. Record the code before any reset: E and both digits, the drive catalog number (-SE, -DN or neither) and the LED states.
  2. Power faults (E09, E35, E37): measure AC on all phases at the drive.
  3. E05 and E34: for E05, with all power and motor connections removed, check continuity from the DC bus to U, V and W (p. 4-4). For E34, disconnect the motor cable and enable with the current limit set to 0; if the fault clears, the cause is wiring or the motor (p. 4-7).
  4. Encoder faults (E11, E20, E21, E30, E31): cable shield and twisted pairs, routing away from noise, grounds and bonding. E31 Encoder Data means corrupted encoder data: replace the motor or encoder (p. 4-7).
  5. Regeneration (E10, E40, E41): deceleration profile and the shunt resistor, including its fuse.
  6. SERCOS faults (E43, E50, Network LED): enable input, node addresses and fiber cables.

Clearing faults safely

Find and correct the cause before operating again; do not defeat or override the drive fault circuits. Before working on the drive, measure the DC bus voltage or wait the time on the drive warning label (p. 4-2). Clearing a fault can restart the machine: follow the plant's permit and lockout rules.

When it is hardware

  • PWR indicator off with power applied and the supply checked: internal power supply malfunction, call Rockwell (p. 4-3).
  • E01 Non-Volatile Memory Endurance Exceeded: unrecoverable; the drive must go back to the factory (p. 4-3).
  • E14 on SERCOS (-SE) drives, SERCOS Hardware Fault: contact Rockwell. On DeviceNet (-DN) drives E14 means the DeviceNet network is broken: troubleshoot the network first (p. 4-5).
  • Steady red Module Status LED: unrecoverable fault (pp. 4-9 to 4-10).

Planning the replacement

Ultra3000 drives are discontinued, so a fault that points to hardware is a good moment to plan the move to a current drive. The replacement Rockwell lists for each 2098-DSD catalog number is on its end-of-life page, and the migration options are in Kinetix servo drive migration. For an engineer on site: breakdown support.

Frequently asked questions

How do I read an Ultra3000 error code?

The seven-segment display shows an E, then flashes the two-digit code one digit at a time, and repeats until the problem is cleared (2098-IN003E-EN-P, p. 4-3). E, 2, 0 means E20.

What does a flashing L mean on an Ultra3000?

The drive is in an overtravel condition and motion restrictions are in effect. It is not an error code (p. 4-3).

What is error E20 on an Ultra3000?

E20 Motor Encoder State Error means the motor encoder made an illegal transition. Check for noise: shielded twisted-pair cable, routing, grounds and the high-frequency bond of the motor to the panel; replace the motor or encoder if it continues (p. 4-6).

What does E34 Ground Fault mean on an Ultra3000?

A wiring error, a motor internal ground short or an internal fault. Disconnect the motor power cable and enable with the current limit set to 0: if the fault clears, the cause is wiring or the motor; if it remains, call Rockwell (p. 4-7).

Sources

  • Rockwell Automation, 2098-IN003E-EN-P, Ultra3000 Digital Servo Drive Installation Manual, 04/2004 — chapter 4 "Troubleshooting Status Indicators" (pp. 4-1 to 4-10)
  • Rockwell Automation, 2098-DU003B-EN-P, Ultra3000 Digital Servo Drive Installation Manual documentation update, 09/2006 — error code E44 (p. 2)

Read 13 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.