A Kinetix 7000 high-power servo drive (Bulletin 2099) reports a fault on the seven-segment "Fault/Status" display on the front of the drive: it shows an E, then flashes the two-digit error code one digit at a time, and repeats until the error is cleared (
The display at power-up
At power-up the display first flashes the Sercos node address, then steps through the phases until phase 4 (p. 127). Where it stops tells you where to look (p. 144):
| Display | Meaning | What to check |
|---|---|---|
| Segments cycling (phase 0) | Looking for a closed Sercos ring | Fiber-optic cables: the ring enters at Rx and leaves at Tx; baud rate switch |
| Fixed 1 (phase 1) | Looking for active nodes | Node addressing on the drive and in RSLogix 5000 |
| Fixed 2 (phase 2) | Logix configuring nodes | Drive model selected in the program against the installed hardware |
| Fixed 3 (phase 3) | Drive configuring its own parameters | Motor catalog number in the program, feedback cable at the MF connector |
| Fixed 4 (phase 4) | Configured, Sercos ring active | — |
Stuck at phase 3 with a "Pseudo Key Failure" in RSLogix 5000 usually means the motor selected in the program does not match the motor installed (p. 144).
Front-panel status indicators
| Indicator | State | Meaning |
|---|---|---|
| Drive | Steady red | Drive faulted: read the seven-segment display |
| Comm | Off | No communication: loose or broken fiber, or receive and transmit swapped |
| Comm | Flashing green | Still establishing communication, or the node address switch does not match the controller |
| Bus | Off | No DC bus power, or a fault; on a follower drive also "Common Bus Follow" not set |
| Bus | Alternating red-green | 24 V DC control power present, no bus power: check the 460 V AC connections |
| Bus | Flashing green | Bus up, axis disabled: no 24 V on the Hardware Enable Input ( |
| Bus | Steady green | Bus up, axis enabled |
Source: Tables 55–57 (p. 143). On a common-bus follower, the Bus indicator waits 2.5 seconds after DC bus voltage is applied before it flashes, so the leader can finish precharge (p. 143). The CP indicator is steady green when control power is applied at the CP terminal (p. 144); if the logic power indicator is off, check the 24 V DC control power at the CP connector (p. 126).
Common error codes
| Code | RSLogix 5000 message (HIM) | Usual causes | What to check |
|---|---|---|---|
| E04 | MotorOvertemp Fault (Motor Overtemp) | Motor thermal switch trips: high ambient or excessive current, wiring, wrong motor, mechanical failure | Continuous torque at ambient (40 °C max), cooling, wiring at MF, bearings, jams (p. 138) |
| E05 | DriveOvercurrent Fault (Power Fault) | Instantaneous overcurrent in the inverter: shorted motor cable or winding, drive too hot, above rating, failed component | Cable continuity, turn the motor by hand, vents and fan, lower acceleration (pp. 139, 147) |
| E07 | MotFeedbackFault (Motor Feedback Loss) | Feedback wiring open, shorted or missing | Encoder and wiring; run the Hookup test (p. 139) |
| E09 | BusUndervoltageFault (Bus Under Voltage) | Three-phase present but DC bus below 275 V DC (460 V system; p. 150 gives 275…560 V DC depending on line voltage, and Table 61 on p. 147 misprints the E09 trip point as 800 V DC); or bus dropped with an axis enabled, a phase lost | Level and stability of the AC input, all phases; disable the axis before removing power (p. 139) |
| E10 | DriveOvervoltageFault (Bus Overvoltage) | Excessive regeneration, motor driven by the machine; bus above 800 V DC (460 V system) | Deceleration profile, shunt module or regenerative converter, system size, line voltage (p. 139) |
| E18 | OverSpeedFault (Overspeed Fault) | Speed above 150 % of maximum; 100 % is the lesser of the user velocity limit and motor rated base speed | Cable noise, tuning, feedback device, velocity limits (p. 140) |
| E20 | MotFeedbackFault (Mtr Fdbk AQB) | Illegal state transition on the motor encoder | Shielded twisted-pair cable, routing, grounds; replace the motor/encoder (p. 140) |
| E30 | MotFeedbackFault (Motor Feedback Comm) | No communication with an intelligent (Stegmann) encoder on the motor feedback port | Motor selection, automatic identification support, encoder wiring (pp. 140, 147) |
| E34 | GroundShortFault (Ground Fault) | Excessive ground current in the converter: wiring error, motor ground short, internal fault | Motor and input power wiring; whether the control power is grounded (p. 140) |
| E35 | DriveUndervoltageFault (Precharge Fault) | Precharge failed: low AC input or internal fault | AC voltage on all phases (p. 140) |
| E37 | PowerPhaseLossFault (Phase Loss Flt) | Phase missing; axis still enabled when three-phase or common DC bus power was removed | Voltage and fusing on all phases and the DC bus; disable before removing power (pp. 141, 147) |
| E38 | SercosFault (Sercos Ring Flt) | Sercos ring lost after being active | Fiber-optic cable present and connected (p. 141) |
| E43 | DriveEnableInputFault (Drive Enable Flt) | Software enable with the enable input inactive, or the input dropped while enabled | Wiring and shielding of the enable input ( |
| E49 | DriveHardFault (Safe Torque Off HW Flt) | Safe Torque Off mismatch: loose wiring at SO, header not seated, +24 V DC missing | Terminations, SO header, +24 V DC; reset and run the proof test per |
| E50 | SercosFault (Sercos Same ADDR) | Duplicate node address on the Sercos ring | A unique node address on every drive (p. 141) |
| E72 | DriveOvertemp Fault (Drive Overtemp) | Inverter thermal switch: failed fan, hot cabinet, RMS current above rating, blocked airflow | Cabinet temperature, fan, airflow, motion profile (p. 142) |
| E109 | IGBT_TempFault (IGBTFLT) | IGBT junction temperature exceeded | Drive sizing; a higher kW drive (p. 142) |
| E111 | Regen_PS_OK | Regen_OK signal missing at pins 7 and 8 of the GPIO connector | The error on the regenerative power supply (RPS), then reset the system (p. 142) |
Codes not listed in the manual's Table 54 are RESERVED (p. 142). For E34 the manual also lists control-power fixes: remove the ground from the control power input, wire control power from main power as in Appendix B, or add an isolation transformer (p. 140).
Checks, step by step
- Record before any reset: the code, the Drive, Comm and Bus states, the Sercos phase at power-up and the catalog number (
2099-BM06-S to2099-BM12-S ). - Common DC bus: connected equipment can hold its own error data; when an
8720MC-RPS regenerative power supply provides the DC bus, check it first (p. 137). - Power faults (E09, E35, E37): measure AC on R (L1), S (L2), T (L3); the startup procedure prints 324…528 V AC for 460 V (p. 127), but the power specifications give 342…528 V AC rms, 380…480 V nominal (p. 150); 324 looks like a misprint, so use the p. 150 range.
- E05 (inverter overcurrent only): with all power and motor connections removed, check continuity from the DC bus to U, V and W; if there is continuity, look for wire fibers between terminals, otherwise send the drive for repair (p. 139). E34: disconnect the motor power cable and enable with the current limit set to 0: if the fault clears, the cause is wiring or the motor (p. 140).
- Feedback (E07, E20, E30, E63, E64): MF wiring, shields, routing, grounding; E63 and E64 are noise on the auxiliary and motor feedback cables when grounding does not follow the installation instructions (p. 141).
- Enable, safety and Sercos (E43, E49, E38, E50): 24 V at
IOD-2 , SO wiring, fiber Rx/Tx, node address switches.
How the axis reacts
Fault actions are set in Axis Properties, "Fault Actions" tab: Shutdown disables the drive and opens the contactor enable relay, Disable Drive lets the motor coast, Stop Motion stops under velocity loop control, and Status Only lets the drive keep operating (p. 146). Only E04, E06, E16, E19, E23, E43, E63/E64 and E72 are programmable; E05, E09, E10, E34 and E35 are Shutdown (pp. 147–148). If an axis reports a fault but the machine does not stop, check for Status Only.
Clearing faults safely
The Kinetix 7000 is a high-power drive (22 to 149 kW, p. 150), and the DC bus is the main hazard:
- DC bus capacitors can hold hazardous voltage after input power is removed. Before working on the drive, measure the DC bus voltage, or wait the full time on the warning label on the front of the drive (p. 137).
- The specifications give a DC bus discharge time of 3 minutes after main AC is removed (p. 150); for access to the ground jumper, the manual asks for at least 5 minutes and a check that no DC bus voltage remains (p. 77). Use the longer time and always measure.
- Ground test equipment such as an oscilloscope (p. 137). Do not defeat the drive fault circuits; correct the cause first (p. 137).
- Do not cycle power repeatedly: at most 4 power cycles per minute on the AC line and 2 on the DC bus (p. 150). After a disable, the axis cannot be re-enabled for 1.5 seconds (p. 145).
Clearing a fault can restart the machine: follow the plant's permit and lockout rules.
When it is hardware
- PWR indicator off with the supply correct: internal power supply malfunction, return for repair (p. 138).
- E05 with continuity from the DC bus to U, V or W and no wire fibers: send the drive for repair (p. 139). E34 still present with the motor cable removed: contact Rockwell (p. 140).
- E54 Excessive Current Feedback Offset, if it persists: return to Rockwell (p. 141).
- E67, E71, E78: cycle power, then replace the module if it persists; E80: replace the module if it persists; E69 and E70: load defaults, save, cycle power or reset, then replace if it persists; E110 EEPROM_Fault, if it persists, and E72 with a failed fan: replace the module (p. 142).
Planning the replacement
The Kinetix 7000 is discontinued, so a fault that points to hardware is a good moment to plan the move to a current drive. The replacement Rockwell lists for each
Frequently asked questions
How do I read a Kinetix 7000 error code?
The seven-segment display shows an E, then flashes the two-digit code one digit at a time, and repeats until the error is cleared (
How long should I wait after switching off a Kinetix 7000 before opening it?
Measure the DC bus voltage or wait the full time on the warning label on the front of the drive (p. 137). The specifications give a DC bus discharge time of 3 minutes after main AC is removed (p. 150), and for access to the ground jumper the manual asks for at least 5 minutes and a check that no voltage remains (p. 77).
What does E09 BusUndervoltageFault mean on a Kinetix 7000?
With three-phase power present, the DC bus is below 275 V DC on a 460 V system, or the bus dropped while an axis was enabled, for example after a phase loss. Check the level and stability of the AC input and all phases, and disable the axis before removing power (p. 139).
How do I fix E34 Ground Fault on a Kinetix 7000?
Check the motor and input power wiring, then disconnect the motor cable and enable with the current limit set to 0: if the fault clears, the cause is wiring or the motor; if it remains, contact Rockwell. Also check whether the control power is grounded (p. 140).
Sources
- Rockwell Automation,
2099-UM001G-EN-P , Kinetix 7000 High Power Servo Drive User Manual, 12/2022 — pp. 77, 126–127, 150, chapter 6 "Troubleshoot the Kinetix 7000 Drive System" (pp. 137–148)
Read 13 November 2026. This article paraphrases the sources and does not quote them; read the original documents before designing or working on a system. Links open the latest edition in Rockwell's literature library; page numbers refer to the edition cited.